Filtern
Erscheinungsjahr
Dokumenttyp
- Vortrag (26)
- Beitrag zu einem Tagungsband (25)
- Zeitschriftenartikel (13)
- Posterpräsentation (11)
- Beitrag zu einem Sammelband (2)
- Dissertation (1)
Schlagworte
- Pool fire (11)
- CFD simulation (9)
- CFD (7)
- Peroxy-fuels (7)
- Mass burning rate (6)
- Organic peroxides (6)
- TBPB (6)
- TBPEH (5)
- Overpressure (4)
- Safety distance (4)
Eingeladener Vortrag
- nein (26)
Experimental investigation and CFD simulation of organic peroxide pool fires (TBPB and TBPEH)
(2010)
Time averaged mass burning rate (m˙′′f ), flame length (H), temperature (T ), irradi- ance (E) and surface emissive power (SEP ) of TBPB (tert -butyl peroxybenzoate) and TBPEH (tert-butyl peroxy-2-ethylhexanoate) pool fires are measured for six pool di- ameters (d = 0.059 m, 0.107 m, 0.18 m, 0.5 m, 1 m and 3.4 m) at BAM in house and outside test facility. The measured heats of combustion (–Δhc) of TBPB and TBPEH are 30113 kJ/kg and 34455 kJ/kg and the specific heat capacities at constant pressure (cp) are 1.8 kJ/(kg K) and 2.1 kJ/(kg K) respectively. The measured m˙′′f of TBPB and TBPEH pool fires are in the range of 0.37 kg/(m2 s)≤ m˙ ′′ f ≤ 0.83 kg/(m2 s) and show little dependence on the pool diameter d, and are four to sixty times higher (for d = 1 m) than that of hydrocarbon pool fires. It is shown that the mass burning rates of the investigated organic peroxides can be represented as an exponential function of the self-accelerating decomposition temperature (SADT). Low SADT implies that the organic peroxide pool fires burn at a much higher m˙′′f than hydrocarbon pool fires. Fuel Froude numbers (Frf) of TBPB and TBPEH are 5 to 100 times (depending on d) higher than for hydrocarbon pool fires. Due to higher Frf the H of TBPB and TBPEH (measured with a S-VHS Videocamera) are found to be two times larger (d = 1 m) than corresponding pool fires of hydrocarbons. Heskestads flame length correlation predicts the Hd (d = 3.4 m) of TBPB and TBPEH pool fires much better than Thomas and Fay correlations. The measured time averaged flame temperatures T (d = 3.4 m) for TBPB and TBPEH pool fires are in the range of 1400 K ≤ T ≤ 1500 K and are 200 K to 300 K higher than for JP-4, kerosene and gasoline. The irradiances of the TBPB and TBPEH pool fires measured by radiometers are E (Δy/d = 0.3) = 45 kW/m2 and E = 98 kW/m2 which are two to ten times higher in comparison to the corresponding n-pentane, super gasoline and diesel pool fires. So the thermal safety distances for organic peroxide pool fires are larger by a factor four in comparison to the hydrocarbon pool fires. An infrared thermography system is used for the determination of SEP of TBPB and TBPEH pool fires. The values of surface emissive power for TBPB and TBPEH are SEP (d = 3.4 m) = 196 kW/m2 and SEP = 258 kW/m2 and thus the SEP are by a factor of approximately two higher than for hydrocarbon pool fires. A self-sustained pulsating Hd (’W’-Effect) is found in TBPB pool flames and is further analysed to explain the reason of occurance on the basis of chemical structure of the fuel and discontinuous heat flux back from flame to the liquid pool. CFD simulations of TBPB and TBPEH pool fires at d = 0.18 m, 0.5 m, 1 m, 3.4 m and 8 m are carried out using the Unsteady Reynolds Averaged Navier Stokes (URANS) equa- tions. The three-dimensional geometries have been discritized with unstructured hybrid grids, with the number of cells in the range of 1 million. Depending on the grid resolu- tion and the pool diameter time steps of 0.0001 s ≤ Δt ≤ 0.01 s for the CFD simulations are used. For solving the discritized equations a finite volume based implicit solver AN- SYS CFX has been used. For modelling the combustion, stoichiometric combustion for both peroxides are assumed. The temperature dependence of the reaction rate has been determined by the Arrhenius approach. For modelling the combustion eddy dissipation concept (EDC) model has been used. For turbulence buoyancy modified k- � and SAS (Scale Adaptive Simulation) turbulence models are used. For the thermal radiation and soot mass fraction discrete transfer radiation model and Magnusson soot model have been used. A new method is suggested for the prediction of mass