Filtern
Dokumenttyp
Schlagworte
- Emission test chamber (8)
- Radon exhalation (6)
- VOC (4)
- Building material (3)
- Radon (3)
- Radon measurement (3)
- Gas mixing device (2)
- Indoor air quality (2)
- Reference material (2)
- Adsorptive wall material (1)
Organisationseinheit der BAM
Paper des Monats
- ja (1)
This study investigated the adaptation of the state-of-the-art test procedure for the determination of emissions of volatile organic compounds (VOC) from materials into indoor air to test for the radon exhalation from stony construction products. A complete robustness validation including all relevant parameters showed that the procedure can be well applied by testing institutes already holding available the required VOC testing infrastructure that solely needs to be complemented by calibrated commercial radon measurement instrumentation. When measurements of the radon exhalation from construction materials become mandatory by law, test capacity can easily be applied. This work can serve as a recommendation for the European standardisation that still is on hold in this point.
The inhalation of radon (222Rn) decay products is the leading cause of lung cancer apart from tobacco smoking. Besides the permeation of radon from the subsoil through the basement as main source of radon in indoor air, also building materials have to be taken into consideration, especially at low air change rates in buildings. The Construction Products Regulation (EC, 2010) gives essential requirements for construction works regarding the release of dangerous substances such as toxic gases and radiation to which radon can be assigned. The recently adopted Basic Safety Standards Directive (EC, 2013), which has to be ratified by each European member state in between the next three years sets reference levels for indoor radon concentrations for the first time. In research project financed by the German Ministry for the Environment, Nature Conservation, Building and Nuclear Safety a practical, reliable and easily applicable test procedure for the determination of radon exhalation from building materials – based on ISO 16000-9 (ISO, 2006) and CEN/TS 16516 (CEN, 2013) – should be developed. In contrast to the static test procedure published by Richter et al. (2013), dynamically operated test chambers shall be foregrounded. First results of this study are presented, focused on the reliable measurement of radon background concentration and the selection of suitable radon test devices, representing the basic elements of the subsequent work.
Compared to the intended EU reference level of 300 Bq m−3 for indoor radon concentrations, the contribution of building materials appears to be low. Considering the recommended limit of 100 Bq m−3 by WHO, their contribution is supposed to be relevant, especially at low air exchange rates. This study as part of a two-part research project investigated the suitability of direct low level 222Rn measurement under simulated indoor conditions with commercial radon monitors and dynamically operated emission test chambers. Active measuring devices based on ionisation or scintillation chambers with 1-σ uncertainties below 8.6% at 20 Bq m−3 were found to be best suitable for a practical test procedure for the determination of radon exhalation rates of building materials. For the measurement of such low concentrations, the knowledge of the accurate device background level is essential.
Emission testing of products is currently a rapidly increasing field of measurement activity. Labelling procedures for construction products are based on such emission test chamber measurements and hence measurement performance should be verified. A suited procedure for this purpose is the testing of one unique homogenous material in different laboratories within a Round Robin Test (RRT). Therefore, it is useful to have a reference material which can be used within inter-laboratory studies or as part of the quality management system to ensure comparable results. Several approaches on the development of reproducibly emitting materials have been published. These have in common only to emit a single VOC – toluene. Two further research studies carried out by BAM aimed to develop reference material for emissions testing containing one or more VOC in a single material. The first approach was a doped lacquer with Volatile and Semi-Volatile Organic Compounds (VOC/SVOC) and the second was Thermoplastic Polyurethane (TPU) or a Squalane/Paraffin mixture. Results received with the lacquer based material were presented in more detail.
Entwicklung einer praxisnahen Prüfmethode zur Bestimmung der Radon-Exhalation aus Bauprodukten
(2012)
Development of a multi-VOC reference material for quality assurance in materials emission testing
(2015)
Emission test chamber measurement is necessary to proof building materials as sources of volatile organic compounds (VOCs). The results of such measurements are used to evaluate materials and label them according to their potential to emit harmful substances, polluting indoor air. If only labelled materials were installed indoors, this would improve indoor air quality and prevent negative impacts on human health. Because of the complex testing procedure, reference materials for the quality assurance are mandatory. Currently, there is a lack of such materials because most building products show a broad variation of emissions even within one batch. A previous study indicates lacquers, mixed with volatile organic pollutants, as reproducible emission source for a wide range of substances. In the present study, the curing of the lacquer-VOC mixture inside micro-chambers was optimised. Therefore, the humidity and the chamber flow were varied. Typical indoor air pollutants with a wide range of volatilities, for example, styrene, n-hexadecane, dimethyl and dibutyl phthalate were selected. It turned out that, under optimised curing parameters inside the micro-chamber, their emission can be reproduced with variations of less than 10 %. With this, a next important step towards a reference material for emission testing was achieved.
With a gas mixing system (GMS) developed in our laboratory we created a gas mixture of
four substances. Adsorptive wall materials of four different compositions were exposed to this
gas mixture, consisting of 1-pentanol, hexanal, butyl acetate and n-decane. Aim of this study
was to scrutinize the ability of these samples to reduce the concentration of the supplied gas.
This capacity is expressed in the sorption flux F or area specific adsorption rate respectively.
The test was performed referring to a draft of ISO 16000-24.
Emissions of building materials might have negative impact on human health and well-being. In the EU-funded research project H-House more than 30 natural materials (earthen dry boards and plasters, bio-based insulation materials made of wood, flax, reed, straw, etc.) used for renovation and refurbishment were tested regarding emissions of VOC, formaldehyde and radon. Different to ordinary emission tests on single materials this study focuses on the emissions from complete wall assemblies. Therefore, specially designed test chambers were used allowing the compounds to release only from the surface of the material facing indoors. The testing parameters were chosen in order to simulate model room conditions. The emission results were finally evaluated using the AgBB evaluation scheme, a procedure currently applied for the approval of flooring materials in Germany.
Natural building materials for interior fitting and refurbishment - What about indoor emissions?
(2021)
Indoor air quality can be adversely affected by emissions from building materials, consequently having a negative impact on human health and well-being. In this study, more than 30 natural building materials (earth dry boards and plasters, bio-based insulation materials, and boards made of wood, flax, reed, straw, etc.) used for interior works were investigated as to their emissions of (semi-) volatile organic compounds ((S)VOC), formaldehyde, and radon. The study focused on the emissions from complete wall build-ups as they can be used for internal Partition walls and the internal insulation of external walls. Test chambers were designed, allowing the compounds to release only from the surface of the material facing indoors under testing Parameters that were chosen to simulate model room conditions. The emission test results were evaluated using the AgBB evaluation scheme, a procedure for the health-related evaluation of construction products and currently applied for the approval of specific groups of building materials in Germany.
Seventeen out of 19 sample build-ups tested in this study would have passed this scheme since they generally proved to be low-emitting and although the combined emissions of multiple materials were tested, 50% of the measurements could be terminated before half of the total testing time.