The ongoing geo-political conflicts and the increasing need for the implementation of measures to improve the energetic system sustainability are increasing the importance of tanks for storing cryogenic fluids in the energy industry. The most common example of cryogenic tank applications is the transport of natural gas and hydrogen in their liquid form (LNG and LH2 respectively) for which, considering the same transport volume cryogenic storage ensures significantly higher transport capacities with respect storage based solely on overpressure.
A common feature of all cryogenic transported fluids is that their condition must be maintained minimizing heat leaks from the environment as much as possible. This is achieved by the implementation of thermal super Insulations (TSI) systems based on e. g. rock wool, perlites, microspheres, multilayer insulations (MLI), and vacuum which have proven to be effective in applications. However, due to the relatively short period of use in some applications, the small number of documented incidents, and the still few investigations carried out in the field, the exploitation of such systems in the cryogenic fluids transport sector still suffers from insufficient knowledge about the course and consequences of incidents. Accidents involving collisions, fires, and their combination are quite common in the transportation sector and may generate extraordinary loads on the tank and its insulation system, eventually leading to tank failure.
The present study focuses on the behavior of TSI systems in tanks when it is exposed to an external heat source representative of a hydrocarbon fire scenario. This may cause an increase of the heat flux into a tank by several orders of magnitude with respect to normal design conditions, thus inducing severe and in the TSI, causing the rapid release of flammable gas and even resulting in a Boiling Liquide Expanding Vapour Explosion (BLEVE).
To study such scenarios a test rig was developed at BAM that allows testing of TSI at industrial conditions and enables subsequent analysis of TSI samples. This test rig considers the typical double-walled design of tanks for cryogenic fluids with vacuum and an additional insulating material in the interspace. Adjustable electrical heating elements simulate the fire on one side of the double wall. This process allows the implementation of repeatable heat loads of up to 100 kW/m². The other side of the double wall is represented by a fluid-supported heat exchanger, which allows the simulation of cold or cryogenic conditions in the test rig, and to determine the heat flux transmitted through the double wall. Thus, the test rig allows thermal loading and performance analysis of TSI samples at the same time.
In the presentation, the results of diverse tested TSI systems will be presented and discussed. As a result of this study, the list of advantages and disadvantages for the choice of tested TSI expands. Within the test, all samples degraded as a consequence of a hydrocarbon fire-orientated thermal load. Strong differences in the behavior of the tested TSI systems over temperature, location, and time were observed. Additionally, the tested MLI insulations were significantly more resistant to their base materials. These results are relevant for the design, the definition of national and international regulations, the Risk assessment, and the development of safety concepts for cryogenic tanks.
Liquefied Hydrogen (LH2) or Liquefied Natural Gas (LNG) establish themselves as important energy carriers in the transport sector. Its storage requires tanks with Thermal Super Insulations (TSI) to keep the transported fluid cold. TSI has proven itself in various applications over a long time, but not in the land transport sector, where accidents involving collisions, fires, and their combination are to be expected. The focus of this study is to investigate the behavior of different types of TSI when exposed to a heat source that represents a fire. Therefore, a High-Temperature Thermal Vacuum Chamber (HTTVC) was used that allows the thermal loading of thermal insulation material in a vacuum and measuring the heat flow through the TSI in parallel. Within this study, 5 samples were tested regarding 3 different types of MLI, rock wool, and perlites. The thermal exposure caused different effects on the samples. In practice, this can be connected to the rapid release of flammable gases as well as a Boiling Liquid Expanding Vapour Explosion (BLEVE). These results are relevant for the evaluation of accident scenarios, the improvement of TSI, and the development of emergency measures.
Liquefied Hydrogen (LH2) or Liquefied Natural Gas (LNG)
establish themselves as important energy carriers in the transport
sector. Its storage requires tanks with Thermal Super Insulations
(TSI) to keep the transported fluid cold. TSI has proven itself in
various applications over a long time, but not in the land
transport sector, where accidents involving collisions, fires, and
their combination are to be expected. The focus of this study is
to investigate the behavior of different types of TSI when
exposed to a heat source that represents a fire. Therefore, a High-
Temperature Thermal Vacuum Chamber (HTTVC) was used that
allows the thermal loading of thermal insulation material in a
vacuum and measuring the heat flow through the TSI in parallel.
Within this study, 5 samples were tested regarding 3 different
types of MLI, rock wool, and perlites. The thermal exposure
caused different effects on the samples. In practice, this can be
connected to the rapid release of flammable gases as well as a
Boiling Liquid Expanding Vapour Explosion (BLEVE). These
results are relevant for the evaluation of accident scenarios, the
improvement of TSI, and the development of emergency
measures.
