High-throughput fire tests and weathering-induced degradation behaviour of intumescent coatings
(2018)
In this work, the weathering-induced degradation of intumescent coatings was investigated by a systematic and comprehensive approach. A mechanism is revealed that is proposed to be responsible for the loss of function of intumescent coatings induced by weathering.
First, the thermal decomposition of artificially weathered intumescent coatings was examined. To get a better understanding of the weathering and ageing phenomena, the degradation behaviour of the single ingredients during the weathering process was investigated, as well as their chemical and physical interactions. For the systematic approach, the materials that are essential for intumescence (ammonium polyphosphate, pentaerythritol, titanium dioxide, melamine and the binder) are treated with moisture, elevated temperature and UV radiation.
Thermogravimetry (TG) and IR spectroscopy were used to compare the initial samples with their different grades of weathering. We demonstrate that ammonium polyphosphate, melamine and the binder are mainly responsible for the ageing process. Further, it was demonstrated that TG and IR spectroscopy are suitable measuring methods to detect the effects of weathering on intumescent coatings.
Finally, a small-scale fire test procedure is introduced. Based on the reduction of the sample size, up to 50 samples can be tested in a single fire test. The results of this fire test have the same quality as the results from standard intermediate fire tests corresponding to DIN 4102-8.
The residual post-fire mechanical properties of fiber-reinforced epoxy composites are influenced by their fire residues after burning. This study uses intumescent/low-melting glass flame retardants to tailor fire residues in epoxy resin. Processibility of prepregs and their quality are analysed for transfer of the flame-retardant epoxy resins to layered glass-fiber reinforced composites. Minimal effects were found on the pre-fire flexural strengths of the composites due to low loading of the flame retardants. However, when transferred to glass-fiber reinforced composites, the fire residues diminish significantly. Further studies are required to improve theoretical and experimental estimations of the post-fire mechanics of the composites.
In den letzten Jahrzehnten wurde die Degradation der polymeren Matrix von flammgeschützten Polymeren eingehend untersucht. Erst in den letzten Jahren jedoch hat sich die Frage der Lebensdauer der Funktionalität des Flammschutzes selbst als wichtige Fragestellung herauskristallisiert, z.B. bei Kabeln. Deshalb sollte diese Fragestellung durch systematisch-variierte künstliche Klima- und Bewitterungstests an flammgeschützten Polymerwerkstoffen untersucht werden.