From halogenated flame retardants to non-halogenated to nanocomposites, each milestone in flame retardancy research led to an increase in performance and safety. With the rise of ceramic precursors in flame retardants, a new field of applications in extreme fire scenarios has become accessible. Intumescent coatings combined with precursors for ceramics show a high temperature transition to a ceramic foam, which provides much better fire resistance than conventional coatings at temperatures beyond 1200°C. Even a protection at 2000 °C for several minutes can be achieved. Combining the expansion property of traditional intumescent coatings with a ceramification at high temperatures leads to high-performance coatings, whose unique properties may prove useful for emergency insulation systems for re-entry bodies in the aerospace industry or special fire protection applications.
In this study, the protection performance in extreme fire conditions, the development of the expansion and the following ceramic transition of a high-performance coating are investigated. To this end, a small scale high-performance burner setup was created. The coated (2.5/4 mm) steel plates (75 x 75 x 2 mm) were exposed to direct flame treatment of a propane-oxygen-burner controlled by two flow controllers. During the test, temperatures above of 1800 °C were reached and steel and flame temperature were recorded. Fire tests of different durations (1, 2.5, 5, 10 and 20 min) were performed. The residues of the different development stages were analysed with non-destructive µ-computed tomography and scanning electron microscopy. The 3D images of the computed tomography provide an insight into the developing cell structure and state of ceramification of the residues.
Purpose – The purpose of this paper is to investigate the performance of intumescent coating on tension rod systems and their components. Steel tension rod systems consist of tension rods, fork end connectors and associated intersection or gusset plates. In case of fire, beside the tension rods themselves, the connection parts require appropriate fire protection. Intumescent fire protection coatings prevent a rapid heating of the steel and help secure the structural load-carrying capacity. Because the connection components of tension rod systems feature surface curvature and a complex geometry, high demand is placed on the intumescence and thermal protection performance of the coatings.
Design/methodology/approach – In this paper, experimental studies were carried out for steel tension rod systems with intumescent coating. The examined aspects include the foaming and cracking behaviour, the influence of different dry film thicknesses, the heating rate of the steel connecting parts in comparison to the tension rods, and the mounting orientation of the tension rods together with their fork end connectors.
Findings – The results show that a decrease in surface curvature and/or an increase inmass concentration of the steel components leads to a lower heating rate of the steel. Moreover, the performance of the intumescent coating on tension rod systems is influenced by themounting orientation of the steel components.
Originality/value – The findings based on fire tests contribute to a better understanding of the intumescent coating performance on connection components of tension rod systems. This subject has not been extensively studied yet.
Intumescent fire protection coatings are used to improve the fire resistance of steel members. Due to slender cross-sections typically used for tension members, high demands are placed on the effectiveness and reliability of the intumescent coatings. This paper describes real-scale fire tests of intumescent coatings applied to steel tension members with circular solid and hollow sections. First, the current regulations for the application of intumescent coatings on steel tension members are discussed. After that, a comparison between the foaming behaviour and failure mechanisms of intumescent coatings applied to steel tension members with different cross-sections and loading conditions is given. Next, the experimental setup and procedure of the performed fire tests are presented. In addition, the influences of various parameters on the performance of the intumescent coating are analysed, including the geometry of the steel profile, dry film thickness of the intumescent coating, load utilisation level as well as the orientation of the member. Based on the theoretical considerations and results of the fire tests, it is evidenced that mechanically loaded fire tests are essential to assess accurately the contribution of intumescent fire protection coatings to the fire resistance of steel tension members with circular solid sections.
For intumescent coatings durability is an important aspect. Due to ageing, which is caused by climatic conditions, the thermal protection performance of intumescent coatings can be reduced during the working life. The national German and the European procedures to assess the durability of intumescent coatings presume a working life of 10 years. For a longer period, additional investigations are required. However, the European assessment procedure does not provide specific information how to prove a durability of more than 10 years. In addition to this formal reason, also from a scientifical position, it is necessary to investigate the degradation of intumescent coatings in detail to propose a corresponding test concept for a durability of more than 10 years.
The presentation summarises the existing knowledge about the degradation behaviour and ageing of intumescent coatings. Furthermore, the results of different approaches from a recently conducted research project are presented. Starting from a water-based and an epoxy-based guide formulation, in a first approach a degradation of the intumescent coating was carried out directly during the production process, i.e. by reducing the concentration of functionally relevant chemical components. In another approach, the duration of the short-term weathering tests was significantly extended, i.e. by multiple repetition of the artificial weathering. The thermal protection performance of the intumescent coating was assessed by fire tests and tests with electrical heating source. In addition, small-scale tests were carried out to determine the thermal material properties of the intumescent coating and thermo-analytical methods were applied to characterise the degradation. Derived from this knowledge, possibilities to test and assess a working life for a period of more than 10 years are proposed.
