Analysis of protection blinding in active distribution grids

  • Protection blinding is a challenging issue in renewables-penetrated distribution grids and refers to a situation where a circuit breaker may not trip due to fault current contribution from distributed generation. This research addresses how the distributed generation location and capacity impact the operation of the circuit breaker in terms of the response time of the circuit breakers. The relative electrical distances of the faults and distributed generation to the circuit breakers are considered. The impact of distributed generation capacity considering the fault location is characterized using a new index called the heterogeneity index. The electrical distance between distributed generations and circuit breakers and the electrical distance between fault and circuit breaker is considered by a second new index called the electrical distance ratio. Data analysis on simulation results shows that these indices capture the phenomena of protection blinding caused by distributed generation. Results show that a higher distributedProtection blinding is a challenging issue in renewables-penetrated distribution grids and refers to a situation where a circuit breaker may not trip due to fault current contribution from distributed generation. This research addresses how the distributed generation location and capacity impact the operation of the circuit breaker in terms of the response time of the circuit breakers. The relative electrical distances of the faults and distributed generation to the circuit breakers are considered. The impact of distributed generation capacity considering the fault location is characterized using a new index called the heterogeneity index. The electrical distance between distributed generations and circuit breakers and the electrical distance between fault and circuit breaker is considered by a second new index called the electrical distance ratio. Data analysis on simulation results shows that these indices capture the phenomena of protection blinding caused by distributed generation. Results show that a higher distributed generation penetration and faults that are electri cally further away from a circuit breaker show severe cases of protection blinding captured by the indices. Furthermore, it is demonstrated how these indices can identify the worst impacted locations in the distribution grid. A key result is that protection blinding does not necessarily occur solely due to the presence of distributed generation between a circuit breaker and a fault, but is dependent on factors such as distributed generation location in the distribution grid, fault level, fault level distribution across the generation units and fault location.show moreshow less

Download full text files

Export metadata

Additional Services

Share in Twitter Search Google Scholar
Metadaten
Author:Amit Patil, Abdorasoul Ghasemi, Hermann de Meer
URN:urn:nbn:de:bvb:739-opus4-14661
DOI:https://doi.org/10.1049/rpg2.13037
Parent Title (English):IET Renewable Power Generation
Document Type:Article
Language:English
Year of Completion:2024
Date of Publication (online):2024/06/30
Date of first Publication:2024/06/30
Publishing Institution:Universität Passau
Release Date:2024/07/30
Tag:General & introductory electrical electronics engineering
Page Number:15 Seiten
Institutes:Fakultät für Informatik und Mathematik
Dewey Decimal Classification:0 Informatik, Informationswissenschaft, allgemeine Werke / 00 Informatik, Wissen, Systeme / 004 Datenverarbeitung; Informatik
open_access (DINI-Set):open_access
Licence (German):License LogoCreative Commons - CC BY - Namensnennung 4.0 International