burning rate (m˙′′f ) by CFD simula- tion. Both peroxide pool fires show approximately constant mass burning rate indepen- dent of d whereas m˙′′f of TBPEH are under predicted at the beginning but show relatively good agreement with measurements for large pool diameters (d = 1 m). In case of TBPB the CFD simulation over predicts the mass burning rate m˙′′f of small TBPB pool fires and shows a continuous decrease with d. CFD predicts the flame length H close to the measured data provided that the constants in Thomas equation are modified. The CFD predicted time averaged surface emission flame temperatures of TBPB and TBPEH pool fires (d = 3.4 m, 1437 K and 1542 K) are in good agreement with the measured time averaged flame temperatures. The CFD predicted SEP for TBPB and TBPEH pool fires (d = 3.4 m, 217 kW/m2 and 288 kW/m2) are also in agreement with the measured values. From the CFD predicted irradiance ECFD it is possible to determine the thermal safety distances from large pool fires of hydrocarbons and organic peroxides.
Data and prediction for the mass burning rate of a tert-butyl-peroxy-benzoat (TBPB) pool fire (pool diameter = 3 m) is presented. The mass burning rates of TBPB fires are up to six times higher and less dependent on pool diameter compared to hydrocarbon pool fires caused by an additional heat release rate due to exothermic decomposition reaction in the liquid phase. This heat release rate is calculated using a 1st order reaction kinetic obtained from micro calorimetric measurements. A new model is derived considering the heat release rate due to the decomposition reaction which is shown to be 100 % of the heat release rate radiated to the pool surface. With the presented model, including also physical quantities, especially the limiting fuel concentration for upward flame propagation, it is possible to predict the mass burning rates of large TBPB pool fires. The predicted values are in very good agreement with the experiments.
The diffusive burning characteristics of four peroxy-fuels (usually known as liquid organic peroxides) and one hydrocarbon fuel are experimentally investigated targeting alternative fuels (or as additives to conventional fuels) for the future. Measurements are performed in form of pool fires with pool diameters in the range between 1 cm and 1 m. Mass, momentum and energy transfer studies are carried out by measuring the mass burning rate, flame length, flame temperature and radiation heat transfer across the liquid fuel and gaseous flame. It has been shown that comparatively much less mass of peroxy-fuels and pressure drop (required to maintained the flow) of fuel are required to produce a given heat flux. The momentum delivered by the peroxy-fuel vapours are order of magnitude higher than for hydrocarbons making the visibility of flame to be 4–5 times larger. A heat balance analysis shows that the total heat release rate of a peroxy-fuel fire is contributed equally by convection and radiation. Finally, the three E's (Efficiency, Economy and Emission) are discussed in the context of present experimental results followed by some recommendations concerning safe handling of the proposed fuels.
Industrial fire and explosion hazards due to accidents in fuel storage units have gained a
considerable attention in the recent times. Both the regulatory bodies and scientific communities
are heavily concerned about the proper safety measures to avoid such calamities in future. This
paper aims to bring some essentials related to the hazards arose from the recent fuel storage fire
accident occurred in Buncefield, UK (2005), Puerto Rico, USA (2009) and Sitapura, India (2009).
The potential similarities behind occurrence of these accidents are studied. The applicability of
various methods (models) and also computer simulations to estimate the safety distances
according to the international standards for both explosion and fire hazard are verified. The
overpressures caused by the Vapor Cloud Explosion (VCE) and radiation flux emitted by the fire
are considered for respective explosion and fire hazard estimations. The prime focus is placed
on the regulations laid down by the National Fire Protection Agency of the United States and
the European Norms.