The importance of tanks for storing cryogenic fluids in the energy industry is increasing because of ongoing political conflicts and the implementation of more environmentally friendly energy sources. Key representatives for the application of cryogenic tanks are natural gas in the form of Liquefied Natural Gas (LNG) and hydrogen, e. g. in the form of Liquefied Hydrogen (LH2), for which significantly higher transport capacities can be achieved with the same transport volume using cryogenic storages than with storages based solely on overpressure.
What applies to all cryogenic transported fluids in common is their condition that must be maintained. Hence heat flows into the preserved fluid must be minimized. Thermal super Insulations (TSI) based on e. g. multilayer insulations (MLI), perlites, and vacuum are utilized for this purpose and have already proven themselves in similar applications. However, for the use of tanks for cryogenic fluids in the transport sector, there is insufficient knowledge regarding the course and consequences of incidents, which is due to the still short period of use and the few documented incidents, hence few investigations carried out in this field. Typical scenarios in the transport sector represent car accidents with collisions, fires, and their combination, which are associated with extraordinary loads on the tank.
The focus of this study is to investigate the behavior of TSI as a result of their thermal exposure to a heat source representing a fire. It is worth mentioning that this could lead to an increase of the heat flux into a tank by several orders of magnitude, and to permanent damage of the TSI, ultimately rapid release of flammable gas as well as a Boiling Liquide Expanding Vapour Explosion (BLEVE). For this purpose, a high temperature thermal vacuum chamber (HTTVC) has been developed that allows thermal loading of MLI or perlites in a vacuum and simultaneous measurement of heat flow through this TSI. The HTTVC is designed to represent realistic insulation conditions and to withstand thermal loads from typical design fires.
The HTTVC was applied to investigate TSI based on MLI and vacuum. It is shown that the thermal stress caused permanent damage to the TSI, with shrinkage, phase change, pyrolysis, and condensation being significant damage mechanisms. The results are relevant for the evaluation of accident scenarios and can thus contribute to the improvement of TSI and the development of emergency measures for the protection of persons and infrastructures.
The importance of tanks for storing cryogenic fluids in the energy industry is increasing because of ongoing political conflicts and the implementation of more environmentally friendly energy sources. Key representatives for the application of cryogenic tanks are natural gas in the form of Liquefied Natural Gas (LNG) and hydrogen, e. g. in the form of Liquefied Hydrogen (LH2), for which significantly higher transport capacities can be achieved with the same transport volume using cryogenic storages than with storages based solely on overpressure.
What applies to all cryogenic transported fluids in common is their condition that must be maintained. Hence heat flows into the preserved fluid must be minimized. Thermal super Insulations (TSI) based on e. g. multilayer insulations (MLI), perlites, and vacuum are utilized for this purpose and have already proven themselves in similar applications. However, for the use of tanks for cryogenic fluids in the transport sector, there is insufficient knowledge regarding the course and consequences of incidents, which is due to the still short period of use and the few documented incidents, hence few investigations carried out in this field. Typical scenarios in the transport sector represent car accidents with collisions, fires, and their combination, which are associated with extraordinary loads on the tank.
The focus of this study is to investigate the behavior of TSI as a result of their thermal exposure to a heat source representing a fire. It is worth mentioning that this could lead to an increase of the heat flux into a tank by several orders of magnitude, and to permanent damage of the TSI, ultimately rapid release of flammable gas as well as a Boiling Liquide Expanding Vapour Explosion (BLEVE). For this purpose, a high temperature thermal vacuum chamber (HTTVC) has been developed that allows thermal loading of MLI or perlites in a vacuum and simultaneous measurement of heat flow through this TSI. The HTTVC is designed to represent realistic insulation conditions and to withstand thermal loads from typical design fires.
The HTTVC was applied to investigate TSI based on MLI and vacuum. It is shown that the thermal stress caused permanent damage to the TSI, with shrinkage, phase change, pyrolysis, and condensation being significant damage mechanisms. The results are relevant for the evaluation of accident scenarios and can thus contribute to the improvement of TSI and the development of emergency measures for the protection of persons and infrastructures.
