Ingenieurbau
Filtern
Dokumenttyp
- Vortrag (32)
- Posterpräsentation (8)
- Beitrag zu einem Tagungsband (6)
- Zeitschriftenartikel (4)
Referierte Publikation
- nein (50)
Schlagworte
- Behälterversagen (50) (entfernen)
Organisationseinheit der BAM
- 2 Prozess- und Anlagensicherheit (17)
- 2.1 Sicherheit von Energieträgern (17)
- 2.2 Prozesssimulation (3)
- 3 Gefahrgutumschließungen; Energiespeicher (3)
- 8 Zerstörungsfreie Prüfung (3)
- 8.1 Sensorik, mess- und prüftechnische Verfahren (3)
- 3.0 Abteilungsleitung und andere (2)
- 3.2 Gefahrguttanks und Unfallmechanik (1)
Eingeladener Vortrag
- nein (32)
Es wurden insgesamt 57 Einzelversuche zum Versagen von Druckgasbehältern durchgeführt. Untersucht wurden dabei 11-kg-Propangasflaschen, PKW-Radmuldentanks für LPG- sowie CNG-Tanks vom Typ III (Compositetanks mit Aluminiumliner) und Typ IV (Compositetanks mit Polymerliner). Mit 18 hydraulischen Berstversuchen wurde das Versagensverhalten unter kalten Bedingungen charakterisiert. In 39 Unterfeuerungsversuchen mit den gefüllten LPG- und CNG-Tanks, davon 36 mit Tanks ohne Sicherheitseinrichtung, wurde das Behälterversagen durch Brandbeaufschlagung untersucht. Neben verschiedenen Behältermanteltemperaturen und dem Behälterinnendruck wurde auch die Temperatur des gespeicherten Mediums dokumentiert. Dadurch war es möglich, genau zu dokumentieren, unter welchen Bedingungen und bei welchem Zustand der Behälter versagt hat. In einem Großteil der Unterfeuerungsversuche mit Behältern ohne Sicherheitseinrichtungen kam es zur Bildung eines Feuerballs, einer massiven Druck- und Temperaturwirkung auf den Nahbereich sowie einer Vielzahl von Fragmenten im Nah- und Fernbereich. In einer Entfernung von l = 7 m wurden Überdrücke von bis zu p = 0,41 bar gemessen. In 30 Unterfeuerungsversuchen kam es zur Fragmentierung des Behälters. Dabei konnten 159 Fragmente mit Wurfweite und Masse dokumentiert werden. Die dabei maximal festgestellte Wurfweite eines Fragments lag bei l = 311 m.
Regelmäßig werden Einsatzkräfte der Feuerwehr bei Brandeinsätzen mit brand- bzw. wärmebeaufschlagten Druckgasbehältern konfrontiert. Aufgrund ihrer großen Verbreitung handelt es sich dabei oftmals um Propan- oder Acetylengasflaschen. Propangasflaschen mit Füllmengen bis 33 Kilogramm sind in flächendeckender Verwendung zum Beispiel in Handwerksbetrieben, Produktionsbereichen, Baustellen und Restaurants, werden aber oftmals auch zum Heizen und Kochen im Privatbereich verwendet. Acetylengasflaschen sind in Verbindung mit entsprechenden Sauerstoffbehältern ebenso in Werkstätten, gewerblichen Anlagen und auf Baustellen zum Autogenschweißen und thermischen Trennen in vielfacher Verwendung. Beide Arten von Druckgasbehältern sind darüber hinaus auch im Straßenverkehr als Gefahrgut und in kleineren Mengen auch als private Fracht anzutreffen. Die Deutsche Gesetzliche Unfallversicherung (DGUV) hat zusammen mit weiteren Experten als Hilfestellung und aufgrund neuer wissenschaftlicher Erkenntnisse zwei DGUV-Informationen für Einsatzkräfte zum Umgang mit wärmebeaufschlagten Druckgasbehältern erstellt.
In continuation of a preceding test series involving sole LPG vehicle tanks, three passenger cars equipped with identical toroidal steel LPG tanks were set on fire. The tanks were installed in the space normally reserved for the spare tyre, in the car boot. No safety device was installed on the tank, in order to force critical failure of the cylinder. Two of the cars were equipped with a tank filled with liquefied propane to a level of 20 % (5.3 kg), the third one was filled completely (25.5 kg). The partially filled tanks failed critically within a time period of more than 20 min after the initiation of the fire. The fully-filled tank did not rupture; the propane was released continuously through a small leak that appeared during the fire. Comprehensive equipment was used to procure measurement data, enabling an analysis of potential consequences and hazards to humans and infrastructure within the vehicle surroundings. The inner status of the tank (pressure, temperature of the liquid phase and the steel casing), the development of the fire (temperature inside and around the vehicle) and the pressure induced in the near-field in case of tank rupture were recorded. The results were analysed in detail and compared against the data gained in tests involving sole, but identical LPG tanks.
