Biodiesel (FAME) from rapeseed is an environmentally friendly alternative to common fossil fuels. It is also suitable to serve as blending component to fuels like heating oil. If the fuel composition is changed, materials compatibility must be guaranteed. Adding polar biodiesel to nonpolar heating oil, changes the blend’s solvency and might cause swelling, extraction and solvation of polymers. The objective of this research was to investigate the compatibility of polymeric materials, which are commonly used for components in middle distillate facilities, along with blends of heating oil and 20 % biodiesel (B20). For this propose, ACM, HNBR, FKM, PE, PA 6, POM, PUR and PVC were exposed to heating oil and B20 for 42 and 84 days at 40 °C. In addition, the polymers HNBR, FKM, PA, POM and PVC were also exposed at 70 °C. Furthermore, the resistance of polymers in eight-year aged B10 at 40 °C was evaluated. Ageing of biodiesel increases acidity which might propagate polymer corrosion. The materials were evaluated as resistant, if the loss in tensile properties (tensile strength and elongation at break) and Shore hardness remained under 15 % compared to the initial unexposed material values. For investigations under compressed conditions, the compression set was determined for specimens of ACM, FKM and HNBR after exposure in heating oil B0 and B20 for 3,7,14, 28, 56 and 90 days at 40 °C according to ISO 815-1. It was found that the resistance in B20 at 40 °C was given for all tested polymers except PUR. In the 8 years aged B10, PUR and POM were not compatible and ACM just conditionally compatible. At 70 °C, FKM and PVC were resistant in B20, whereas HNBR and PA 6 were not compatible. Swelling occurred for the elastomers ACM, HNBR and PUR.
Biodiesel is subject to degradation processes like oil and grease. The oxidative degradation products of vegetable oil esters in biodiesel particularly lead to enhanced sedimentation in blended fuels.
The polarity of biodiesel increases its solvency and facilitates permeation and extraction. Solvation, swelling and/or extraction lead to changes in the physical properties and chemical changes of polymeric materials. It also accelerates the degradation (hydrolysis and oxidation) of these materials with the loss of additives and stabilizers.
The objective of this research was to determine the resistance of frequently used polymeric materials such as ACM, EPDM, FKM, FVMQ, CR, CSM, IIR, HNBR, NBR, PA, PE; POM, PUR, PVC and VMQ in biodiesel and heating oil with 10 %/20 % biodiesel (B10/B20) at 40°C and 70°C.
Mass, tensile strength and breaking elongation of the test specimens were determined before and after the exposure for 84 days in the biodiesel heating oil blends. The visual examination of some elastomer test specimens clearly showed the great volume increase until break or partial dissolution. Shore hardness A and D were determined before and after exposure of the test specimens in the biofuels for 42 days.
The elastomers CR, CSM, EPDM, IIR, NBR and VMQ were generally not resistant to biodiesel and B10 at 40°C and 70°C. FKM, ACM, HNBR, PA, PE, POM, and PVC showed high compatibility in B10/B20 at 40°C. A lower compatibility was determined for ACM in biodiesel. ACM and HNBR were not resistant in B20 at 70°C.
Heating oil storage tanks made of polyethylene grades have been on the market in Germany since the early 1970s. To ensure safety, their replacement is recommended by tank manufacturers after a period of 30 years. Polyethylene is subject to ageing by alteration of the properties during its life cycle. The degree of degradation and the nature of the process mainly depend on the chemical alteration of the polyethylene, the wall thickness of the tank and the environmental conditions. There are no data available on the long-term behaviour of the polyethylene grades, especially after a service life of more than 30 years.
The aim of this investigation was to find a suitable test method to determine the factual degree of damage in comparison to the uncontaminated polyethylene grades. Material data of the used polyethylene grades are available because the BAM was the competent authority for the tests and expert reports for the approval of these tanks until the middle of the 1990s. Therefore, tank sections from the bottom, the shell and the roof of 22 individual storage tanks produced of polyethylene grades A and B have been examined by Melt Flow Rate (MFR) and Attenuated Total Reflectance (ATR). Their service life was in the range between 20 and 41 years.
The MFR measurements of the tank sections showed differences in the values depending on the weight which was used (5 kg or 21.6 kg). An increase of the MFR was determined for the samples of polyethylene grade A, whereas a reduction of the MFR values was measured for most samples of polyethylene grade B. This grade is mainly subject to the internal ageing by cross-linkages, increased degree of branched molecules and loss of the plasticizer.
ATR analysis exhibits an absorption band at 909 cm‒1 predominantly in samples of polyethylene grade A indicating chain scission and concomitantly formed terminal vinyl groups. This absorption band can be used for the characterization of the ageing of the polyethylene grades.
Biodiesel is viewed as a major source of energy. In areas such as the European Union, where 80 % of the oil-based fuel is imported, there is also the desire to reduce dependence on external oil supplies.