The interest in hydrogen-based green energy is increasing worldwide, and the same is true for hydrogen-powered vehicles. Among the possible solutions to store hydrogen in such vehicles, cryogenic tanks equipped with multi-layer insulation (MLI) are the most promising to increase the amount of energy stored per unit volume. However, MLI is affected by severe deterioration when exposed to an external source of heat such as a fire following a car accident, leaving the tank unprotected and leading to failure in a relatively short time. In this work, a one-dimensional model to evaluate MLI thermal degradation when a liquid hydrogen tank is exposed to fire is presented. The relevance of taking MLI degradation into account when simulating the pressure increase due to external fire exposure is here demonstrated through the analysis of several case studies. The results show that MLI systems performance depletes within a few minutes of exposure to hydrocarbon poolfire.
The interest in hydrogen-based green energy is increasing worldwide, and the same is true for hydrogen-powered vehicles. Among the possible solutions to store hydrogen in such vehicles, cryogenic tanks equipped with multi-layer insulation (MLI) are the most promising to increase the amount of energy stored per unit volume. However, MLI is affected by severe deterioration when exposed to an external source of heat such as a fire following a car accident, leaving the tank unprotected and leading to failure in a relatively short time. In this work, a one-dimensional model to evaluate MLI thermal degradation when a liquid hydrogen tank is exposed to fire is presented. The relevance of taking MLI degradation into account when simulating the pressure increase due to external fire exposure is here demonstrated through the analysis of several case studies. The results show that MLI systems performance depletes within a few minutes of exposure to hydrocarbon poolfire.
Liquefied Hydrogen (LH2) or Liquefied Natural Gas (LNG) establish themselves as important energy carriers in the transport sector. Its storage requires tanks with Thermal Super Insulations (TSI) to keep the transported fluid cold. The presentation includes 2 main topics of the department.
First TSI has proven itself in various applications over a long time, but not in the land transport sector, where accidents involving collisions, fires, and their combination are to be expected. To analyze fire scenarios a High-Temperature Thermal Vacuum Chamber (HTTVC) was developed that allows the thermal loading of thermal insulation material in a vacuum and measuring the heat flow through the TSI in parallel. Within this chamber, 5 samples were tested regarding 3 different types of MLI, rock wool, and perlites. In the presentation, the results are presented.
Second, the studying of accident scenarios enables the improvement of thermal superinsulation and to find novel insulation concepts. This is necessary for LH2 large-scale storages, for which state-of-the-art solutions are not suitable. Within the presentation, a novel insulation concept will be presented.
An overview of test standards and regulations relevant to the fire testing of pressure vessels
(2021)
Fire exposure of storage and transportation vessels of hazardous materials (including pressure liquefied gases) can result in BLEVEs and other high-consequence incidents with large societal and economic impacts. To reduce risk most countries have numerous regulations, codes of practice and guidance notes covering the design, operation and maintenance of vessels and thermal protection systems. Yet despite such regulations there remains no internationally accepted fire test procedure for pressure vessel and accompanying thermal protection systems that is capable of meeting a range of regulatory requirements. This paper considers some of the regulations in place in the western world and considers the origin of these based on large and medium-scale testing conducted to date. It examines conditions found in these tests to propose a set of recommendations on which to base a standard method of test. These recommendations are proposed as being representative of a credible large pool fire scenario that may occur.
Liquefied propane gas (LPG) tanks in a fully engulfing accidental fire experience a fast increase in internal pressure. The result is often a Boiling Liquid Expanding Vapor Explosion (BLEVE) that can result in a large fireball and flying debris over a radius of more than 100 meters.
In the last 30 years BAM has carried out more than 30 real scale fire tests on propane storage vessels across three test sites. The primary research goal was to identify systems that can delay or prevent a BLEVE. Early studies started with water deluge systems, and have since moved on to consider alternative protection systems.
It has been shown that an unprotected vessel fails within 10 minutes or less. Tests with different oil and propane fueled fires have given an overview on possible real accidents involving full-engulfing scenarios. LPG tanks of various sizes (2.7 m³, 3.6 m³, 4.8 m³, 6.7 m³) were used with different filling levels. Numerous protection systems, ranging from active systems like water systems to passive thick- and thin-film layers. Also, the degree of thickness of these layers was variated. Pressure relief valves (PRV) have also been investigated, both alone and in combination with protection systems.
This paper gives an overview of the work performed by BAM in the field of BLEVE prevention of protecting system since the last 30 years. It has been shown that e.g. with a full applied coating degree on the tank with and without PRV can be reached an exposition in a test fire scenario a duration of more than 60min. For partly coated tanks with and without PRV the duration time is like an unprotected vessel. Furthermore, it could be shown that the active water system also protects with technically correct design.