Minimum explosion concentration (MEC) of three agriculture dusts and two coal dusts was studied via a 20-L explosion chamber to reveal the role of gaseous inhibitors. Both active method (CO2 diluting air) and passive method (CO2 replacing O2) were used. The TG and DTG thermal analysis tests were conducted to study the pyrolysis and combustion characteristics of dust samples. An alternative explosion criterion based on combustion duration time was used to determine MEC, and compared with the standardized overpressure method. Under 10-kJ ignition condition, as oxygen mole fraction (XO2) decreased from 21% to 10%, MEC of agriculture dusts and coal dusts respectively increased by around 5 times and 2 times. The active inerting method with a lower N2/CO2 ratio was found to have a better suppression effect on the explosion of the five carbonaceous dusts because the blend has a higher specific heat and a lower oxygen diffusion rate.
MIKE III apparatus tests were conducted to investigate the minimum ignition energy (MIE) of coal dusts in air and O2/CO2 atmospheres with and without small amount of CH4/H2. The O2 mole fraction (XO2) in the gas mixtures varied from 21% to 50% with the CH4/H2 mole fraction from 0 to 2%. Experimental result showed that MIE of coal dusts significantly decreases even by three orders of magnitude in mJ with increasing XO2 and the addition of CH4/H2. Compared with CH4, H2 had a relatively strong promotion effect on the spark ignition of coal dusts. The inhibiting effect of CO2 was found to be much stronger than N2, but this inhibiting effect of CO2 could be eliminated by 9% increment of XO2. The effect on MIE of coal dusts thus followed by the order: 9% increment of XO2 > CO2 replacing N2 > 2% CH4 or H2 addition. Moreover, two empirical models were used to estimate the MIE of hybrid dust-gas mixture (HMIE), and the results showed that calculated data can well reflect the promoting effect of elevated XO2 and flammable gas addition, and the inhibiting effect of inert gas
Minimum ignition temperature of dust clouds (MITC) was studied experimentally and theoretically in different atmospheres. Three carbonaceous dusts were tested in both air and O2/CO2 atmospheres with CH4 mole fraction from 0 to 2%. Results showed that the ignition risk of the three dusts significantly increases (decrease of MITC by ~100 ℃) with increasing XO2 from 21% to 50%, but significantly decreases replacing N2 in air with CO2. The inhibition effect of CO2 on MITCs could be diminished by increasing XO2 or adding CH4. The addition of small amount of CH4 has different effects on the MITCs of different dust samples, following the opposite order of volatile matter content: anthracite>bituminous coal>starch. Two modified steady-state ignition models, considering the density of mixture gas and dust cloud, XO2 and its diffusivity, were developed to interpret the experimental observations. The analysis revealed that the global heterogeneous ignition model suits well for the hybrid mixtures of anthracite or bituminous coal dusts. In contrast, the proposed global homogeneous ignition model was found to be only valid for the pure starch dust, and the extra CH4 addition could strongly affect the ignition process of starch, particularly in O2/CO2 atmospheres with higher XO2.
The explosion characteristics of anthracite coal dust with/without small amount of CH4 (1.14 vol %) were investigated by using a 20 L spherical explosion apparatus with an emphasis on the roles of oxygen mole fraction and inert gas. Two methods based on overpressure and combustion duration time were used to determine the minimum explosion concentration (MEC) or the lower explosion limit (LEL) of the pure anthracite coal dust and the hybrid coal-methane mixtures, respectively. The experiment results showed that increasing oxygen mole fraction increases the explosion risk of coal dust: with increasing oxygen mole fraction, the explosion pressure (Pex) and the rate of explosion pressure rise ((dp/dt)ex)) increase, while MEC decreases. The explosion risk of anthracite dust was found to be lower after replacing N2 with CO2, suggesting that CO2 has a better inhibition effect on explosion mainly due to its higher specific heat. However, the addition of 1.14% CH4 moderates the inhibition effect of CO2 and the promotion effect of O2 on anthracite dust explosion for some extent, increasing explosion severity and reducing the MEC of anthracite dust. For hybrid anthracite/CH4 mixture explosions, Barknecht’s curve was found to be more accurate and conservative than Chatelier’s line, but neither are sufficient from the safety considerations. The experimental results provide a certain help for the explosion prevention and suppression in carbonaceous dust industries.
Gaseous inhibitors are used in many industries for the explosion prevention of combustible dusts, mitigating the potential hazard to humans, properties and environments. This work experimentally and theoretically studied the inerting effect of gaseous inhibitors on the ignition process of dust clouds in O2/N2/CO2 atmospheres, with an emphasis on the role of the CO2/N2 ratio. 10 different combustible carbonaceous dusts were selected, including grain dust, biomass dust and coal dust. Experimental results showed that the inhibition effect of CO2/N2 is closely related to the ignition mechanism of dust clouds. Specifically, a higher ratio of CO2/N2 yields a stronger inhibition effect on the ignition process of dust samples with relatively low volatile matter contents predominated by heterogeneous ignition. In addition, two novel steady-state ignition mechanism models were developed to interpret the experimental observations. Maxwell-Stefan equations were used to describe the diffusivity in the ternary O2/N2/CO2 gas mixtures. The analytical results were in good agreement with the experimental data of the minimum ignition temperature of dust cloud (MITC) in oxygen-lean atmospheres. The mechanism modelling can be used to estimate the critical ignition temperature of all carbonaceous dust clouds with a wide range of volatile matter content under different inert atmospheres, which will provide a reference for the explosion hazard assessment of dust posed by a hot surface in the process industries.
