Most fluorinated hydrocarbons that shall replace refrigerants with high GWP, like R134a, are flammable. For evaluating inertization measures for explosion protection, flammability of low-GWP refrigerants R1234yf, R32 and R1132a blended with carbon dioxide, nitrogen and argon were studied experimentally in a closed autoclave at atmospheric conditions. Furthermore, a calculation method was adapted to reduce the experimental costs for flammability studies on these gas mixtures. For igniting R1234yf in the closed autoclave a newly developed ignition system was used that allows generating electric arcs with high ignition energy. Gas mixtures containing the mildly flammable R1234yf and R32 could be inerted by adding much less inert gas than mixtures containing R1132a, which is more similar to unfluorinated hydrocarbons regarding the explosion regions. By using the adapted model of constant adiabatic flame temperature profiles estimating the explosion limits of fluorinated hydrocarbons was possible with similar accuracy as for unfluorinated hydrocarbons.
Keywords: Explosion Protection, Inertization, Flammability, HFOs, HFC., R1234yf, R32, R1132a
For evaluation of explosion scenarios in closed systems involving the mildly flammable refrigerants R1234yf, R1234ze and R32 dependent on the ignition energy, ignitions were carried out in a closed autoclave. A newly developed ignition system was used, which allows generating electric arcs with defined energies in a range between 3 J and 1000 J. The lower explosion limit of R32 decreases with increasing ignition energy. R32-explosions can be more severe than explosions involving highly flammable substances.
However, in case of R1234yf and R1234ze, the ignition energy had to be increased to more than 100 J and more than 500 J to detect explosions in the closed system at all, although flame Propagation phenomena can already be observed if these substances are ignited with much weaker ignition sources in open glass tubes. The explosions were very mild with these substances.