Formaldehyde is considered as carcinogenic and is emitted from particleboards and plywood used in toy manufacturing. Currently, the flask method is frequently used in Europe for market surveillance purposes to assess formaldehyde release from toys, but its concordance to levels measured in emission test chambers is poor. Surveillance laboratories are unable to afford laborious and expensive emission chamber testing to comply with a new amendment of the European Toy Directive; they need an alternative method that can provide reliable results. Therefore, the application of miniaturised emission test chambers was tested. Comparisons between a 1 m3 emission test chamber and 44 mL microchambers with two particleboards over 28 days and between a 24 L desiccator chamber and the microchambers with three puzzle samples over 10 days resulted in a correlation coefficient r2 of 0.834 for formaldehyde at steady state. The correlation between the results obtained in microchambers vs. flask showed a high variability over 10 samples (r2: 0.145), thereby demonstrating the error-proneness of the flask method in comparison to methods carried out under ambient parameters. An exposure assessment was also performed for three toy puzzles: indoor formaldehyde concentrations caused by puzzles were not negligible (up to 8 μg/m3), especially when more conservative exposure scenarios were considered.
This study shows that formaldehyde Emission results in micro-scale emission chambers are comparable with results in bigger chambers both for particle boards and wooden toys. On the contrary, the WKI flask method was leading to more variable results depending on sample geometry. Thus, microchambers could be used for reliable routine market surveillance. An exposure assessment led to noticeable formaldehyde indoor air concentration values, pointing out the need for an effective Surveillance of such samples.
The ISO 16000-6 standard describes a method for the determination of volatile organic compounds (VOCs) in indoor and test chamber air by sorbent-based active sampling, thermal desorption and gas chromatography coupled with mass spectrometry (GC/MS). It also gives directions to adapt this methodology to very volatile organic compounds (VVOCs). Indeed, toxicologically based guideline values are being implemented for these compounds and it becomes necessary to measure them. But a comprehensive and robust measurement method is lacking. Investigations on the use of gaseous standards, the suitability of chromatography columns, the suitable sorbent combinations and the water removal are required. The talk will highlight the points that need to be explored towards the standardisation of a suitable procedure and provide appropriate preliminary results.
Since 1997, the Committee for Health-related Evaluation of Building Products (AgBB) has been developing the basis for building regulations for protection against indoor health risks that may arise when building products are used. In 2009, the AgBB decided to include relevant VVOCs in the assessment procedure. The ISO 16000-6 (2021) states that the use of the thermal desorption gas chromatography technique is appropriate for VVOCs, if adaptations are considered. However, a suitable method for the trustworthy quantification of VVOC emissions from building products and in the indoor air is still missing.
This webinar will present the results of a research project on the development of a procedure for VVOC analysis:
• identification of the gaps towards standardization
• investigations on gas standards and the suitability of chromatography columns
• investigations on sorbent combinations and water management
• validation of the method and screening of VVOC emissions from building products.