Wood crib fire tests to evaluate the influence of extinguishing media and jet type on extinguishing performance at close range

  • This paper is intended to be the first study to discuss the fire suppressing performance of the four most common extinguishing media under the same reproducible conditions. The tests were performed in bench-scale and used standardized 5A wood cribs as well as a miniature extinguishing system with a liquid flow rate of 1.4 lmin−1. The tests results present a consistent overview of the fire suppression efficacies of water, water with a foaming agent, nozzle-aspirated foam and compressed air foam. Depending on their jet types, the cooling capabilities of the extinguishing media water and water with a foaming agent were compared to the cooling capability of a full Jet of wet, general and dry foams. The results show that compressed air foam suppressed fire most effectively under the test conditions. Because of the convoluted crib structure, water and water with foaming agents used from a distance are more effective in the form of a full jet rather than a spraying jet. At close range,This paper is intended to be the first study to discuss the fire suppressing performance of the four most common extinguishing media under the same reproducible conditions. The tests were performed in bench-scale and used standardized 5A wood cribs as well as a miniature extinguishing system with a liquid flow rate of 1.4 lmin−1. The tests results present a consistent overview of the fire suppression efficacies of water, water with a foaming agent, nozzle-aspirated foam and compressed air foam. Depending on their jet types, the cooling capabilities of the extinguishing media water and water with a foaming agent were compared to the cooling capability of a full Jet of wet, general and dry foams. The results show that compressed air foam suppressed fire most effectively under the test conditions. Because of the convoluted crib structure, water and water with foaming agents used from a distance are more effective in the form of a full jet rather than a spraying jet. At close range, spraying jets multiply their effectiveness. A slight difference can be observed in the cooling performance of extinguishing foams that use foaming agents from different manufacturers. The paper establishes a link between the foaming agent's cooling capability and its wetting power by relating the results of wood crib fire tests according to DIN EN 3–7 and findings from laboratory immersion tests compliant with DIN EN 1772.zeige mehrzeige weniger

Volltext Dateien herunterladen

  • Publica-Version.pdf
    eng

Metadaten exportieren

Weitere Dienste

Teilen auf Twitter Suche bei Google Scholar Anzahl der Zugriffe auf dieses Dokument
Metadaten
Autor*innen:Tim Rappsilber, Simone KrügerORCiD, Philipp Below
Dokumenttyp:Zeitschriftenartikel
Veröffentlichungsform:Graue Literatur
Sprache:Englisch
Titel des übergeordneten Werkes (Englisch):Fire Safety Journal
Jahr der Erstveröffentlichung:2019
Organisationseinheit der BAM:7 Bauwerkssicherheit
7 Bauwerkssicherheit / 7.5 Technische Eigenschaften von Polymerwerkstoffen
Verlag:Elsevier Ltd.
Jahrgang/Band:106
Erste Seite:136
Letzte Seite:145
DDC-Klassifikation:Technik, Medizin, angewandte Wissenschaften / Ingenieurwissenschaften / Ingenieurbau
Freie Schlagwörter:Druckluftschaum; Krippe; Löschen
CAF
Themenfelder/Aktivitätsfelder der BAM:Infrastruktur
Infrastruktur / Fire Science
DOI:10.1016/j.firesaf.2019.04.014
ISSN:0379-7112
ISSN:1873-7226
Verfügbarkeit des Dokuments:Datei im Netzwerk der BAM verfügbar ("Closed Access")
Datum der Freischaltung:20.05.2019
Referierte Publikation:Ja
Datum der Eintragung als referierte Publikation:04.07.2019
Einverstanden