Materials compatibility is a major concern whenever the fuel composition is changed. The question arises of whether polymeric materials are resistant to heating oil with 20 % biodiesel (B20) in comparison to pure heating oil.
The polarity of biodiesel increases its solvency and facilitates permeation and extraction. Solvation, swelling and/or extraction lead to changes in the physical properties. Extraction alters the fuel chemistry. These chemical changes could also accelerate the degradation (hydrolysis and oxidation) of the polymeric material with the loss of additives and stabilizers.
The objective of this research was to determine the resistance of frequently used materials for components in middle distillate facilities such as ACM, FKM, HNBR, PA, PE, POM, PUR and PVC in heating oil and heating oil blend B20 for 84 days at 40 °C, and FKM, HNBR, PA, POM, PUR and PVC at 70 °C.
Mass, tensile strength, breaking elongation and Shore hardness A (D) of the test specimens were determined before and after exposure for 84 (42) days in the test fuels under static conditions.
For the investigations under compressed conditions, the mass and the compression set of FKM test specimens were determined before and after exposure for 3, 7, 14, 28, 56 and 90 days in B20 at 40 °C and 70 °C according to ISO 815-1 “Rubber, vul-canized or thermoplastic - determination of compression set – Part 1: At ambient or elevated temperatures”.
There is not determined a threshold for the reduction in tensile properties and Shore hardness in the international standards. Therefore, a threshold of 15 % was determined for the evaluation of the compatibility.
The change of tensile strength and breaking elongation of test specimens made of ACM, FKM, HNBR, PA, PE, POM, PUR and PVC exposed to heating oil and the blend B20 was less than 15 % at 40 °C. A maximum reduction in Shore hardness A of 14 % was determined for ACM at 40 °C and for HNBR of 15 % at 70 °C.
It can be concluded that ACM, FKM, HNBR, PA, PE, POM, PVC and PUR were resistant in B20 at 40°C. FKM, PA, POM and PVC were evaluated as resistant in heat-ing oil and B20 at 70 °C, HNBR and PUR were not resistant in these fuels at 70°C.
Based on the mass increase and compression set values of FKM test specimens it can be stated that FKM is resistant in B20 under compressed conditions at 40 °C and 70 °C.
Compatibility of polymeric materials with heating oil/biodiesel blends at different temperatures
(2019)
Materials compatibility is a major concern whenever the fuel composition is changed. The question arises of whether polymeric materials are resistant to heating oil with admixtures of 10 % biodiesel (B10) and 20 % biodiesel (B20).
The polarity of biodiesel increases its solvency and facilitates permeation and extrac-tion. Solvation, swelling and/or extraction lead to changes in the physical properties and chemical changes of polymeric materials.
The objective of this research was to determine the resistance of frequently used sealing materials such as FKM, EPDM, CR, CSM, NBR, IIR, VMQ, FVMQ, PA and PUR in up to four-year aged B10 for 84 days at 20 °C, 40 °C and 70 °C.
The polymeric materials: ACM, FKM, HNBR, PA, PE; POM, PUR and PVC were ex-posed to B20 for 84 days at 40°C and 70°C in another research project.
Mass, tensile strength, breaking elongation and Shore hardness A (D) of the test specimens were determined before and after the exposure for 84 (42) days in the heating oil blends B10 and B20.
There is not determined a threshold for the reduction in tensile properties and Shore hardness in the international standards. Therefore, a threshold of 15 % was deter-mined for the evaluation of the compatibility.
Measurements of the variations in mass, tensile properties and Shore hardness after exposure of the polymers in non-aged and aged heating oil B10 showed clearly that FKM, FVMQ and PA were the most resistant materials in B10. The elastomers CR, CSM, EPDM, IIR, NBR and VMQ were generally not resistant to B10. Damage to the materials increased with higher test temperatures and the age of B10.
FKM, POM and PVC showed high compatibility in B20 at 40°C and 70 °C. ACM, HNBR and PA were evaluated as resistant in B20 at 40 °C but not at 70°C.
Biofuels including ethanol and biodiesel (fatty acid methyl ester, FAME) represent an important renewable fuel alternative to petroleum-derived transport fuels. Increasing biofuels use would bring some benefits, such as a reduction in oil demands and greenhouse gas emissions, and an improvement in air quality. Materials compatibility is a major concern whenever the fuel composition is changed in a fuel system.
