Fireballs of liquid organic peroxides differ from those of liquid hydrocarbon fuels. Modified equations for predicting the fireball diameter, height, surface emissive power and the duration in dependence of the fuel mass are presented for di-tert-butyl peroxide. They base on 13 steel drum tests with fuel masses from 10 kg to 168 kg. Moreover, computational fluid dynamics simulations are performed using the laminar flamelet approach and a statistically turbulence treatment. Fireballs involving peroxide from 10 kg to 80 kg were simulated and their properties compared to the experimentally developed models. The deviations of each property are partially compensating each other leading to an adequate prediction of thermal safety distances for both, a time-independent and a time-averaged treatment. Simulations prove to be a good tool for predicting thermal radiation hazards of fireball scenarios.
The thermal radiation impact of organic peroxide fireballs is experimentally assessed using an infrared camera. Fireballs are generated while liquid peroxide filled steel drums are subjected to gas burner fire at different heating rates. Three large burning clouds are observed with varying flame characteristics. Thermal radiation properties are assessed by infrared images with the presented methods. Despite of the two-dimensional temperature fields, the flames are treated and characterized as three-dimensional objects. Fireball diameters and heights are calculated based on a representing radiating sphere with the same cloud volume. By the use of the solid flame model and assumptions for emissivity and transmissivity, heat fluxes and thermal radiation doses against distance are predicted. Thermal safety distances are presented based on the maximum irradiance and the allowed exposure time. The validation of the maximum and time-dependent radiation fields is achieved through heat flux sensors in varying distances to the fireball. The results prove the use of an infrared camera and a volume based size calculation to fully assess the thermal radiation hazards of fireballs.
Organic peroxides are capable to form fireballs with explosive violence. Only fireball models for liquid hydrocarbon fuels are available for the assessment of the thermal radiation properties. Because the development of such fireballs usually differ from those of organic peroxides the properties need to be characterized by modified equations. In this study liquid organic peroxide fireballs from 16 kg to 155 kg substance masses are characterized and compared to selected existing correlations. Flame characteristics and irradiances are measured with infrared cameras and heat flux sensors. All fireballs are consequences of simulated worst case scenarios where filled steel drums are engulfed by fire with varying heat impact. The differences of the given semi-empirical equations and the presented experimental work are explained. A new model is proposed for organic peroxide fireballs by modifying the constants of the known equations. The thermal radiation impact and safety distances are calculated and compared.
Acetylene pressure cylinders are widely used in the industrial sector for welding, flame cutting, or heating.
Sometimes during work, not only with acetylene cylinders, fires occur and in this case the risk of destruction increases and the behavior of such an exposed cylinder is unpredictable. The purpose of this study is to identify those critical conditions when acetylene cylinders burst and explode in fires. In the present study, acetylene cylinders were exposed to fire conditions. For this purpose, a woodpile as a source of fire was chosen, tested, and evaluated. In addition to the fire condition, this option guaranteed reproducibility and similar conditions for all tests. The individual cylinders were equipped with thermocouples measuring the shell temperature, and half of them were prepared in order to measure the temperatures inside the cylinder. An important factor was the measurement of the amount of pressure that was achieved during the destruction of the cylinder. For this purpose, a pressure transducer was attached to the outlet of the cylinder valve. Exposed to direct fire, they can explode in 10 min, which was confirmed. The critical pressure of 40 bar has been reached in 6 min, followed by destruction after 7 min in fire. Cylinders with internal thermocouples were destroyed when lower pressure was achieved. This confirms the fact that any change of the pressure cylinder affects the original properties. After the tests, the fragments of the selected cylinders were subjected to material tests. The results obtained in these tests are the main source of information for understanding the behavior of acetylene cylinders in fire and the possibility of increasing the safety of intervening rescue services in an emergency.