Data and predictions for the mass burning rates of di-tert-butyl peroxide (DTBP) pool fires (0.003 m < pool diameter < 3 m) are presented. The mass burning rates of DTBP fires are up to five times higher and are less dependent on pool diameter compared to hydrocarbon pool fires caused by an additional heat release rate due to exothermic decomposition reaction in the liquid phase. This heat release rate is calculated using a first-order reaction kinetic obtained from microcalorimetric measurements. A new model is derived considering the heat release rate due to the decomposition reaction, which is shown to be 40% of the heat release rate radiated to the pool surface. With the presented model, which also includes physical quantities, especially the limiting fuel concentration for upward flame propagation, it is possible to predict the mass burning rates of large DTBP pool fires. The predicted values are in very good agreement with the experiments.
Es werden Experimente zur Bestimmung der Massenabbrandraten von multiplen Poolfeuern präsentiert. Als Modellsubstanzen dienen n-Heptan und Di-tert-butylperoxid (DTBP). Es werden Versuche im Labormaßstab mit Durchmessern von d = 6 cm und relativen Abständen von 0.08 ≤ D/d ≤ 4 beschrieben und durch Feldversuche mit Pooldurchmessern d = 1.5 m und relativen Abständen zwischen den Pool von 0.17 ≤ D/d ≤ 1 ergänzt. Es kann gezeigt werden, dass die Massenabbrandraten multipler Feuer im Vergleich zu Einzelfeuern mit gleicher Brennstoffoberfläche bis zu einem Faktor 5.9 (n-Heptan) und 1.6 (DTBP) erhöht sind. Die Erhöhung ist abhängig vom relativen Abstand zwischen den Pools D, der Anzahl der Pools N und vom jeweiligen Brennstoff und zeigt ein lokales Maximum, welches mit dem Merging-Bereich der Flammenverschmelzung zusammenfällt. Die Massenabbrandrate als Funktion des relativen Abstandes zwischen den Pools kann durch eine Vergrößerung der Flammenbodenoberfläche infolge Flammenverschmelzung erklärt werden.
Present work deals with the potential usage of peroxy-fuels (usually known as organic peroxides) in engine combustion processes. Although as additives (in small quantities < 5% to conventional fuels e.g. diesel, gasoline) peroxy-fuels are well known for many years their commercial applications as a main or primary fuel are not investigated in detail as such except a few. Since they are thermally unstable and energetic their safety demands great care during processing which restricts their commercial exploitation. However, once the issues with safety are resolved they can be much more advantageously employed than conventional fuels. Some of these advantages are: significant amount of fuel saving, reduction in amount of inducted air or even in the complete absence of air i.e. anaerobically, smaller volume of combustion (chamber), oxygenated fuel quality and low emissions. In this study we introduce an idea to develop the components of an engine operating solely on peroxy-fuels. The engine concept is based on single and multiple injectors in a cylinder with special material coating to ensure a temperature controlled processing.
Limiting distances for flame merging of multiple n-heptane and di-tert-butyl peroxide pool fires
(2013)
Experiments to determine the limiting distances for flame merging of multiple pool fires are presented. As model substances n-heptane and di-tert-butyl peroxide are used. Laboratory scale tests with a Diameter d = 6 cm and relative distances between the pools of 0.08 ≤ D/d ≤ 4 are described and complemented with field experiments with a diameter d = 1.5 m and relative distances between the pools of 0.17 ≤ D/d ≤ 1.
Three regions for flame merging are observed and limiting distances are determined. A merging Region with the limiting distance Dmerg/d within which all flames merge together over the complete burning time. A transition region with the limiting distance Dtran/d within which some flames merge together while other flames are separated from each other. A separated region within which all flames are completely separated from each other. A correlation against the number of burning pools is presented to predict the limiting distances Dmerg/d und Dtran/d.
Most of the measurements of temperatures in large pool fires are indirect and present a number of complexities due to the interactions of convection, radiation and soot blockage. In the present work these influences for two organic peroxide [tert-butyl peroxybenzoate (TBPB) and tert-butyl peroxy-2-ethylhexanoate (TBPEH)] pool fires are analysed.
Thermocouple measured temperature in the clear flame zone i.e. combustion zone are found to be 250-400 K lower than from the thermographic measurements. The convective and radiative heat flux contributions from the fire on temperature measurements are discussed. CFD (Computational Fluid Dynamics) simulations have been performed for large pool fires and the predicted time averaged flame temperatures were found to be in qualitative agreement with
measurements due to the stoichiometric combustion model used in the present simulations.