The objective of this research was to determine the resistance of frequently used sealing materials such as CR (chloroprene rubber), CSM (chlorosulfonated polyethylene), EPDM (ethylene-propylene-diene rubber), FKM (fluorocarbon rubber), FVMQ (methyl-fluorosilicone rubber), IIR (butyl rubber), NBR (acrylonitrile-butadiene rubber), PA (polyamides), PUR (polyester urethane rubber) and VMQ (methyl-vinyl-silicone rubber), in heating oil with admixtures of biogenic sources such as E10 (fuel with max. 10 % ethanol), E85 (fuel with 85 % ethanol), non-aged and aged biodiesel, diesel fuel with 5 % biodiesel, non-aged and aged B10 (heating oil with 10 % biodiesel) at 20 °C, 40 °C and 70 °C. Mass, tensile strength and breaking elongation of the test specimens were determined before and after the exposure for 84 days in the fuels. The visual examination of some elastomer test specimens clearly showed the great volume increase until break or partial dissolution. Shore hardness A and D (for PA) were determined before and after exposure of the test specimens in the biofuels for 42 days.
There is not determined a threshold for the reduction in tensile properties and Shore hardness in the international standards. Therefore, a threshold of 15 % was set for the evaluation of the compatibility. The sealing materials CR, CSM, EPDM, IIR and NBR were generally not resistant to biodiesel and B10. In summary, it can be therefore stated that the chemical resistance of the fluoropolymers FKM and FVMQ in fuels and biofuels is the best one.
The objective of this research was to determine the resistance of frequently used sealing materials such as FKM (fluorocarbon rubber), FVMQ (methyl-fluoro-silicone rubber), VMQ (methyl-vinyl-silicone rubber), EPDM (ethylene-propylene-diene rubber), CR (chloroprene rubber), CSM (chlorosulfonated polyethylene), IIR (butyl rubber), PA (polyamides), NBR (acrylonitrile-butadiene rubber) and PUR (polyester urethane rubber) in fuels and heating oil with admixtures of biogenic sources such as E10 (fuel with 10 % ethanol), E85 (fuel with 85 % ethanol), non-aged and aged biodiesel, diesel fuel with 5 % biodiesel, non-aged and aged B10 (heating oil with 10 % biodiesel) at 20 °C, 40 °C and 70 °C.
Mass, tensile strength and breaking elongation of the test specimens were determined before and after the exposure for 84 days in the fuels. The visual examination of some elastomer test specimens clearly showed the great volume increase until break or partial dissolution. Shore hardness A and D (for PA) were determined before and after exposure of the test specimens in the biofuels for 42 days.
There is not determined a threshold for the reduction in tensile properties and Shore hardness in the international standards. Therefore a threshold of 15 % was determined for the evaluation of the compatibility.
In summary, it can be therefore stated that the chemical resistance of the fluoropolymers FKM and FVMQ in fuels and biofuels is the best one.
Tanks for heating oil made of polyethylene grades have been on the market since the early 1970s in Germany. Tank manufacturers recommend the replacement of the tanks after a period of 30 years due to guarantee safety. Polyethylene grades are subject to ageing by alteration of the properties during their life cycle. The degree of ageing and the nature of the degradation process mainly depend on the chemical degradation of the polyethylene, the wall thickness of the tank and the environmental conditions. There are no results available on the long-term behavior of the polyethylene grades, especially after a service life of more than 30 years. The aim of this investigation was the determination of the factual degree of damage in comparison to the uncontaminated polyethylene grades. Material data of the used polyethylene grades are available because the BAM was the competent authority for the tests and expert reports for the approval of these tanks until the middle of the 1990s.
The determination of the Melt Flow Rate (MFR) and the Fourier Transmission IR Spectroscopy (FTIR) of tank sections from the bottom, the shell and the roof of 10 segregated heating oil storage tanks produced of polyethylene grades A and B were used as tests methods.
The MFR measurements of the tank sections showed differences in the values depending on the weight which was used (5 kg or 21.6 kg). A reduction of the MFR values was measured for most of the sections of tanks made of polyethylene grade B after a service life of the tanks of more than 30 years. This grade is mainly subject to the internal ageing by cross-linkages, increased degree of branched molecules and loss of the plasticizer, and to a lesser extent by oxidative degradation. The FTIR analysis, especially of tank sections of the bottom and the shell showed that the intensity of the CH2 asymmetric and symmetric stretching vibrations in the range: 2800 - 2900 cm-1 and the CH2 bending deformation vibration at 1400 cm-1 increased due chain scissions. The intensity of the carbonyl stretching vibration C=O at 1740 cm-1 is low. The carbonyl index characterizes the degree of oxidation.
Materials compatibility is a major concern whenever the fuel composition is changed. The question arises of whether sealing materials are resistant to fuels with bioethanol and biodiesel (rapeseed oil fatty acid methyl ester).
Previous research considered the resistance of frequently used sealing materials such as FKM (fluorocarbon rubber), FVMQ (methyl-fluoro-silicone rubber), VMQ (methyl-vinyl-silicone rubber), EPDM (ethylene-propylene-diene rubber), CR (chloroprene rubber), CSM (chlorosulfonated polyethylene), IIR (butyl rubber), PA (polyamides), NBR (acrylonitrile-butadiene rubber) and PUR (polyester urethane rubber) in fuels and heating oil with admixtures of biogenic substances such as biodiesel and B10 (heating oil with 10 % biodiesel) under purely static conditions.
