Filtern
Dokumenttyp
Sprache
- Englisch (19)
Referierte Publikation
- ja (19) (entfernen)
Schlagworte
- Emission test chamber (6)
- VOC (6)
- Thermal desorption (5)
- Gas chromatography (4)
- Reference material (4)
- Radon exhalation (3)
- VVOC (3)
- Volatile organic compounds (3)
- Air sampling (2)
- Building materials (2)
Organisationseinheit der BAM
Paper des Monats
- ja (2)
Emission testing of products is currently a rapidly increasing field of measurement activity. Labelling procedures for construction products are based on such emission test chamber measurements and hence measurement performance should be verified. A suited procedure for this purpose is the testing of one unique homogenous material in different laboratories within a Round Robin Test (RRT). Therefore, it is useful to have a reference material which can be used within inter-laboratory studies or as part of the quality management system to ensure comparable results. Several approaches on the development of reproducibly emitting materials have been published. These have in common only to emit a single VOC – toluene. Two further research studies carried out by BAM aimed to develop reference material for emissions testing containing one or more VOC in a single material. The first approach was a doped lacquer with Volatile and Semi-Volatile Organic Compounds (VOC/SVOC) and the second was Thermoplastic Polyurethane (TPU) or a Squalane/Paraffin mixture. Results received with the lacquer based material were presented in more detail.
In this work, we use a gas sensor system consisting of a commercially available gas sensor in temperature cycled operation. It is trained with an extensive gas profile for detection and quantification of hazardous volatile organic compounds (VOC) in the ppb range independent of a varying background of other, less harmful VOCs and inorganic interfering gases like humidity or hydrogen. This training was then validated using a different gas mixture generation apparatus at an independent lab providing analytical methods as reference. While the varying background impedes selective detection of benzene and naphthalene at the low concentrations supplied, both formaldehyde and total VOC can well be quantified, after calibration transfer, by models trained with data from one system and evaluated with data from the other system. The lowest achievable root mean squared errors of prediction were 49 ppb for formaldehyde (in a concentration range of 20–200 ppb) and 150 μg/m³ (in a concentration range of 25–450 μg/m³) for total VOC. The latter uncertainty improves to 13 μg/m³ with a more confined model range of 220–320 μg/m³. The data from the second lab indicate an interfering gas which cannot be detected analytically but strongly influences the sensor signal. This demonstrates the need to take into account all sensor relevant gases, like, e.g., hydrogen and carbon monoxide, in analytical reference measurements.
Determination of radon exhalation from construction materials using VOC emission test chambers
(2013)
The inhalation of 222Rn (radon) decay products is one of the most important reasons for lung cancer after smoking. Stony building materials are an important source of indoor radon. This article describes the determination of the exhalation rate of stony construction materials by the use of commercially available measuring devices in combination with VOC emission test chambers. Five materials – two types of clay brick, clinker brick, light-weight concrete brick, and honeycomb brick – generally used for wall constructions were used for the experiments. Their contribution to real room concentrations was estimated by applying room model parameters given in ISO 16000-9, RP 112, and AgBB. This knowledge can be relevant, if for instance indoor radon concentration is limited by law. The test set-up used here is well suited for application in test laboratories dealing with VOC emission testing.
The reliable measurement of very volatile organic compounds (VVOC) in indoor air by use of thermal desorption gas chromatography (TD-GC) in order to include them into evaluation schemes for building products even nowadays is a great challenge. For capturing these small molecules with carbon numbers ranging from C 1 –C 6 , strong adsorbents are needed. In the present study, recovery rates of nine suitable adsorbents of the groups of porous polymers, graphitised carbon blacks (GCB) and carbon molecular sieves (CMS) are tested against a complex test gas standard containing 29 VVOC. By consideration of the recovery and the relative humidity (50% RH), combinations of the GCB Carbograph 5TD, the two CMS Carboxen 1003 and Carbosieve SII as well as the porous polymer Tenax® GR were identified to be potentially suitable for sampling the majority of the VVOC out of the gas mix. The results reveal a better performance of the adsorbents in combination than being used alone, particularly under humid sampling conditions. The recovery rates of the chosen compounds on each adsorbent should be in the range of 80–120%.
Volatile organic compounds (VOCs) found indoors have the potential to affect human health. Typical sources include building materials, furnishings, cleaning agents, etc. To address this risk, chemical emission testing is used to assess the potential of different materials to pollute indoor air. One objective of the European Joint Research Project 'MACPoll' (Metrology for Chemical Pollutants in Air) aims at developing and testing a reference material for the quality control of the emission testing procedure. Furthermore, it would enable comparison of measurement results between test laboratories. The heterogeneity of the majority of materials makes it difficult to find a suitable reference sample.
In the present study, styrene, 2-ethyl-1-hexanol, N-methyl-α-pyrrolidone, lindane, n-hexadecane, 1,2-dimethyl- and 1,2-di-n-butyl-phthalate were added to 12 commercially available lacquers (6 alkyd and 6 acrylic polymer based lacquers) serving as carrier substrate. After homogenization, the mixtures were loaded into a Markes Micro-Chamber/Thermal Extractor (µ-CTE) for curing and investigation of the emission behavior for each compound. For almost all of the investigated chemicals, the preferred glossy acrylic lacquer showed emissions that were reproducible with a variation of less than 20% RSD. Such lacquer systems have therefore been shown to be good candidates for use as reference materials in inter-laboratory studies.
