Wissenschaftliche Artikel der BAM
Filtern
Erscheinungsjahr
- 2019 (3) (entfernen)
Dokumenttyp
Schlagworte
- Condition monitoring (1)
- Dampfdruck (1)
- Distributed acoustic sensing (DAS) (1)
- Distributed vibrations sensing (DVS) (1)
- Fiber-optic sensing (1)
- Frequenzanalyse (1)
- Gas explosion (1)
- Lache (1)
- Pipeline integrity (1)
- Rissbildung in Stahl (1)
Organisationseinheit der BAM
- 2 Prozess- und Anlagensicherheit (3)
- 2.1 Sicherheit von Energieträgern (3)
- 8 Zerstörungsfreie Prüfung (2)
- 8.1 Sensorik, mess- und prüftechnische Verfahren (1)
- 8.4 Akustische und elektromagnetische Verfahren (1)
- 8.6 Faseroptische Sensorik (1)
- 9 Komponentensicherheit (1)
- 9.6 Additive Fertigung metallischer Komponenten (1)
When handling flammable or toxic liquids or liquefied gases, the occurrence of a leakage and formation of a liquid pool is a scenario to be considered for risk assessment. Several models are available for the estimation of the evaporating mass flow, but only a very reduced number of experimental data is available for Validation purposes.
In the last years, the Federal Institute for Materials Research and Testing (BAM) in Berlin, Germany, carried out pool Evaporation experiments with different substances in basins with a Diameter ranging from 0,50 m to 1 m mainly on open air test sites with a built up (inner city) and a non-built-up (flat terrain) topography, but also in an enclosed space. The resulting experimental data sets cover a range of vapor pressures from 0,1 bar to 0,94 bar.
The aim of this work is to make the füll data set publicly available and to provide a description of the experimental boundary conditions.
Based on these data, a Validation of existing pool Evaporation models has been carried out and eventually led to a new formulation of an evaporation model, which is also presented here, covering the whole ränge from low wind speeds up to high vapor pressures.
Pipe integrity is a central concern regarding technical safety, availability, and environmental compliance of industrial plants and pipelines. A condition monitoring system that detects and localizes threats in pipes prior to occurrence of actual structural failure, e.g., leakages, especially needs to target transient events such as impacts on the pipe wall or pressure waves travelling through the medium. In the present work, it is shown that fiber-optic distributed acoustic sensing (DAS) in conjunction with a suitable application geometry of the optical fiber sensor allows to track propagating acoustic waves in the pipeline wall on a fast time-scale. Therefore, short impacts on the pipe may be localized with high fidelity. Moreover, different acoustic modes are identified, and their respective group velocities are in good agreement with theoretical predications. In another set of experiments modeling realistic damage scenarios, we demonstrate that pressure waves following explosions of different gas mixtures in pipes can be observed. Velocities are verified by local piezoelectric pressure transducers. Due to the fully distributed nature of the fiber-optic sensing system, it is possible to record accelerated motions in detail. Therefore, in addition to detection and localization of threatening events for infrastructure monitoring, DAS may provide a powerful tool to study the development of gas explosions in pipes, e.g., investigation of deflagration-to-detonation-transitions (DDT).
Um ein tieferes Verständnis über die Schallemission bei der Entstehung und Ausbreitung von Rissen in Stahlrohrleitungen zu erlangen, wurde ein Stahlrohr der Güte S355J2H im Vierpunkt-Biegeversuch quasistatisch bis hin zum Wanddurchbruch (Leckage) belastet und mittels Schallemissionsmessung und Gleichstrompotentialmessung überwacht. Das Rohrsegment wurde durch einen 90°- Außenumfangskerb in der Mitte der Rohrlänge definiert vorgeschädigt, um davon ausgehend ein stabiles Risswachstum zu induzieren und die Analyse von Schallemission aus Rissereignissen, die am Kerb eintraten, sicherzustellen. Für die Schallemissionsmessung wurden vier Breitbandsensoren max. 105 mm vom Kerb entfernt montiert. Die Signalaufzeichnung erfolgte kontinuierlich und schwellwertunabhängig. Für die Gleichstrompotentialmessung wurde ein Gleichstrom von 300 A eingeleitet und der Potentialabfall über dem Kerb mit fünf Sonden entlang des Kerbs gemessen. Beide Messverfahren identifizieren die Rissinitiierung sowie Veränderungen im Risswachstum. Die detektierten Schallemissionsereignisse werden, unter Berücksichtigung spektraler Eigenschaften, mit fortschreitender Belastung und Rissentwicklung analysiert. Diese Studien wurden im Rahmen des interdisziplinären Forschungsprojekts AGIFAMOR, Aging infrastructure - Faseroptisches Monitoring von Rohrleitungen, an der BAM durchgeführt.