2.1 Sicherheit von Energieträgern
Filtern
Dokumenttyp
- Vortrag (18)
- Zeitschriftenartikel (9)
- Beitrag zu einem Tagungsband (4)
- Posterpräsentation (3)
- Sonstiges (1)
Schlagworte
- Auswirkungsbetrachtungen (8)
- Behälterversagen (8)
- Elektrische Energiespeicher (8)
- Stationäre Energiespeicher (8)
- LPG (7)
- Lithium-ion battery (6)
- Auswirkungsbetrachtung (5)
- BAM TTS (5)
- EES (5)
- Alternative Antriebe (4)
Organisationseinheit der BAM
- 2 Prozess- und Anlagensicherheit (35)
- 2.1 Sicherheit von Energieträgern (35)
- 7 Bauwerkssicherheit (5)
- 7.5 Technische Eigenschaften von Polymerwerkstoffen (5)
- 3 Gefahrgutumschließungen; Energiespeicher (4)
- 3.0 Abteilungsleitung und andere (3)
- 8 Zerstörungsfreie Prüfung (3)
- 8.1 Sensorik, mess- und prüftechnische Verfahren (3)
- 2.2 Prozesssimulation (2)
- 3.1 Sicherheit von Gefahrgutverpackungen und Batterien (2)
Eingeladener Vortrag
- nein (18)
The number of cars which use a battery for propulsion, like BEV (battery electric vehicle) or PHEV (plug-in hybrid electric vehicle), is increasing. Following, the probability of these car types being involved in car accidents will increase. In a worst-case accident scenario, the installed batteries could go under thermal runaway (TR). A TR could be initiated by various causes, e.g., high temperatures from outside, mechanical damage of the cells/modules/batteries or internal and external short circuits. During such an event, large amounts of heat and toxic and/or flammable gases are released. This poses a great hazard to people and property in the immediate vicinity. The paper describes a large-scale test series on the lithium-ion battery TR consequences of automobile cells and modules up to E = 6.85 kWh. Near field temperatures of ΔT > 800°C in a distance of l = 2 m were measured. During an overcharge test, fragment throwing distances of l > 30 m were detected. Subsequent gas explosions of the released gases were documented. Hydrogen fluoride (HF) was measured in all tests, from cell to module. The highestmeasured concentration was cHF = 76 ppm, which is significantly higher than the 30-min-level for AEGL 2 (acute exposure guideline level 2). Based on the experimentally determined consequences, concrete measures for the accident analysis are subsequently drawn.
The number of cars which use a battery for propulsion, like BEV (battery electric vehicle) or PHEV (plug-in hybrid electric vehicle), is increasing. Following, the probability of these car types being involved in car accidents will increase. In a worst-case accident scenario, the installed batteries could go under thermal runaway (TR). A TR could be initiated by various causes, e.g., high temperatures from outside, mechanical damage of the cells/modules/batteries or internal and external short circuits. During such an event, large amounts of heat and toxic and/or flammable gases are released. This poses a great hazard to people and property in the immediate vicinity. The paper describes a large-scale test series on the lithium-ion battery TR consequences of automobile cells and modules up to E = 6.85 kWh. Near field temperatures of ΔT > 800°C in a distance of l = 2 m were measured. During an overcharge test, fragment throwing distances of l > 30 m were detected. Subsequent gas explosions of the released gases were documented. Hydrogen fluoride (HF) was measured in all tests, from cell to module. The highest measured concentration was cHF = 76 ppm, which is significantly higher than the 30-min-level for AEGL 2 (acute exposure guideline level 2). Based on the experimentally determined consequences, concrete measures for the accident analysis are subsequently drawn.
For a comprehensive safety assessment of stationary lithium-ion-battery applications, it is necessary to better understand the consequences of thermal runaway (TR). In this study, experimental tests comprising twelve TR experiments including four single-cell tests, two cell stack tests and six second-life module tests (2.65 kW h and 6.85 kW h) with an NMC-cathode under similar initial conditions were conducted. The temperature (direct at cells/modules and in near field), mass loss, cell/module voltage, and qualitative vent gas composition (Fourier transform infrared (FTIR) and diode laser spectroscopy (DLS) for HF) were measured. The results of the tests showed that the battery TR is accompanied by severe and in some cases violent chemical reactions. In most cases, TR was not accompanied by pregassing of the modules. Jet flames up to a length of 5 m and fragment throwing to distances to more than 30 m were detected. The TR of the tested modules was accompanied by significant mass loss of up to 82%. The maximum HF concentration measured was 76 ppm, whereby the measured HF concentrations in the module tests were not necessarily higher than that in the cell stack tests.
