Wissenschaftliche Artikel der BAM
Filtern
Dokumenttyp
Schlagworte
- Dust explosions (2)
- Hybrid mixtures (2)
- Lithium-ion battery (2)
- Thermal runaway (2)
- 20L-sphere (1)
- Alternative Energieträger (1)
- Battery (1)
- Consequences (1)
- Explosion limit (1)
- Explosionsschutz (1)
Organisationseinheit der BAM
- 2.1 Sicherheit von Energieträgern (8) (entfernen)
Paper des Monats
- ja (1)
In this paper, we investigate the evaporation mass flow originating from spills of gas-oline. Large spills of gasoline may form during partial or complete roof sinkings or inthe case of perforations at various deck fittings at external floating roof tanks usedfor the storage. Additionally, spills may form in the retention area in the case of leak-ages at pipes or at the hull. The aim is to predict the order of magnitude of real-scaleevaporation mass flow. The determined evaporation mass flows will be used in arelated project as input values for subsequent dispersion modeling in the vicinity ofthe tanks. This is relevant for questions of fire and explosion protection as well as forenvironmental protection aspects in tank farms or refineries, which use externalfloating roof tanks. The measurements presented in this paper were compared withpredictions by empirical models and investigations of evaporations from small floorspills, round-bottom flask, or from Petri dishes published in the literature. The maingoal of this paper is to test the applicability of empirical models to provide reasonableevaporation mass flows as input for CFD dispersion simulations.
For a comprehensive safety assessment of stationary lithium-ion-battery applications, it is necessary to better understand the consequences of thermal runaway (TR). In this study, experimental tests comprising twelve TR experiments including four single-cell tests, two cell stack tests and six second-life module tests (2.65 kW h and 6.85 kW h) with an NMC-cathode under similar initial conditions were conducted. The temperature (direct at cells/modules and in near field), mass loss, cell/module voltage, and qualitative vent gas composition (Fourier transform infrared (FTIR) and diode laser spectroscopy (DLS) for HF) were measured. The results of the tests showed that the battery TR is accompanied by severe and in some cases violent chemical reactions. In most cases, TR was not accompanied by pregassing of the modules. Jet flames up to a length of 5 m and fragment throwing to distances to more than 30 m were detected. The TR of the tested modules was accompanied by significant mass loss of up to 82%. The maximum HF concentration measured was 76 ppm, whereby the measured HF concentrations in the module tests were not necessarily higher than that in the cell stack tests.
Subsequently, an explosion of the released vent gas occurred in one of the tests, resulting in the intensification of the negative consequences. According to the evaluation of the gas measurements with regard to toxicity base on the “Acute Exposure Guideline Levels” (AEGL), there is some concern with regards to CO, which may be equally as important to consider as the release of HF.
Influence of pre-ignition pressure rise on safety characteristics of dusts and hybrid mixtures
(2021)
For the determination of the safety characteristics of dusts it is necessary to disperse the dust in the oxidating atmosphere (usually air). In the standard procedures for dusts this is realized by a partially evacuated explosion vessel (20L-sphere) in which the dust gets injected from a dust chamber pressurized with air. Shortly after that injection (60 ms) the dust cloud gets ignited under turbulent conditions, that are otherwise seen as almost ambient with 20 ◦C and about 1 bar (abs). While there has been a lot of research about the influence of the ignition delay time and the level of turbulence in the recent years little attention was paid to the pre–ignition pressure rise and the allowed variations in the standards. In the following work we showed that the allowed ranges for the pressures in the different dust standards influence the safety characteristics of dust alone severely.
Even though hybrid mixtures are an emerging risk problem in an interconnected industry there is no standard for the determination of their safety characteristics. In this work it is shown that especially for the preparation of hybrid mixtures of flammable dust and gas the pressures after injection of the dust and the mixing procedure have a large influence on the composition of the tested mixtures and therefore on the safety characteristics.
Considering both effects, wrong concentration of gas and wrong initial pressure, the discrepancy of safety characteristics from different facilities will be too big to applicable. The methods to overcome these weaknesses are also presented.
The production of materials with dimensions in the nanometre range has continued to increase in recent years. In order to ensure safety when handling these products, the hazard potential of such innovative materials must be known. While several studies have already investigated the effects of explosions (such as maximum explosion pressure and maximum pressure rise) of powders with primary particles in the nanometre range, little is known about the ignition temperatures and flame velocities. Therefore, the minimum ignition temperature (MIT) of metallic nano powders (aluminium, iron, copper and zinc) was determined experimentally in a so called Godbert-Greenwald (GG) oven. Furthermore, the flame velocities were determined in a vertical tube. In order to better classify the test results, the tested samples were characterised in detail and the lower explosion limits of the tested dust samples were determined. Values for the burning velocity of aluminium nano powders are higher compared to values of micrometre powders (from literature). While MIT of nanometre aluminium powders is within the range of micrometre samples, MIT of zinc and copper nano powders is lower than values reported in literature for respective micrometre samples.
Quasi-static dispersion of dusts for the determination of lower explosion limits of hybrid mixtures
(2020)
Knowledge of explosion limiting concentration of explosible materials is necessary for the design of explosion protection measures. Currently employed methods of testing MEC of a dust cloud or LEL of a hybrid mixture are based on arbitrary assumptions and possess technical limitations that often lead to values of MEC/LEL, which are unrealistically low or poorly reproducible.
