One of the biggest problems in high-voltage silicone rubber insulation cable accessories is the damage on electrical treeing, initiated by partial discharges. The electrical treeing starts at unavoidable imperfections inside the material or at interfaces. The damage is usually irreversible and leads around the starting points to a partial destruction of the material. To prolong the lifetime and thereby to increase the assurance of the structural component commonly, for mechanical improvement constituted filler is modified to obtain a self-healing silicone rubber. Damage mechanism is analysed to address the filler to the damage mode.
To avoid a catastrophic failure of insulation in high-voltage (HV) applications, a monitoring of partial discharges (PD) is necessary. Fluorescently labelled polymer optical fibres (F-POF) offer an electrically passive method for PD detection in HV facilities. F-POF could be embedded into HV cable insulation material, which are usually made of silicone rubber. Due to the difficult accessibility of HV cable accessories, a self-healing silicone rubber, based on incorporated capsules, with prolonged service life after PD detection represents an attractive material design for HV electrical insulation.