Subsequently, an explosion of the released vent gas occurred in one of the tests, resulting in the intensification of the negative consequences. According to the evaluation of the gas measurements with regard to toxicity base on the “Acute Exposure Guideline Levels” (AEGL), there is some concern with regards to CO, which may be equally as important to consider as the release of HF.
Composition and Explosibility of Gas Emissions from Lithium-Ion Batteries Undergoing Thermal Runaway
(2023)
Lithium-based batteries have the potential to undergo thermal runaway (TR), during which mixtures of gases are released. The purpose of this study was to assess the explosibility of the gaseous emission from LIBs of an NMC-based cathode during thermal runaway. In the current project, a series of pouch lithium-based battery cells was exposed to abuse conditions (thermal) to study the total amount of gases released and the composition of the gas mixture. First, the battery cells were placed in a closed vessel, and the pressure and temperature rise inside the vessel were measured. In a second step, the composition of gases was analysed using a Fourier transform Infrared (FTIR) spectrometer.
We found that the amount of released gases was up to 102 ± 4 L, with a clear dependence on the battery capacity. This study showed that the concentration of gaseous emissions such as carbon monoxide (CO), methane (CH4), ethylene (C2H4), ethane (C2H6), and hydrogen cyanide (HCN) increased with higher cell capacity. Of the five studied flammable gases, the maximum concentrations of carbon monoxide (16.85 vol%), methane (7.6 vol%), and ethylene (7.86 vol%) were identified to be within their explosible range. Applying Le Chatelier’s law, a calculated lower explosion limit (LEL) of 7% in volume fraction was obtained for the gas mixture. The upper explosion limit (UEL) of the gas mixture was also found to be 31% in volume. A filter comprising pyrobubbles was used for the removal of the studied gas components released during the thermal abuse. The investigation revealed that the pyrobubbles filter was highly effect in the removal of HCN (up to 94% removal) and CO2 (up to 100% removal). Herein, we report the dependency of the method of thermal runaway trigger on the measured maximum temperature.
Der Vortrag stellt den aktuellen Bearbeitungsstand des Teilvorhabens an der BAM dar. Der Schwerpunkt liegt dabei auf der ersten Versuchsserie mit Batteriezellen und -modulen bis zu 6.8 kWh. Darüber hinaus werden die weiteren geplanten Versuche vorgestellt sowie die Ergbnisverwertung aus dem Projekt aufgezeigt.
Every technical system has a failure rate, including a lithium-ion battery. To minimize the effects in the event of a thermal runaway, it is necessary to know what consequences to expect. In the talk, current results from tests on the thermal runaway behaviour of lithium-ion batteries will be presented and conclusions drawn for the handling of those.
Meta-analysis of heat release and smoke gas emission during thermal runaway of lithium-ion batteries
(2023)
Herein a meta-analysis of 76 experimental research papers from 2000 to 2021 is given about possible effects on the thermal runaway of lithium-ion battery cells. Data on the hazards of gas emissions and released heat are related to each other and differentiated by cell properties such as, cell geometry, cathode type or state of charge. Quantitative information on the total heat release in the range of 2.0–112.0 kJ Wh−1, the peak heat release rate in the range of 0.006–2.8 kW Wh−1and the smoke gas emission were extracted, normalized in terms of cell energy (Wh), combined in a data library and compared graphically. The total amount of gas emitted (3–48 mmol Wh−1) as well as the released amount of carbon monoxide (1–161 mg Wh−1) and hydrogen fluoride (2–197 mg Wh−1) were investigated as a function of the state of charge and cell geometry. The analysis reveals that the measured values are significantly influenced by the types of calorimeters and smoke gas analyzers used as well as by the type of thermal runaway trigger. This meta-analysis can serve as an important basis for any risk assessment of lithium-ion batteries.
Der Vortrag stellt den aktuellen Bearbeitungsstand des Teilvorhabens an der BAM dar. Der Schwerpunkt liegt dabei auf der ersten Versuchsserie mit Batteriezellen und -modulen bis zu 6.8 kWh. Aus diesen Versuche werden die wesentlichen Ergebnisse gezeigt, insbesondere die Teperatur-, Spannungs, Gas- und Gewichtsmessung beim thermischen Durchgehen.