The aim of this study was to evaluate the fluorocarbon rubber performance under compressed conditions. For the investigations, the mass and the compression set of the FKM test specimens were determined before and after exposure for 3, 7, 14, 28, 56 and 90 days in E10 (fuel with 10 % ethanol), E85 (fuel with 85 % ethanol), biodiesel (fatty acid methyl ester, FAME), Super (fuel with max. 5 % ethanol), diesel fuel with max. 5 % biodiesel, pure diesel fuel, Super Plus (fuel without ethanol) and heating oil with 10 % biodiesel (B10) at 40 °C according to ISO 815-1 “Rubber, vulcanized or thermoplastic - determination of compression set – Part 1: At ambient or elevated temperatures”. The compression set test belongs beside the determination of the Shore hardness, the density and the tensile properties to the basic test methods for elastomers. It was measured in regular time intervals up to a re-drying of more than 90 days after relaxation of test specimens. For comparison, FKM test specimens were exposed without fuel under compressed conditions at 40 °C.
The highest mass increase of FKM test specimens was measured after 90 days exposure in E10 by 9 %, followed by 8 % in Super fuel, by 4 % in E85 and by 0.6 % in biodiesel. Mass increase and swelling of the test specimens in E10 and Super fuel with max. 5 % ethanol had an influence on the compression set values which were subject to high fluctuations in comparison to the values obtained after exposure to other fuels such as biodiesel, diesel fuel and B10.
The results of the present work confirmed the higher swelling of the elastomers such as FKM in E10 obtained under static condition. It can be concluded on the basis of the mass increase and compression set values that FKM is resistant in all fuels under compressed conditions at 40 °C.
Biofuels including ethanol and biodiesel (FAME) represent a renewable fuel alternative to petroleum-derived transport fuels. The aim of this work was to study the interaction between high density polyethylene (HDPE) with permeation barriers in form of polyamide (PA) and fluorination, and biofuels such as E85 (fuel with 85 % ethanol), biodiesel and B10 (heating oil with 10 % biodiesel). 10 l jerrycans made of polyethylene with permeation barrier of PA were filled with E85 and biodiesel and exposed to temperatures of 20 °C and 40 °C for 5 years. Half of the 20 l jerrycans of HDPE for filling with B10 were fluorinated at the inner layer to prevent permeation before the exposure. Tensile properties were determined once a year, and FTIR-spectroscopy was used to evaluate possible changes.
The tensile properties tensile strength and breaking elongation of HDPE jerrycan cuttings with permeation barrier decreased, but not significantly, after immersion in E85, biodiesel and B10. The elasticity modulus of the polyethylene grades was especially reduced during exposure to E85.
The FTIR spectra of HDPE jerrycan cuttings with permeation barrier showed that immersion tests for five years with the test fuels at 20 °C and 40 °C did not lead to a decomposition of the permeation barriers.
Biofuels including ethanol and biodiesel (FAME) represent a renewable fuel alternative to petroleum-derived transport fuels. The aim of this work was to study the interaction between high density polyethylene (HDPE) with permeation barriers in form of polyamide (PA) and fluorination, and biofuels such as E85 (fuel with 85 % ethanol), biodiesel and B10 (heating oil with 10 % biodiesel). 10 l jerrycans made of polyethylene with permeation barrier of PA were filled with E85 and biodiesel and exposed to temperatures of 20 °C and 40 °C for 5 years. Half of the 20 l jerrycans of HDPE for filling with B10 were fluorinated at the inner layer to prevent permeation before the exposure. Tensile properties were determined once a year, and FTIR-spectroscopy was used to evaluate possible changes.
The tensile properties tensile strength and breaking elongation of HDPE jerrycan cuttings with permeation barrier decreased, but not significantly, after immersion in E85, biodiesel and B10. The elasticity modulus of the polyethylene grades was especially reduced during exposure to E85.
The FTIR spectra of HDPE jerrycan cuttings with permeation barrier showed that immersion tests for five years with the test fuels at 20 °C and 40 °C did not lead to a decomposition of the permeation barriers.
The objective of this research was to determine the resistance of frequently used sealing materials such as fluorocarbon rubber (FKM), fluorosilicone rubber (FVMQ), silicone rubber (VMQ), ethylene-propylene-diene rubber (EPDM), chloroprene rub-ber (CR), chlorosulfonated polyethylene (CSM), butyl rubber (IIR), acrylonitrile buta-diene rubber (NBR), polyester urethane rubber (PUR) and polyamide (PA) in non-aged/aged biodiesel and heating oil with 10 % biodiesel at 20 °C, 40 °C and 70 °C. Mass, tensile properties and Shore hardness A/D (for polyamide) of the test speci-mens were determined before and after the exposure for 84/42 days in the aged and non-aged fuels of different age.