Laboratory test results are of vital importance for correctly classifying and labelling chemicals as “hazardous” as defined in the UN Globally Harmonized System (GHS) / EC CLP Regulation or as “dangerous goods” as defined in the UN Recommendations on the Transport of Dangerous Goods. Interlaboratory tests play a decisive role in assessing the reliability of laboratory test results. Interlaboratory tests performed over the last 10 years have examined different laboratory test methods. After analysing the results of these interlaboratory tests, the following conclusions can be drawn:
1. There is a need for improvement and validation for all laboratory test methods examined.
2. To avoid any discrepancy concerning the classification and labelling of chemicals, the use of validated laboratory test methods should be state of the art, with the results accompanied by the measurement uncertainty and (if applicable) the probability of incorrect classification.
This paper addresses the probability of correct/incorrect classification (for example, as dangerous goods) on the basis of the measurement deviation obtained from interlaboratory tests performed by the Centre for quality assurance for testing of dangerous goods and hazardous substances (CEQAT-DGHS) to validate laboratory test methods. This paper outlines typical results (e.g. so-called “Shark profiles” – the probability of incorrect classification as a function of the true value estimated from interlaboratory test data) as well as general conclusions and steps to be taken to guarantee that laboratory test results are fit for purpose and of high quality.
Godbert-Greenwald furnace was used to investigate the minimum ignition temperature of dust clouds (MITC) in air with the presence of flammable gas which is lower than its lower explosion limit (LEL). Three flammable gases (CH4, H2 and CO) and three carbonaceous dusts (anthracite coal, bituminous coal and sweet potato starch) were tested. Results showed that all flammable gases have distinct effects on the MITC of the dust samples and volatile matter content of dust plays an important role during the ignition process. Specifically, the MITC of anthracite coal dust decreased from 610 °C to 560 °C, 580 °C and 570 °C with 3% CH4, 3% CO and 2.5% H2, respectively. Moreover, a heterogeneous ignition mechanism model was proposed to verify the equally global ignition characteristic between hybrid anthracite coal-CxHy mixture and bituminous coal. All three gases had an ignorable effect on the MITC of starch dust considering the experimental error. The presence of CO and H2 slightly promoted the ignition of bituminous coal dust, but the addition of CH4 showed a distinct concentration effect on the MITC of bituminous coal: the MITC decreased with 1% CH4 while increased with 2% and 3% CH4.
This negative-effect of flammable gases at such low concentrations on ignition temperature of bituminous coal dusts was found for the first time. Furthermore, the presence of the 2nd flammable gas had a smaller effect on the MITC of dust samples with a higher volatile content, resulted from the competition of heterogeneous and homogeneous ignition mechanisms.
Minimum explosion concentrations of coal dusts with CH4/H2/CO below the gas lower explosion limit
(2020)
A 20-L spherical explosion chamber was used to investigate the explosion characteristics of dust clouds in air with the presence of flammable gas which is lower than its lower explosion limit (LEL).
including minimum explosion concentration (MEC) of dust. Explosion pressure (Pex) and explosion pressure rise (dp/dt)ex). Two dust samples (anthracite coal, bituminous coal) and were three flammable gases (CH4, H2 and CO) were tested. Experimental results showed that the explosion of hybrid mixtures occurs when both dust and gas concentrations are lower than the LEL/MEC of the single substances.
Meanwhile. all flammable gases with different volume fractions have distinct effects on the MEC. Pex and (dp/dt)ex of the dust samples.
With the increase of the flammable gas concentration. either the Pex and (dp/dt)ex increase or the MEC decreases for all the hybrid mixtures of both two dust samples. At the same concentration of coal dusts. the addition of CH4 promotes higher explosion risks than the other two flammable gases. The distribution of (dp/dt)ex is quite different with the restricted area defined by empirical formulas.
These results improve our understanding of the explosion behaviour and the explosion risk of hybrid dust-gas mixtures in air.
Smouldering fires and explosions arising from self-ignition of coal dust deposits represent a serious hazard for human being, environment and industry. It is essential for plant operators to know the conditions (temperature, duration and quantity) at which storage will be safe. In this work, self-ignition behaviour of three bituminous coal dusts in large scales are theoretically studied, based on the experimental data via a standardized hot-basket apparatus. A comprehensive 2-D transient model is developed, using a 2nd-order reaction kinetics considering both coal and oxygen consumptions, to investigate self-ignition parameters of coal dust accumulations. The numerical model shows a less conservative prediction compared with the steady-state methods. The computational self-ignition temperature and ignition delay time show a satisfaction agreement with lab-scale experimental results. In addition, the influences of ambient temperature and moisture content are analysed. The result shows that the moisture content delays the ignition and a small variation of the ambient temperature nearby the critical condition will lead to a large difference of the ignition delay time.
Industrial fires and explosions initiating from self-ignition of combustible porous dust deposits represent a serious hazard for human beings, environment and industry. Understanding the fundamental basis of combustible dust ignition behaviours at different geometries is of importance to prevent and mitigate the accidental risks. A correlation of self-ignition temperatures (SITs) measured by hot-oven tests and minimum ignition temperatures of dust layers (MITLs) determined by hot-plate tests has been established previously. However, this analogy approach based on Frank-Kamenetzkii model is limited by ignoring the influence of oxygen diffusion. In this work, an improved method is developed by implementing a correction factor for the pre-exponential factor caused by the boundary geometry. This method is testified by comparing with experimental data, previous analogy method and numerical simulation. Results show that our proposed method performs a better predictability of MITLs and simplicity. The improved analogy method indicates that the different boundary geometries of a dust deposit significantly impact the apparent pre-exponential factor, while have an ignorable influence on the activation energy, which is also verified by numerical investigations. Furthermore, the numerical model with the corrected kinetic parameters provides a satisfactory explanation compared with experimental observations regarding to temperature and concentration evolutions of dust layers.