The use of energetic materials as a main fuel in high temperature process
industries are not known to the scientific community as such. This paper
highlights some of the features and advantages of using organic peroxides
especially di-tert-butyl peroxide (DTBP) in high temperature process industries.
The feasibility of using DTBP as a main or supporting fuel in process industries
have also been justified with the help of Computational Fluid Dynamics (CFD)
simulations. For peroxides requirement of less fuel and air for the same amount
of heat flux has been shown. The resulted emission from the combustion of
DTBP is also discussed.
Combustion of peroxy-fuels
(2011)
The diffusion flames of organic peroxides exhibit quite different characteristics than hydrocarbons. What makes them interesting to study is their fast burning behaviour. As a result the flame temperature enhances and so does the thermal radiation. Due to all these they demand safe handling during processing. However, they can be utilised at several places in different industries where a fuel with fast burning, high temperature and intense radiation are desired. Some of the possibilities to use them as a main or supporting fuel in a wide range of industrial utilities are the major content of this paper.
A new burner concept (PEROXY-BAM®) for the combustion of liquid organic peroxides (Peroxy-fuels) is presented. As peroxy-fuels are thermally unstable the design of burners for them should be accordingly modified ensuring a safe operation. It is found that 10 to 100 time less amounts of peroxy fuels are required for the same heat flux or output in comparison to hydrocarbons. Correspondingly, the fuel pump power and the volume of combustion chamber (furnace) are also reduced. As a result of less amount of fuel the emissions will also be stepped down and oxygen in the molecule helps to establish conditons like in an oxy-fuel combustion process. The advantages of using peroxy-fuels over hydrocarbons inside a model combustion chamber are also investigated with the help of CFD (Computational Fluid Dynamics) simulations.
new burner concept for peroxy-fuels is proposed. The performance of the proposed peroxy-fuel burner is predicted with the help of Computational Fluid Dynamics (CFD) simulation. It is found that peroxy-fuel burner not only requires considerable less amount of fuel for the same output/power but also at the same time the overall size of the processing unit can be reduced. As peroxy-fuels contain oxygen atoms within the molecule itself a similar to oxy-fuel combustion environment is created without even supplying pure oxygen. CFD simulations also support the above facts and demonstrate the existence of less favorable conditions to form NOx.
The mass burning rate of pool fires of organic peroxides do not vary appreciably with the pool size as have been observed for the hydrocarbons. Instead the decomposition temperature largely controls the same. The dependence of mass burning rate on the decomposition temperatures namely self-accelerating decomposition temperature (SADT) and extrapolated onset temperature measured by differential scanning calorimetry (DSC) for organic peroxide pool fires are identified and correlations are developed.
Industrial fire and explosion hazards due to accidents in fuel storage units have gained a considerable attention in recent years. Both, the regulatory bodies and scientific communities are heavily concerned about the proper safety measures to avoid such calamities in the future. This paper aims to bring some essentials related to the hazards that arose from recent fuel storage fire accidents occurring in Buncefield, UK (2005), Puerto Rico, USA (2009) and Sitapura, India (2009). The potential similarities behind occurrence of these accidents are studied. The applicability of various methods (models) and also computer simulations to estimate the safety distances according to the international standards for both explosion and fire hazard are verified. The overpressures caused by the Vapor Cloud Explosions (VCE) and radiation fluxes emitted by the fires are considered for respective explosion and fire hazard estimations. The prime focus is placed on the regulations laid down by the National Fire Protection Agency of the United States and the European Norms.
An extraordinary deviceless self-sustained oscillatory diffusive burning is observed in tert-butyl peroxybenzoate (TBPB) (technical pure) and hybrid fuel, i.e., TBPB and kerosene (both 50%) flames when burned in form of pool fires. Such oscillations or more precisely self-sustained deviceless control of mass burning (flow) is not reported till date. Generally, devices comprising electronic control system and/or mechanical means (valves) are necessary to produce such oscillatory burning or control of fuel flow. This unique oscillation is strongly recorded for pool diameters of 6 cm ≤ d ≤ 11 cm beyond which the effect was weakened and unseen (hid) visually. The fuel regression (loss) takes place in irregular time steps and is formulated in form of a step function. The variation in fuel mass burning rates, visible flame lengths and radiation heat fluxes with time are measured as respective representatives of oscillations. The periodicity in the strongest oscillations in relative visible flame lengths is investigated and the measured data are found to be best fitted in sinusoidal form. Both, chemical and thermal effects are shown to be possibly responsible for such effects. Furthermore, a theory is offered to characterise similar effect showing fuels.