Biodiesel fuels are easily oxidized and contain acids and water. The sealing materi-als: acrylonitrile butadiene rubber, butyl rubber, chloroprene rubber, chlorosulfonated polyethylene and ethylene-propylene-diene rubber and were generally not resistant to biodiesel and heating oil with 10 % biodiesel. Fluorocarbon rubber, fluorosilicone rubber and polyamide were the most resistant materials in all tested fuels up to 70 °C. The degree of damage to the sealing materials increased with higher test temperatures and the age of the fuels.
Plastic storage tanks for heating oil have been on the market since the early 1970s in Germany, mainly made from polyethylene grades. Tank manufacturers and experts examining the tanks recommend the replacement of the tanks to ensure the safety after a period of 30 years. The tank manufacturer is legally obliged to specify the service life of the tanks.
Polyethylene is subject to ageing by alteration of the properties during its life cycle. A distinction is made between internal and external ageing processes. The internal ageing, such as the breakdown of internal stresses, post-crystallization, phase sepa-ration of multicomponent systems and plasticizer migration is attributed to thermodynamically instable conditions of the plastic material. The external ageing in form of stress cracking, fatigue cracking, thermooxidative degradation or swelling is based on physical or chemical effects of the environment of the polyethylene grade. The degree of ageing and the nature of the degradation process mainly depend on the chemical degradation of the polyethylene, the wall thickness of the tank and the environmental conditions. There are no results available on the long-term behaviour of the polyethylene grades used as materials for heating oil storage tanks, especially after a service life of more than 25 years.
The aim of this investigation was the determination of the factual degree of damage in comparison to the uncontaminated polyethylene grades. Data on the melt flow rate (MFR) and density of the used polyethylene grades are available because the BAM was the competent authority for the approval of the plastic heating oil storage tanks until the end of the 1980s.
The technical service of specialist companies for fuel tank disposal supplied tank sections from the bottom, the shell and the roof of 8 segregated heating oil storage tanks. Some of the tanks had been in service for more than 30 years. Two polyethylene grades mainly were used as materials for these tanks over this time. The determination of the MFR according to EN ISO 1133 and the FTIR spectroscopy followed standard test methods.
The highest average percentage increase in the MFR was determined as 31- 43 % for the bottom section of the tanks, for both the inner shell and the outer shell. The lowest increase in MFR was measured for the top of the tank, with 6 - 12 % for the inner shell and 0 - 8 % for the outer shell. The tank shell sections had an average percentage increase in MFR of 10 - 33 % for the inner shell and of 14 - 40 % for the outer shell.
The oxidative damage of the polyethylene grades was highest in the bottom area due to the permanent contact with the heating oil and degradation products.
The microtome cuttings were analyzed with image-guided infrared microscopy in the transmission mode and confirmed the results obtained with the MFR measurements.
In summary it can be concluded that the oxidative damage of the polyethylene grades after long-term contact with heating oil is relative low.
The chemical industry has expressed great interest in using polyethylene terephthalate (PET) as material for packagings for the transport of dangerous goods. Due to the high strength and stiffness of PET, the wall thickness and weight of packagings can be reduced.
The aim of this work was to find a laboratory test method for the determination of the stress cracking resistance of PET. One test method is the Full Notch Creep Test (FNCT), which was developed for polyethylene (PE) and is described in the standards EN ISO 13274 and EN 15507. It was investigated whether testing specimens made of PET with a full coplanar notch around the middle of the specimens show weakening after the impact of a tensile force in a wetting solution at 50°C. Unfortunately, this method couldn’t be used for PET because the specimens broke during notching due to the high brittleness of PET. The molding of the sheets and the following temper process for twelve hours are very time-consuming, Another possibility is laid down in BAM’s Dangerous Goods Rule BAM-GGR 015. This test was carried out with 1l PET bottles, which were filled with a 5% wetting solution and mounted with a clamping tool for 28 days at 40°C. Tensile test specimens were cut out afterwards from the middle of the bottles in the deformed areas. The tensile properties of the PET specimens couldn’t be determined due to the hardness of the material.
In conclusion, the only way to provide information about the stress cracking resistance of PET was to perform stacking tests with PET design types of packagings. 1l bottles made of PET were filled with a 5% wetting solution and stored with a stacking load for 28 days at 40°C according to EN ISO 16495. The test bottles of PET passed the stacking tests.
Polyethylene terephthalate (PET) is used as material for packagings for the transport of dangerous goods due to its high strength and stiffness. For this reason, the wall thickness and weight of the packagings can be reduced.