Development of a multi-VOC reference material for quality assurance in materials emission testing
(2015)
Emission test chamber measurement is necessary to proof building materials as sources of volatile organic compounds (VOCs). The results of such measurements are used to evaluate materials and label them according to their potential to emit harmful substances, polluting indoor air. If only labelled materials were installed indoors, this would improve indoor air quality and prevent negative impacts on human health. Because of the complex testing procedure, reference materials for the quality assurance are mandatory. Currently, there is a lack of such materials because most building products show a broad variation of emissions even within one batch. A previous study indicates lacquers, mixed with volatile organic pollutants, as reproducible emission source for a wide range of substances. In the present study, the curing of the lacquer-VOC mixture inside micro-chambers was optimised. Therefore, the humidity and the chamber flow were varied. Typical indoor air pollutants with a wide range of volatilities, for example, styrene, n-hexadecane, dimethyl and dibutyl phthalate were selected. It turned out that, under optimised curing parameters inside the micro-chamber, their emission can be reproduced with variations of less than 10 %. With this, a next important step towards a reference material for emission testing was achieved.
Emissions of building materials might have negative impact on human health and well-being. In the EU-funded research project H-House more than 30 natural materials (earthen dry boards and plasters, bio-based insulation materials made of wood, flax, reed, straw, etc.) used for renovation and refurbishment were tested regarding emissions of VOC, formaldehyde and radon. Different to ordinary emission tests on single materials this study focuses on the emissions from complete wall assemblies. Therefore, specially designed test chambers were used allowing the compounds to release only from the surface of the material facing indoors. The testing parameters were chosen in order to simulate model room conditions. The emission results were finally evaluated using the AgBB evaluation scheme, a procedure currently applied for the approval of flooring materials in Germany.
The ISO 16000-6 standard describes a method for the determination of volatile organic compounds (VOCs) in indoor and test chamber air by sorbent-based active sampling, thermal desorption and gas chromatography coupled with mass spectrometry (GC/MS). It also gives directions to adapt this methodology to very volatile organic compounds (VVOCs). Indeed, toxicologically based guideline values are being implemented for these compounds and it becomes necessary to measure them. But a comprehensive and robust measurement method is lacking. This work highlights the points that still need to be explored towards the standardisation of a suitable procedure: investigations on sorbent combinations, the suitability of chromatography columns and the use of gaseous standards are required. The biggest challenge remains in the fact that strong sorbents adsorb water together with VVOCs. Water may impair the analysis and the optimal approach to eliminate it is still to be found and integrated into the sampling strategy.
EN 16516 sets specifications for the determination of emissions into indoor air from construction products. Reliable, accurate and International System of Unit (SI)-traceable measurement results of the emissions are the key to consumer protection. Such measurement results can be obtained by using metrologically traceable reference materials. Gas-phase standards of volatile organic compounds (VOCs) in air can be prepared by a variety of dynamic methods according to the ISO 6145 series. However, these methods are not always applicable for semi-VOCs (SVOCs) due to their high boiling point and low vapour pressure. Therefore, a novel dynamic gas mixture generation system has been developed. With this system gas-phase standards with trace level VOCs and SVOCs in air can be prepared between 10 nmol mol−1 and 1000 nmol mol−1. The VOCs and SVOCs in this study have normal boiling points ranging from 146 °C to 343 °C. Metrologically traceable reference materials of the gas-phase standard were obtained by sampling of the VOC gas-phase standard into Tenax TA® sorbent material in SilcoNert® coated stainless steel tubes. Accurately known masses between 10 ng and 1000 ng per VOC were sampled. These reference materials were used to validate the dynamic system. Furthermore, the storage and stability periods of the VOCs in the reference materials were determined as these are crucial characteristics to obtain accurate and SI-traceable reference materials. In a round robin test (RRT), the reference materials were used with the aim of demonstrating the feasibility of providing SI-traceable standard reference values for SVOCs for interlaboratory comparison purposes. Based on the results from the validation, the storage and stability studies and the RRT, gas-phase standards and reference materials of VOCs and SVOCs with relative expanded uncertainties between 5% and 12% (k = 2) have been developed. These reference standards can be used as calibrants, reference materials or quality control materials for the analysis of VOC emissions.
Natural building materials for interior fitting and refurbishment - What about indoor emissions?
(2021)
Indoor air quality can be adversely affected by emissions from building materials, consequently having a negative impact on human health and well-being. In this study, more than 30 natural building materials (earth dry boards and plasters, bio-based insulation materials, and boards made of wood, flax, reed, straw, etc.) used for interior works were investigated as to their emissions of (semi-) volatile organic compounds ((S)VOC), formaldehyde, and radon. The study focused on the emissions from complete wall build-ups as they can be used for internal Partition walls and the internal insulation of external walls. Test chambers were designed, allowing the compounds to release only from the surface of the material facing indoors under testing Parameters that were chosen to simulate model room conditions. The emission test results were evaluated using the AgBB evaluation scheme, a procedure for the health-related evaluation of construction products and currently applied for the approval of specific groups of building materials in Germany.
Seventeen out of 19 sample build-ups tested in this study would have passed this scheme since they generally proved to be low-emitting and although the combined emissions of multiple materials were tested, 50% of the measurements could be terminated before half of the total testing time.