CCQM-K143 is a key comparison that assesses participants’ ability to prepare single element calibration solutions. Preparing calibration solutions properly is the cornerstone of establishing a traceability link to the International System of Units (SI), and therefore should be tested in order to confirm the validity of CCQM comparisons of more complex materials. CCQM-K143 consisted of participants each preparing a single copper calibration solution at 10 g/kg copper mass fraction and shipping 10 bottled aliquots of that solution to the coordinating laboratory, the National Institute of Standards and Technology (NIST). The masses and mass fraction for the prepared solutions were documented with the submitted samples.
The solutions prepared by all participants were measured at NIST by high performance inductively coupled plasma optical emission spectroscopy (HP-ICP-OES). The intensity measurements for copper were not mapped onto values of mass fraction via calibration. Instead, ratios were computed between the measurements for copper and simultaneous measurements for manganese, the internal standard, and all subsequent data reductions, including the computation of the KCRV and the degrees of equivalence, were based on these ratios. Other than for two participants whose measurement results appeared to suffer
from calculation or preparation errors, all unilateral degrees of equivalence showed that the measured values did not differ significantly from the KCRV. These results were confirmed by a second set of ICP-OES measurements performed by the Physikalisch-Technische Bundesanstalt (PTB). CCQM-K143 showed that participants are capable of preparing calibration solutions starting from high purity, assayed copper metal.
Similar steps are involved when preparing solutions for other elements, so it seems safe to infer that similar capabilities should prevail when preparing many different, single-element solutions.
Two test series were examined using nondestructive measuring methods by six independent laboratories before determining their compressive strength. The nondestructive test methods used were the rebound hammer and ultrasonic pulse velocity measurement. Two types of geometries were investigated: drilled cores and cubes. The measurement procedure for each of these datasets is conditioned to the geometry and is therefore different.
The first series consists of 20 drilled cores (approximately diameter/height = 10 cm/20 cm) from the 55-year-old Lahntal Viaduct near Limburg, Germany. After preparation in the first laboratory, the lateral surface of the drilled cores was tested with the rebound hammer using a given pattern. Every laboratory tested every drilled core at different locations.
Ultrasonic measurements in transmission were performed repeatedly at predefined points on the flat surfaces of the specimen.
The second series consisted of 25 newly manufactured concrete cubes of a mix with a target concrete strength class of C30/37. The edge length was 15 cm. Each laboratory received five specimens of this test series. Thus, contrary to the first series, each specimen was tested by only one laboratory. Two side faces of each cube were tested with the rebound hammer. In addition, ultrasonic measurements were performed by one laboratory. The time of flight was measured between the tested side faces of the rebound hammer at different positions.
For both series, rebound hammers were used to determine the R-value as well as the Q-value. The rebound hammer models within the laboratories were always the same, while they differed between the laboratories. The ultrasonic measurements took place with different measurement systems and couplants. Finally, both specimen series were tested destructively for compressive strength.
The dataset contains the raw data summarized in tabular form. In addition, relevant calculated data are included in some cases. For the ultrasonic measurements, the time of flight has already been converted into the ultrasonic velocity. Besides, in addition to the raw data of the compressive strength test (force, weight, and geometry values), the calculated compressive strengths and densities are also provided.
An experimental and numerical investigation of the effect of bisphenol A bis(diphenyl phosphate) (BDP) and polytetrafluoroethylene (PTFE) on the fire behaviour of bisphenol A polycarbonate/acrylonitrile butadiene styrene (PC/ABS) in the vertical UL 94 scenario is presented. Four PC/ABS blends were discussed, which satisfy different UL 94 classifications due to the competing effects of gasification, charring, flame inhibition and melt flow/dripping. For numerical investigation, the particle finite element method (PFEM) is used. Its capability to model the complex fire behaviour of polymers in the UL 94 is analysed. The materials' properties are characterised, in particular the additives impact on the dripping behaviour during thermal exposure. BDP is an efficient plasticiser; adding PTFE prevents dripping by causing a flow limit. PFEM simulations reproduce the dripping and burning behaviour, in particular the competition between gasification and dripping. The thermal impact of both the burner and the flame is approximated taking into account flame inhibition, charring and effective heat of combustion. PFEM is a promising numerical tool for the investigation of the fire behaviour of polymers, particularly when large deformations are involved. Not only the principal phenomena but also the different UL 94 classifications and the extinction times are well predicted.