Filtern
Erscheinungsjahr
- 2013 (2) (entfernen)
Dokumenttyp
- Zeitschriftenartikel (2) (entfernen)
Sprache
- Englisch (2)
Referierte Publikation
- ja (2)
Schlagworte
- Coal (1)
- Energy carriers (1)
- Fire (1)
- Freezing (1)
- Hazardous materials (1)
- Mitigation (1)
- Risk (1)
- Storage (1)
- Underground storage (1)
Observed autoignition events and extinguishing the resulting smouldering fires in an underground storage system of a coal-fired power plant have provided insight into the array of contributing variables, and some experience on quantifying the risk with alternative scenarios of event initiation, progress and potential mitigation. Although the first attempts to quantify the risk suggest high sensitivity to the sequence of action taken after fire alarm, and no similar storage sites really exist, some recommended preventive, corrective and other mitigating activities can be at least partly defined and improved by using the cumulative experience and parallel efforts in other closed or underground storage sites. However, there are also so-called black (or at least grey) swans: unexpected events for which the facility may be poorly prepared for. In the case of the underground storage silos, such an event was experienced when incoming cold coal during a harsh winter season froze the sewer system that normally protects the stored coal from seepage water. With blocked normal bypass, the seepage water found its way to the coal silos and created large clumps of icy coal that blocked the coal conveyors. Although freezing weather is not unusual at high-latitude power plants, the common methods to combat freezing of coal are mainly useful for open storage sites and above-ground transport. Options for mitigation are discussed, as well as the event chain leading to an event that had never previously occurred. The case is discussed from the point of view of options to prepare for rare or unforeseen events.
Approaches towards a generic methodology for storage of hazardous energy carriers and waste products
(2013)
Energy carriers – either conventional or 'new' ones – have to be provided in large amounts to meet the requirements of permanent availability and reliable supply of electricity. Depending on their state of aggregation, energy carriers are either stored in large masses (if solid or liquid) or at elevated pressures (if gaseous). Both impose the hazard of large-scale fire, in the latter case additionally the danger of explosion or unintended release. Very similar hazards occur for wastes. Solid wastes are present in large masses and only a small part is recycled. Most of the solid wastes are used in energy conversion. The main gaseous waste is CO2. During capturing also the hazard of unintended release exists. In this article, existing approaches for safe storage and fire prevention are discussed and a generic methodology is outlined. This methodology consists of the following steps:
gaining knowledge about the behaviour of the material stored (reactivity, thermal stability, etc.),
assessing the environmental conditions for the storage site (neighbourhood, safety distances, etc.),
assessment of prospective consequences of an incident and
development of individual loss prevention conceptions.
All steps require both experimental testing and theoretical considerations about accident scenarios as integral parts of the methodology.