In order to determine the remaining life-time of reinforced concrete infrastructure like marine constructions, bridges or parking decks a fast and reliable detection of harmful species is necessary. If, as an example chlorine exceeds a specific concentration threshold, the result can be pitting corrosion of the reinforcement, which affects the stability and lifetime of building structure. In cooperation with industrial partners and BAM a mobile LIBS system for the on-site measurements has been developed. The mobile system uses a low energy laser with a pulse energy of 3 mJ and a NIR-spectrometer in combination with a scanner for two-dimensional mapping (140 x 170mm).
This work presents the mobile LIBS system, the calibration and an on-site applications in a parking garage. A correlation between surface measurements on a parking deck and ingress profiles obtained due to concrete cores are presented. LIBS results using the mobile LIBS system are able to provide in-time information about the Cl concentration and can therefore be used for quality assurance during reinstatement work.
In civil engineering concrete is the most used building material for making infrastructures like bridges and parking decks worldwide. It is as a porous and multiphase material made of aggregates with a defined grain size distribution, cement and water as well as different additives and admixtures depending on the application. Different grain sizes are important to ensure the needed density and compressive strength.
The resulting porous cement matrix contains a mixture of flour grains (aggregates with a grain size below 125 lm) and cement particles (particle size≈50lm). Harmful species like chlorides may penetrate together with water through the capillary pore space and may trigger different damage processes. The damage assessment of concrete structures in Germany is estimated due to the quantification of harmful elements regarding to the cement content only. In the evaluation of concrete using LIBS a two-dimensional scanning is necessary to consider the heterogeneity caused by the aggregates. Therefore, a LIBS system operating with a low energy NdCr:YAG laser, a pulse energy of 3 mJ, a wavelength of 1064 nm, a pulse width of 1.5 ns and a Repetition rate of 100 Hz has been used. Different Czerny-Turner spectrometers with CCD detectors in the UV and NIR range have been used for the detection. Large aggregates (macro-heterogeneity) can be excluded from the evaluation, whereas small aggregates in the range of the laser spot size (flour grains) cannot be spatially resolved. In this work the micro heterogeneity caused by flour grains and their impact on the quantification with LIBS will be discussed. To analyze the effect of changing grain sizes and ratios, the ablation behavior has been determined and compared. Samples with defined grain sizes were made and analyzed using LIBS.
The grain size distributions were analyzed with laser diffraction (LDA).
The durability and the lifetime of reinforced concrete structures can be drastically reduced by the influence of damage processes. One of the most common causes is chloride-induced corrosion, which is triggered by increased chloride content near the reinforcement. In a study, the chloride content should be determined directly at corrosion areas. The LIBS system used consists of a micro-chip laser (3 mJ, 100 Hz, 1.5ins) and two compact spectrometers covering the wavelength range of 177-355 nm (UV) and 750-940 nm (NIR). The analysis of the chloride content was carried out via the atomic chlorine spectral line 837.59 nm, using helium for signal amplification. Calibrations were carried out for quantitative chlorine measurements with 15 reference samples in the working range of 0.05 to 6.00 wt% chlorine. The calibration of the LIBS system was done according to DIN 32 645 and was tested for linearity. The determination of the quantitative chlorine contents was carried out on samples which were broken and thus have a high surface roughness. This requires real time correction of the focus point to compensate for the roughness of the samples. The poster shows spatially resolved element distributions and determined quantitative chloride concentrations near the corrosion Areas.
For the determination of the remaining life-time and the degree of damage of reinforced concrete structures such as marine construction, bridges or parking decks, a highly precise measurement of harmful species is also required for trace elements. One of the most interesting elements is chlorine, because above a certain threshold corrosion is triggered. To increase the intensity of the chlorine line, helium is usually used, which is costly. To overcome this problem, low electrical discharge reheating is used which operates in air atmosphere. A comparison between results obtained by measuring with helium and reheating by electrical discharge is presented. The performance is compared by the resulting calibration curves and the calculated limit of detection obtained by 15 reference samples based on cement with NaCl. Concentrations of reference samples range from 0.05 to 2.5 wt% chlorine.
The Laser-induced Breakdown Spectroscopy (LIBS) is an useful analytical technique for the chlorine detection in building materials, specifically in the reinforcement concrete. If chlorine exceeds a specific concentration threshold, the result can be pitting corrosion of the reinforcement, which affects the stability and lifetime of building structures like marine constructions, bridges or parking decks. The critical chlorine content based to cement is 0.4 wt.-% based to the cement for reinforced concrete. The ingress of chlorides from sea water or de-icing salt leads to corrosion of the reinforcement.
The chlorine spectral line Cl I at 837.59 nm shows a good performance in helium atmosphere. For measurements without helium we used a electric discharge setup to reheat the Laser-induced plasma with a voltage below 100 V. In this case the reheating shows an increasing chlorine emission in air atmosphere.
This work shows chlorine calibration curves with LIBS in a helium flow and LIBS with electric discharge reheating in air atmosphere. The determination of the limit of detection (LOD) for both setups and the measurement results of a drill core sample with a quantitative chlorine ingress profile will be presented.