This contribution presents an improved method for experimental determination of MEC of a combustible dust cloud or LEL of a flammable gas or hybrid mixture. The new set-up operates under laminar conditions and allows a uniform suspension of dust particles in an open top acrylic glass tube. Dust concentration is measured with the help of infrared sensors installed a few centimeters above and below the ignition source.
In order to evaluate the dependence of MEC on flow front velocity, MEC of lycopodium was determined at four flow velocities. The results show that the flow field intensity does not significantly influence the MEC of lycopodium for the flow ranges tested in this work. Moreover, LEL of hybrid mixtures of lycopodium and methane was also tested at flow velocities of 4.7 cm/s, 5.8 cm/s, 7 cm/s and 11 cm/s and compared with the values obtained from other sources. The results suggest that the requirement of high energy pyrotechnical igniter may be relinquished, provided that a truly homogeneous suspension of dust particles could be achieved.
Moreover, the effect of relative amount of dust and gas, on the course of ignition and flame propagation in hybrid mixtures at their LEL, was studied by the help of high speed videos. For hybrid mixtures of carbonaceous dusts (like lycopodium) at their LEL, ignition occurs in the gas phase, however, flame propagation is only possible through a two-way interaction of dust and gas during the course of combustion.
Die Einführung von Wasserstoff als sicherer Energieträger braucht eine robuste Wissensbasis, darauf aufgebaute Werkzeuge zur Auslegung und Sicherheitsbewertung von Wasserstofftechnologien und ein international harmonisiertes Regelwerk. Viele der innovativen Technologien implizieren Wasserstoff bei hohen Drücken und/oder kryogenen Temperaturen, mit denen in verteilten Anwendungen erstmalig private Nutzer in Kontakt kommen. Um überkonservative, teure Sicherheitslösungen zu vermeiden, gleichzeitig aber die Einsetzbarkeit und Sicherheit von Wasserstoffanwendungen zu demonstrieren und die Akzeptanz für die Technologie aufrecht zu halten, muss auch die Sicherheitsforschung mit den Trends der technologischen Entwicklung Schritt halten, oder sie besser noch antizipieren. So beschreibt dieser Überblicksartikel nicht nur den gegenwärtigen Stand der Kenntnisse und Technik bezüglich Wasserstoffsicherheit, sondern auch ihre Weiterentwicklung.
Composition and Explosibility of Gas Emissions from Lithium-Ion Batteries Undergoing Thermal Runaway
(2023)
Lithium-based batteries have the potential to undergo thermal runaway (TR), during which mixtures of gases are released. The purpose of this study was to assess the explosibility of the gaseous emission from LIBs of an NMC-based cathode during thermal runaway. In the current project, a series of pouch lithium-based battery cells was exposed to abuse conditions (thermal) to study the total amount of gases released and the composition of the gas mixture. First, the battery cells were placed in a closed vessel, and the pressure and temperature rise inside the vessel were measured. In a second step, the composition of gases was analysed using a Fourier transform Infrared (FTIR) spectrometer.
We found that the amount of released gases was up to 102 ± 4 L, with a clear dependence on the battery capacity. This study showed that the concentration of gaseous emissions such as carbon monoxide (CO), methane (CH4), ethylene (C2H4), ethane (C2H6), and hydrogen cyanide (HCN) increased with higher cell capacity. Of the five studied flammable gases, the maximum concentrations of carbon monoxide (16.85 vol%), methane (7.6 vol%), and ethylene (7.86 vol%) were identified to be within their explosible range. Applying Le Chatelier’s law, a calculated lower explosion limit (LEL) of 7% in volume fraction was obtained for the gas mixture. The upper explosion limit (UEL) of the gas mixture was also found to be 31% in volume. A filter comprising pyrobubbles was used for the removal of the studied gas components released during the thermal abuse. The investigation revealed that the pyrobubbles filter was highly effect in the removal of HCN (up to 94% removal) and CO2 (up to 100% removal). Herein, we report the dependency of the method of thermal runaway trigger on the measured maximum temperature.
In this study, 19 experiments were conducted with 25 pouch cells of NMC cathode to investigate thermal runaway and the release of gases from lithium-ion batteries (LIBs). Single cells, double cells, and a four-cell battery stack were forced to undergo thermal runaway inside an air-tight reactor vessel with a volume of 100 dm3 . The study involved two series of tests with two types of ignition sources. In the Series 1 tests, a heating plug was used to initiate thermal runaway in LIBs in the ranges of 80–89% and 90–100% SOC. In the Series 2 tests, a heating plate was used to trigger thermal runaway in LIBs in the ranges of 30–50%, 80–89%, and 90–100% SOC. Thermal runaway started at an onset temperature of 344 ± 5 K and 345 K for the Series 1 tests and from 393 ± 36 K to 487 ± 10 K for the Series 2 tests. Peak reaction temperatures ranged between 642 K and 1184 K, while the maximum pressures observed were between 1.2 bar and 7.28 bar. Thermal runaway induced explosion of the cells and lead to a rate of temperature increase greater than 10 K/s. The amounts of gases released from the LIBs were calculated from pressures and temperatures measured in the reactor.
Then, the gas composition was analyzed using a Fourier transform infrared (FTIR) spectrometer. The highest gaseous production was achieved at a range of 90–100% SOC and higher battery capacities 72 L, 1.8 L/Ah (Series 1, battery stack) and 103 L, 3.2 L/Ah (Series 2, 32 Ah cell)). Among the gases analyzed, the concentration of gaseous emissions such as C2H4 , CH4 , and C2H6 increased at a higher cell capacity in both series of tests. The study results revealed characteristic variations of thermal behavior with respect to the type of ignition source used.