According to the European dangerous goods regulations RID and ADR, samples of PET design types of packagings for dangerous goods must be pre-stored with the original filling good for six months at 23 °C, before the design type tests can be carried out. For packagings made of polyethylene (PE) tests to prove the stress cracking resistance by using laboratory methods are possible to reduce time and costs. Therefore, standard liquids, simulating the different types of damaging effects on PE are defined in RID and ADR. However, there is no information and research available about the damaging mechanisms on PET, especially regarding to stress cracking resistance and test methods.
One laboratory test method is the Full Notch Creep Test (FNCT), which was developed for polyethylene (PE) and is described in the standards EN ISO 13274 and EN 15507. It was investigated whether testing specimens made of PET with a full coplanar notch around the middle of the specimens show weakening after the impact of a tensile force in the standard liquid (5 % wetting solution) at 50 °C. The tests showed that this method couldn’t be used for PET because the specimens broke during notching due to the high brittleness of PET. Another disadvantage is the very time-consuming temper process for twelve hours after molding of the sheets.
Another test method is described in BAM’s Dangerous Goods Rule BAM-GGR 015. This test was carried out with 1l PET bottles, which were filled with a 5% wetting solution and mounted with a clamping tool for 28 days at 40°C. Tensile test specimens were cut out afterwards from the middle of the bottles in the deformed areas. The tensile properties of the PET specimens couldn’t be determined due to the hardness of the material.
The only test method to provide information about the stress cracking resistance of PET was to perform stacking tests with PET design types of packagings. 1l bottles made of PET were filled with the standard liquid (5 % wetting solution) and stored with a stacking load for 28 days at 40°C according to EN ISO 16495. The test bottles of PET passed the stacking tests.
In conclusion, samples of PET design types of packagings for dangerous goods must be pre-stored with the original filling good for six months at 23 °C, before the design type tests can be carried out.
Changes in fuel composition and the introduction of alternative fuels often create problems of corrosion and degradation in materials. The objective of this research was to determine the corrosion behaviour of commercial metallic tank materials (unalloyed steels, austenitic CrNi- and CrNiMo-steels, aluminium and its alloys) in fuels and heating oil with admixtures of biogenic sources, such as gasoline with addition of ethanol (E10, E85), pure biodiesel and heating oil with 10 % biodiesel (B10).
Metallic tank materials were evaluated as resistant in a liquid if the annual corrosion rate due to uniform corrosion did not exceed 0.1 mm/year, and localized corrosion effects in the form of pitting corrosion, stress corrosion cracking and crevice corrosion did not occur.
The corrosion rates of the tank materials after exposure to E10, E85, non-aged and two-year aged pure biodiesel, and non-aged and one-year aged heating oil B10 for four weeks at 50 °C, according to DIN 50905/4, were well below the limit of 0.1 mm/year. For the unalloyed steels, the formation of rust was observed independently of the biofuels amount of ageing. U-bend specimens made of unalloyed steel were not damaged in form of stress corrosion cracking in all test fuels at this test temperature.
Changes in fuel composition and the introduction of alternative fuels often create problems of corrosion and degradation in materials. The objective of this research was to determine the corrosion behaviour of commercial metallic tank materials (unalloyed steels, austenitic CrNi- and CrNiMo-steels, aluminium and its alloys) in fuels and heating oil with admixtures of biogenic sources, such as gasoline with addition of ethanol (E10, E85), pure biodiesel and heating oil with 10 % biodiesel (B10).
Metallic tank materials were evaluated as resistant in a liquid if the annual corrosion rate due to uniform corrosion did not exceed 0.1 mm/year, and localized corrosion effects in the form of pitting corrosion, stress corrosion cracking and crevice corrosion did not occur.
The corrosion rates of the tank materials after exposure to E10, E85, non-aged and two-year aged pure biodiesel, and non-aged and one-year aged heating oil B10 for four weeks at 50 °C, according to DIN 50905/4, were well below the limit of 0.1 mm/year. For the unalloyed steels, the formation of rust was observed independently of the biofuels amount of ageing. U-bend specimens made of unalloyed steel were not damaged in form of stress corrosion cracking in all test fuels at this test temperature.
The objective of this research was to determine the resistance of frequently used sealing materials such as EPDM, FKM, FVMQ, CR, CSM, IIR, NBR, PA, PUR and VMQ in aged biodiesel and heating oil B10 with 10 % biodiesel.
The mass, tensile strength, breaking elongation and Shore hardnesses of the test specimens were determined before and after exposure in non-aged, one-year, two-year, three-year and four-year aged biodiesel and B10 at 20 °C, 40 °C and 70 °C.
A threshold for the reduction in tensile properties and Shore hardness is not set in the international standards. Therefore, a threshold of 15 % was set for the evaluation of the compatibility. The decrease in tensile properties and Shore hardness increased with the age and the temperature of the biodiesel and the heating oil.