The flame temperatures T of a multiple n-heptane pool fire d = 6 cm, N = 5, D/d = 0.33 are measured with type S thermocouples and predicted with Large Eddy Simulation (LES) and an assumed pdf-approach containing a detailed kinetic with 112 species and 800 elementary reactions. Multiple pool fires show higher flame temperatures up to ≈ 200 K in comparison to single pool fires. CFD simulation is in good agreement with the experimental results and a validation is performed. It can be shown that multiple fires have an enhanced air-entrainment leading to an increased formation of OH radicals and consequently to the observed higher flame temperatures.
In verfahrenstechnischen Anlagen kann es während des Umgangs, des Transports und der Lagerung durch Freisetzung und anschliesender Zündung von brennbaren Flüssigkeiten zu Lachen-, Pool- oder Tankfeuern kommen. Die sich ausbildenden Feuer konnen große Schäden an benachbarten verfahrenstechnischen Anlagen und Personen verursachen. Im Unterschied zu Einzelfeuern sind multiple Pool- und Tankfeuer aufgrund ihrer Wechselwirkungseffekte sicherheitstechnisch von besonderer Bedeutung. Mit Di-tert-butyl-peroxid (DTBP) und n-Heptan als Leitsubstanzen werden Labor- und Feldexperimente (d ≤ 1.5 m) mit wechselwirkenden Poolflammen (N ≤ 9) in einer Matrixanordnung bei relativen horizontalen Abständen D/d zwischen den Pools im Bereich 0.16 ≤ D/d ≤ 4 durchgeführt.
Die Phänomene der Flammenverschmelzung (Flammenfusion) in Abhängigkeit vom Poolabstand D/d werden experimentell untersucht und modelliert.
Prediction of burning rate of an accidentally released flammable fuel by means of CFD simulation
(2009)
Prediction of burning rate of an accidentally released flammable fuel by means of CFD simulation
(2009)
Massenabbrandraten organischer Peroxide unter besonderer Berücksichtigung der thermischen Stabilität
(2013)
Die Flüssigkeitstemperatur Temperatur in der flüssigen Phase unmittelbar im Grenzbereich zur Gasphase während eines Abbrandes organischer Peroxide überschreitet die Onset-Temperatur der beginnenden exothermen Zersetzungsreaktion des Peroxids, so dass diese zu berücksichtigen ist. Für die Peroxide Di-tert-butyl-Peroxid (DTBP) und tert-butyl-peroxybenzoat (TBPB) muss daher bei der Berechnung des Wärmerückstromes ein zusätzlicher Term für die Zersetzung in der Flüssigkeit additiv ergänzt werden. Der Umsatz der Zersetzungsreaktion wird unter den Bedingungen eines CSTR modelliert und erfolgt auf Basis einer Reaktionskinetik 1. Ordnung. Es kann gezeigt werden, dass der Wärmestrom in einem DTBP-Poolfeuer ≈ 40 % und einem TBPB-Poolfeuer ≈ 100 % des Wärmerückstromes durch Wärmestrahlung entspricht. Durch Q-Punkt-d können die vergleichsweise hohen Massenabbrandraten und die relative Unabhängigkeit der Massenabbrandraten vom Pooldurchmesser erklärt werden. Über eine Energiebilanz wird ein Modell basierend auf physikalischen Parametern entwickelt, das die Massenabbrandraten großer Poolfeuer, in sehr guter Übereinstimmung mit den experimentellen Ergebnissen, vorhersagt.
