TY - CONF A1 - Wagner, Marcus A1 - Lehrer, Tobias A1 - Franke, Markus A1 - Al-Abadi, Ali A1 - Gamil, Ahmed T1 - A Tank Resonance Model for Power Transformers T2 - ARWtr 2022 proceedings, 2022 7th Advanced Research Workshop on Transformers (ARWtr): October (23)24-26, 2022, Baiona, Spain N2 - During the factory acceptance test, the sound levels are measured. If the measured sound levels exceed pre-specified values, modifications on the transformer’s active part and/or tank need to be conducted. Tank resonance, if occurs, at twice main power frequency and its higher harmonics is one of the main reasons of amplifying the generated sound levels. Therefore, it is preferable to know already in the design stage about the occurrence of the tank resonance and propose reliable tank solutions. The current study presents a newly developed model for calculating the mode shapes and its corresponding eigenfrequencies of the tank. Y1 - 2022 UR - https://opus4.kobv.de/opus4-oth-regensburg/frontdoor/index/index/docId/5514 SP - 7 EP - 12 PB - IEEE ER -