In continuation of a preceding test series involving sole LPG vehicle tanks, three passenger cars equipped with identical toroidal steel LPG tanks were set on fire. The tanks were installed in the space normally reserved for the spare tyre, in the car boot. No safety device was installed on the tank, in order to force critical failure of the cylinder. Two of the cars were equipped with a tank filled with liquefied propane to a level of 20% (5.3 kg), the third one was filled completely (25.5 kg). The partially filled tanks failed critically within a time period of more than 20 min after the initiation of the fire. The fully-filled tank did not rupture; the propane was released continuously through a small leak that appeared during the fire. Comprehensive equipment was used to procure measurement data, enabling an analysis of potential consequences and hazards to humans and infrastructure within the vehicle surroundings. The inner status of the tank (pressure, temperature of the liquid phase and the steel casing), the development of the fire (temperature inside and around the vehicle) and the pressure induced in the near-field in case of tank rupture were recorded. The results were analysed in detail and compared against the data gained in tests involving sole, but identical LPG tanks.
Immer wieder werden Feuerwehren bei Einsätzen mit brandbeaufschlagten Acetylenflaschen konfrontiert. Im Falle eines Behälterversagens stellen diese eine enorme Gefährdung für die Einsatzkräfte dar. Die BAM beschäftigt sich seit vielen Jahren mit den Auswirkungen im Falle eines solchen Behälterversagens. Der Beitrag stellt die Arbeit der BAM auf diesem Gebiet vor und zeigt verschiedene Handlungsoptionen auf, um das Risiko für die Einsatzkräfte zu verrringern. Weiterhin wird ein Merkblatt zu brandbeaufschlagten Acetylenflaschen vorgestellt, welche zusammen mit der DGUV im Jahr 2018 herausgegeben werden.
In Deutschland gibt es eine große Anzahl von Kraftfahrzeugen, die mit alternativen Antrieben (z. B. LPG (Liquefied Petroleum Gas), CNG (Compressed Natural Gas)) ausgerüstet sind. In zahlreichen Großversuchsserien untersucht die Bundesanstalt für Materialforschung und -prüfung (BAM) im Rahmen des internen Forschungsprojekts CoFi-ABV (Complex Fires – Auswirkungen von Behälterversagen) die Auswirkungen beim Versagen der Treibstoffbehälter dieser alternativen Antriebe. Ziel dieser Untersuchungen ist eine ganzheitliche Auswirkungsbetrachtung, um die Risiken für Feuerwehren und Rettungskräfte besser abschätzen zu können. Im Vorfeld zu den Versuchen für LPG- und CNG-Tanks wurden in einer weiteren Versuchsserie 15handelsübliche 11-kg-Propangasflaschen ohne Sicherheitseinrichtung unterfeuert. Alle 15 Behälter haben – wie zu erwarten war – versagt. Neben den Zustandsdaten des Behälters zum Versagenszeitpunkt (Temperatur des Behältermantels, Innendruck und -temperatur) wurden die Auswirkungen auf die Umgebung hinsichtlich Druckwirkung und Fragmentierung (Anzahl, Masse, Distanz, Richtung) dokumentiert.
In einer Großversuchsserie wurden auf dem BAM-TTS 15 11-kg-Propangasflschen ohne Sicherheitseinrichtung mit drei verschiedenen Methoden (Holz, Benzinpool, Gas) unterfeuert. Der Vortrag präsentiert die dokumentierten Auswirkungen (z. B. Fragementierung, Überdruck), die Art des Versagens sowie den Behälterzustand zum Zeitpunkt des Versagens.
Immer wieder werden Feuerwehren bei Einsätzen mit brandbeaufschlagten Propan- und Acetylenflaschen konfroniert. Im Falle eines Behälterversagens stellen diese eine enorme Gefährdung für die Einsatzkräfte dar. Die BAM beschäftigt sich seit vielen Jahren mit den Auswirkungen im Falle eines solchen Behälterversagens. Der Beitrag stellt die Arbeit der BAM auf diesem Gebiet vor und zeigt verschiedene Handlungsoptionen auf, um das Risiko für die Einsatzkräfte zu verrringern. Weiterhin werden zwei Merkblätter zu brandbeaufschlagten Druckgasbehältern vorgestellt, welche zusammen mit der DGUV im Jahr 2018 herausgegeben werden.