The environmental compatibility of reactive fire-retardant coatings (intumescent paints) was investigated by a combination of leaching and ecotoxicological tests. Three representative fire-retardant coating systems were tested using two leaching procedures: “Horizontal Dynamic Surface Leaching Test” (DSLT) and the “Intermittent Immersion Test” (IIT). All eluate fractions (8 for DSLT and 9 for IIT) were analyzed for pH, conductivity, concentration of total organic carbon and selected anions und cations. Additionally, a GC-MS screening of selected fractions was conducted for identification of organic compounds. Eluate fractions 1 + 2 and fraction 7 of the DSLT were analyzed in four ecotoxicological tests (algae, daphnia, fish egg, luminescent bacteria) and in one genotoxicity test (umu). Concentration of most analytes was rather low or below limit of detection for many eluates. Analytes detected in eluates of all three products are Zn, Ba, SO4(2−) and PO4(3−). Release patterns do not indicate a general trend: some compounds show maximum release in the first fractions while for others the maximum was observed in later test stages. Ecotoxic effects in eluates were found, which were higher in the eluate fraction 7 (maximum lowest ineffective dilution for luminescent bacteria (LIDL) 256) than in the eluate fraction 1 + 2 (maximum LIDL = 24). The sensitivity of the test systems was very different with highest effects for luminescent bacteria, followed by algae and daphnia and without effects in the fish egg test and umu test. A biotest battery for the comprehensive assessment is therefore advisable.
Intumescent coatings are used in civil engineering to improve the fire resistance of steel constructions. Due to the thin coating thickness and the profile-following application, the architectural appearance of the steel structure can be preserved. EN 13381-8 provides regulations to determine the contribution to the fire resistance of intumescent coatings applied to steel beams and columns. The scope of this standard excludes tension members and steel members with solid sections. For products that have already been successfully tested and assessed on beams and columns, EN 13381-10 offers the possibility based on unloaded fire tests to extend the scope of application of intumescent coatings to tension bars with solid sections. This approach contradicts the national safety level in Germany, where mechanically loaded testing is mandatory. Therefore, a new part of the test standard series EN 13381 is currently developed to enable the application of intumescent coatings on steel tension bars with solid section based on mechanically loaded fire tests. BAM has already carried out numerous fire tests on loaded steel tension members with intumescent coatings. Currently, in the BAM research project FIRESTEMIC, the influence of the steel bar orientation and the profile type on the thermal performance of intumescent coatings are investigated. Both questions concerning the thermal protection ability of intumescent coatings were analysed based on three different test sets, which were carried out in the tension furnace (Fig. 1a). The fire exposure corresponds to the standard temperature-time curve according to EN 1363-1.
This paper summarises the main findings from the fire tests conducted in the FIRESTEMIC project. The results serve as an experimental background for the proposal of the new standard. Regarding the bar orientation, a new test setup was developed and proposed for the new standard. The two tested commercial water-based intumescent coatings with applied dry film thickness from 1.5 mm to 2.5 mm showed only a slight dependence on the bar orientation. In terms of the steel profile type, circular and rectangular solid sections with identical section factor and applied dry film thickness were tested. It was observed that the circular solid bars with diameter 30 mm heat up faster compared to the solid rectangular bars with dimension 30×30 mm (Fig. 1b). Also at larger steel bars, i.e. diameter 40 mm and dimension 40×40 mm, the same trend occurred. Thus, it is recommended for the new test standard to allow a transfer of the test results from circular to rectangular solid sections. In addition, the paper will describe and explain the test and assessment procedure proposed for the newly developed standard.
Intumescent coatings are commonly used in civil engineering to improve the fire resistance of steel constructions. Especially in the case of tension bars, where mostly circular or rectangular solid sections are used, intumescent coatings offer an efficient measure to improve the fire resistance taking advantage of profile-following application and low coating thickness requirements. Thus, the architectural appearance of slender profiles can be preserved. The paper describes real-scale mechanically loaded and unloaded fire tests of circular and rectangular solid steel tension bars with intumescent coating. The aim of these tests is to investigate the influence of the different profile types as well as different bar orientations on the performance of intumescent coatings. The results are used to specify a normative test and assessment procedure to be implemented in a new European standard for determining the contribution of intumescent coatings to the fire resistance of circular or rectangular bars used as tension members.