The age of the biodiesel was not relevant for the sealing materials CR, CSM, EPDM, IIR and NBR, which were generally not resistant to biodiesel and B10. FKM and PA showed high compatibility in non-aged and aged biodiesel. FVMQ and PA could be evaluated as resistant in non-aged and aged B10 at 20°C and 40°C, whereas FKM was resistant up to 70°C despite of the age of B10.
The objective of this research was to determine the resistance of frequently used sealing materials such as EPDM, FKM, FVMQ, CR, CSM, IIR, NBR, PA, PUR and VMQ in aged biodiesel and heating oil B10 with 10 % biodiesel.
The mass, tensile strength, breaking elongation and Shore hardnesses of the test specimens were determined before and after exposure in non-aged, one-year, two-year, three-year and four-year aged biodiesel and B10 at 20 °C, 40 °C and 70 °C.
A threshold for the reduction in tensile properties and Shore hardness is not set in the international standards. Therefore, a threshold of 15 % was set for the evaluation of the compatibility. The decrease in tensile properties and Shore hardness increased with the age and the temperature of the biodiesel and the heating oil.
The age of the biodiesel was not relevant for the sealing materials CR, CSM, EPDM, IIR and NBR, which were generally not resistant to biodiesel and B10. FKM and PA showed high compatibility in non-aged and aged biodiesel. FVMQ and PA could be evaluated as resistant in non-aged and aged B10 at 20°C and 40°C, whereas FKM was resistant up to 70°C despite of the age of B10.
The objective of this research was to determine the resistance of frequently used sealing materials such as FKM, FVMQ, VMQ, EPDM, CR, CSM, IIR, PA, NBR and PUR in fuels and heating oil with and without admixtures of biogenic sources such as E10, diesel fuel with 5 % biodiesel, non-aged and 2 year aged B10 (heating oil with 10 % biodiesel), pure diesel, standard heating oil and premium grade fuel Super plus at 20 °C, 40 °C and 70 °C.
Mass, tensile strength and breaking elongation of the test specimens were determined before and after the exposure for 84 days in the fuels. The visual examination of some elastomer test specimens clearly showed the great volume increase until break or partial dissolution. Shore hardness A and D (for PA) were determined before and after exposure of the test specimens in the biofuels for 42 days.
There is not determined a threshold for the reduction in tensile properties and Shore hardness in the international standards. Therefore a threshold of 15 % was determined for the evaluation of the compatibility.
In summary, it can be therefore stated that the chemical resistance of the fluoropolymers FKM and FVMQ in fuels and biofuels is the best one.
The chemical industry has expressed great interest in using polyethylene terephthalate (PET) as material for packagings for the transport of dangerous goods. Due to the high strength and stiffness of PET, the wall thickness and weight of packagings can be reduced. This is a relevant cost factor. PET is a semi-crystalline thermoplast which is produced by polycondensation of terephthalic acid and ethylene glycol.
According to the European dangerous goods regulations RID and ADR, samples of PET design types of packagings for dangerous goods must be pre-stored with the original filling good for six months at 23°C, before the design type tests can be carried out. For packagings made of polyethylene (PE) tests to prove the stress cracking resistance by using laboratory methods are possible to reduce time and costs. Therefore, standard liquids, simulating the different types of damaging effects on PE are defined in RID and ADR. However, there is no information and research available about the damaging mechanisms on PET in comparison to PE, especially regarding to stress cracking resistance and test methods.
The aim of this work is to compare the stress cracking resistance of PE and PET with the Full Notch Creep Test (FNCT), which was developed by chemical industry and is described in the standards EN ISO 16101 and EN 15507. It was investigated whether testing specimens made of PE and PET with a full coplanar notch around the middle of the specimens show weakening after the impact of a tensile force in a wetting solution (Lutensol® FSA 10) at 50°C in a test device on the basis of the FNCT.
The test results confirmed the suitability of the method for eight PE grades. Unfortunately, this method couldn’t be used for PET because the specimens broke during notching. In addition the molding of the sheets and the following temper process for twelve hours are very time-consuming, and the specimens broke during notching due to the high brittleness of PET.
Another possibility to provide evidence of stress cracking resistance of PE packagings is laid down in BAM’s Dangerous Goods Rule BAM-GGR 015. This test was carried out with PE and PET bottles to compare both materials. Therefore 1l test bottles were filled with a 5% wetting solution and mounted with a clamping tool for 28 days at 40°C. Tensile test specimens were cut out afterwards from the middle of the bottles in the deformed areas. Tensile strength and breaking elongation of PE specimens were determined in comparison to the PET specimens. The tensile properties of the PET specimens couldn’t be determined due to the strength and the stiffness of the material.
In conclusion the only way to provide information about the stress cracking resistance of PET was to perform stacking tests. 1l bottles made of PE and PET were filled with a 5% wetting solution and stored with a stacking load for 28 days at 40°C according to EN ISO 16495. Design types of PE and PET both passed the stacking tests.