A big part of the infrastructure is made of concrete, which is a multiphase system made of cement, aggregates, water and pores. Concrete is often used in combination with steel as reinforced concrete. Environmental influences, especially the ingress of harmful ions in combination with the ingress of water, trigger different damage processes which reduce the designed lifetime of a structure. The ingress of chlorides from de-icing salt or sea water leads to corrosion of the reinforcement. In addition, the carbonation of the concrete may trigger the corrosion of the reinforcement. The ingress of alkalis from deicing salts may cause the expansion of the amorphous silica aggregates (alkali-silica reaction) through
formation of a swelling gel of calcium silicate hydrate if water is present. The ingress of sulphates may cause spalling of the concrete surface due to ettringite formation.
For the standard procedure in civil engineering cores are taken, cut in slices, grinded and the obtained homogenized powder is solved in acid and investigated by standard procedures.
BAM has developed the LIBS technique for the 2D evaluation of the chemical composition of concrete. The technique is established for automated laboratory use with high numbers of samples to investigate transport processes of harmful species (Cl-, CO2 , SO4 2-and alkalis) in concrete. Information about ingress depth and the quantitative values are important to estimate the remaining lifetime of the infrastructure. LIBS is a surface technique. To get information about the ingress depth, a drill core has to be taken and cut in the middle. The measurements are carried out at the cross section. The main advantages of LIBS are the direct measurement on the surface of the concrete, fast analysis (sample rate 100 Hz) with a spatial resolution of up to 100 µm, the consideration of the heterogeneity of the concrete and the possibility of automated measurements which save a lot of manpower and time. As an example the investigation of ingress profiles for standard diffusion and migration tests in civil engineering takes hours in comparison to just a few minutes using LIBS. At the same time a 2D-evaluation provides information about hot spots of elemental concentration which may not be found by standard methods.
The state of the art of LIBS technique for applications in civil engineering will be presented, including typical results of 2D investigation of concrete in laboratory. The performance is also demonstrated by examples for onsite applications using a mobile LIBS system. The road map to standardization is presented as well.
For the damage assessment of reinforced concrete structures the quantified ingress profiles of harmful species like chlorides, sulfates and alkali need to be determined. In order to provide on-site analysis of concrete a fast and reliable method is necessary. Low transition probabilities as well as the high ionization energies for chlorine and sulfur in the near-infrared range makes the detection of Cl I and S I in low concentrations a difficult task. For the on-site analysis a mobile LIBS-system (k = 1064 nm, Epulse ≤ 3 mJ, t = 1.5 ns) with an automated scanner has been developed at BAM. Weak chlorine and sulfur signal intensities do not allow classical univariate analysis for process data derived from the mobile system. In order to improve the analytical performance multivariate analysis like PLS-R will be presented in this work. A comparison to standard univariate analysis will be carried out and results covering important parameters like detection and quantification limits (LOD, LOQ) as well as processing variances will be discussed (Allegrini and Olivieri, 2014 [1]; Ostra et al., 2008 [2]). It will be shown that for the first time a low cost mobile system is capable of providing reproducible chlorine and sulfur analysis on concrete by using a low sensitive system in combination with multivariate evaluation.
Periodic mapping of reinforcement corrosion in intrusive chloride contaminated concrete with GPR
(2014)
This paper presents an experimental effort for developing a novel reinforcement corrosion monitoring technique based on Ground Penetrating Radar (GPR). Experiments were carried out to periodically monitor the accelerated reinforcement corrosion process with GPR. The data were processed in both time and timefrequency domains to investigate the tendencies of GPR signal attribute changes related with corrosion, moisture and chloride contamination. Data processing methods were proposed to visualize the reinforcement corrosion and chloride distribution with target specified signal attribute mapping. Half-Cell Potential (HCP) and Laser-Induced Breakdown Spectroscopy (LIBS) methods were employed to verify the GPR observations.
The effect of particle grain sizes in different cement-based mixtures on the laser-induced plasma evolution is studied using two experimental methods: (i) temporal and spatial evolution of the laser-induced shock wave is investigated using shadowgraphy and two-dimensional plasma imaging, and (ii) temporal and spatial distribution of elements in the plasma is investigated using two-dimensional spectral imaging. This study is motivated by the interest in applying laser-induced breakdown spectroscopy (LIBS) for chemical analysis of concrete, and subsequently obtain information related to damage assessment of structures like bridges and parking decks. The distribution of grain sizes is of major interest in civil engineering as for making concrete different aggregate grain sizes defined by a sieving curve (64mm to 0.125 mm) are needed. Aggregates up to a size of 180 μm can be excluded from the data set, therefore only the amount of small aggregates with a grain size below 180 μm must be considered with LIBS. All components of the concrete with a grain size smaller than 0.125mm are related to the flour grain content. Tested samples consisted of dry and hardened cement paste (water-cement ratio w/z=0.5), which served as a reference. Aggregate mixtures were made by adding flour grains (size 40 μm) and silica fume (size 0.1 μm) in different ratios to cement: 10%, 30%, 50% and 60%, all combined to the remaining percentage of dry or hydrated cement. The visualization results show that a dependance in the evolution of the plasma as a function of sample grain size can be detected only in the initial stages of the plasma formation, that is, at the initial 3 μs of the plasma life. Spectral information reveals the elemental distribution of the silicon and calcium in plasma, in both neutral and ionized form. Here also, a significant effect is observed in the first 1 μs of the plasma lifetime.