Materials compatibility is a major concern whenever the fuel composition is changed in a fuel system. The question arises of whether sealing materials are resistant to fuels with bioethanol and biodiesel (rapeseed oil fatty acid methyl ester).
The objective of this research was to determine the resistance of frequently used sealing materials such as FKM (fluorocarbon rubber), FVMQ (methyl-fluoro-silicone rubber), VMQ (methyl-vinyl-silicone rubber), EPDM (ethylene-propylene-diene rubber), CR (chloroprene rubber), CSM (chlorosulfonated polyethylene), IIR (butyl rubber), PA (polyamides), NBR (acrylonitrile-butadiene rubber) and PUR (polyester urethane rubber) in aged fuels and heating oil with admixtures of biogenic substances such as biodiesel and B10 (heating oil with 10% biodiesel).
The mass, tensile strength and breaking elongation of the test specimens were determined before and after exposure for 84 days in non-aged, one-year, two-year, three-year and four-year aged biodiesel and B10 according to DIN 53504 – “Testing of rubber - determination of tensile strength at break, tensile stress at yield, elongation at break and stress values in a tensile test”.
The visual examination of some elastomer test specimens clearly showed the great volume increase until breaking or partial dissolution. The Shore hardnesses A and D (for PA) were determined before and after exposure of the test specimens in the biofuels for 42 days according to DIN 53505 – “Testing of rubber – Shore A and Shore D hardness test”.
A threshold for the reduction in tensile properties and Shore hardness is not set in the international standards. Therefore, a threshold of 15 % was set for the evaluation of the compatibility.
Biodiesel fuels are easily oxidized and contain acids and water. The age of the biodiesel was not relevant for the sealing materials CR, CSM, EPDM, IIR and NBR, which were generally not resistant to biodiesel. FKM and PA showed high compatibility in non-aged, one-year, two-year, three-year and four- year aged biodiesel, which was attributed to the absence of polarity. The decrease in tensile properties and Shore hardness increased with the age and the temperature of the biodiesel, but the measured values were still lower than the defined threshold.
FKM and FVMQ absorbed much less non-aged and aged B10 and swelled less. CR, CSM, EPDM, IIR, NBR and VMQ were not resistant to B10 at all at 20°C, 40°C and 70°C as the decrease in the tensile properties was significantly over 50%.
FVMQ and PA could be evaluated as resistant in non-aged and aged B10 at 20°C and 40°C, whereas FKM was resistant up to 70°C despite the age of the B10. The damaging impact of B10 increased with the age and the temperature.
Impact of biocomponents in the fuel and heating oil on the compatibility of sealing materials
(2016)
The objective of this research was to determine the resistance of frequently used sealing materials such as FKM, FVMQ, VMQ, EPDM, CR, CSM, IIR, PA, NBR and PUR in fuels and heating oil with and without admixtures of biogenic sources such as E10, diesel fuel with 5 % biodiesel, non-aged and 2 year aged B10 (heating oil with 10 % biodiesel), pure diesel, standard heating oil and premium grade fuel Super plus at 20 °C, 40 °C and 70 °C.
Mass, tensile strength and breaking elongation of the test specimens were determined before and after the exposure for 84 days in the fuels. The visual examination of some elastomer test specimens clearly showed the great volume increase until break or partial dissolution. Shore hardness A and D (for PA) were determined before and after exposure of the test specimens in the biofuels for 42 days.
There is not determined a threshold for the reduction in tensile properties and Shore hardness in the international standards. Therefore a threshold of 15 % was determined for the evaluation of the compatibility.
In summary, it can be therefore stated that the chemical resistance of the fluoropolymers FKM and FVMQ in fuels and biofuels is the best one.
Impact of biocomponents in the fuel and heating oil on the compatibility of sealing materials
(2016)
The objective of this research was to determine the resistance of frequently used sealing materials such as FKM, FVMQ, VMQ, EPDM, CR, CSM, IIR, PA, NBR and PUR in fuels and heating oil with and without admixtures of biogenic sources such as E10, diesel fuel with 5 % biodiesel, non-aged and 2 year aged B10 (heating oil with 10 % biodiesel), pure diesel, standard heating oil and premium grade fuel Super plus at 20 °C, 40 °C and 70 °C.
Mass, tensile strength and breaking elongation of the test specimens were determined before and after the exposure for 84 days in the fuels. The visual examination of some elastomer test specimens clearly showed the great volume increase until break or partial dissolution. Shore hardness A and D (for PA) were determined before and after exposure of the test specimens in the biofuels for 42 days.
There is not determined a threshold for the reduction in tensile properties and Shore hardness in the international standards. Therefore a threshold of 15 % was determined for the evaluation of the compatibility.
In summary, it can be therefore stated that the chemical resistance of the fluoropolymers FKM and FVMQ in fuels and biofuels is the best one.