Amuay refinery disaster (2012) is another recent example of Vapor Cloud Explosion (VCE) and fire accidents preceded by Buncefield (2005), Puerto-Rico (2009) and Jaipur (2009), respectively [9]. The incident has left many safety issues behind which must be repeatedly addressed. Unfortunately, the lessons taught by previous similar events are just not understood carefully. It reveals that the proper safety measures for such facilities were either underestimated or were not accounted seriously. Consequently, the resulting overpressures from explosion and the subsequent thermal radiation from tank fires have once again proved to be disastrous to both mankind and infrastructure. This article highlights the aftermaths of Amuay incident and addresses the challenges put forward by it. Furthermore, a comparative study is performed between such incidents to analyze the similarities and how they could have been avoided.
Two-phase CFD (Computational Fluid Dynamics) model for characterising the spill-over/dispersion of peroxy-fuels is presented. The model is independent of type and burning rate of the spilled/dispersed fuel and considers only overflow Reynolds number (Re) to characterise the spill/dispersion behaviour. Additional simulations are performed for LNG (Liquified Natural Gas) dispersion and it is found that the model can be used for different fuels within a defined range of Re. Different scenarios with Re = 100 to 3 × 105 are investigated covering a wide range of mass flow rates, opening sizes and viscosities. Depending on Lower Flammability Limits (LFL) of the fuels spill/dispersion (vapour cloud) diameters (DCFD) and heights (hCFD) are predicted. A generalised correlation between DCFD and Re is established to predict the dispersion occurring at varying scales. The model is validated by: (1) conducting an extensive grid independent study; (2) comparing the results with the existing analytical methods and (3) comparing against the standard field test data on LNG dispersions.
Industrial fire and explosion hazards are most often also associated with the dispersion of toxic substances.
These substances can be gases, liquids, solids or in form of aerosols. The critical toxic exposure limits to People and enviroment from such substances are regulated by the concerned authorities of the countries. In order to comply with the defined regulation estimation of such critical limits must be carried out by different semi-empirical and phenomenological models/methods for risk assessment.
Many of such methods provide a qualitative estimation of time and space dependent extrimities of toxicity. The overwhelm development of computational capacity has made it possible to perform Computational Fluid Dynamics (CFD) simulation by solving the three-dimensional transport equations for mass momentum and species in lower and upper atmosphere, respectively. CFD simulation not only provides a detailed 3D distribution of toxic particulates/gases in the neighbourhood of the plant but also helps to study the worst-case sceanrios. In the past several small- and large-scale accidents occured in oil and gas plants in different parts of the world including the recent one in Rheinland refinery near Cologne in Germany. This work deals with this accident and provides a methodology to predict the critical exposure limits of smoke emitted by a toluene tank fire by means of CFD simulation.
Organic peroxides are energetic substances liable to decompose due to exothermic reactions when exposed to uncontrolled temperature, contamination, confinement and quantity. Their safe storage and transportation are the prime concern and chemical industries and regulating authorities. Their accidental release may and most often lead to shape of a pool. In present study, safety distances from such large pool fires (diameter d = 3.4 m) of organic peroxides are numerically predicted by solving the reactive, 3-D time dependent Navier-Stokes equations with reliable assumptions. The present model is validated against the data on buoyant turbulent diffusion flames. The safety distances predicted by simulation assume three regions in a fully developed fire i.e. hot spot, luminous zone and a flame surface. The time averaged data of temperatures of these regions lead to better estimation of irradiances against the measured data. A developed sphere analogy method (for a special class of organic peroxides) for maximum surface emissive power prediction is also verified.
The industrial fire accidents e.g. Buncefield (2005) and Jaipur (2009) have come up with several issues concerning safe storage and transportation of flammable liquids. The pre and post fire consequences are therefore important to be analyzed prior to the handling of flammable fuels. Pool or/and tank fire is the most often seen scenario after the leak/spill of liquid fuel. An overview of the typical scenarios from large hydrocarbon and organic peroxide pool fires and their respective safety distances for the people and the infrastructure are the important subjects of this paper.
Combustion of peroxy-fuels
(2011)
Die thermische Zersetzung von AIBN wurde in einem Projekt mit mehreren Teilnehmern untersucht. Hierbei wurde die selbstbeschleunigende Zersetzungstemperatur SADT) sowohl experimentell als auf Grundlage von Simulationsrechnungen bestimmt. Die Besonderheit bei dem Feststoff AIBN ist, dass die Zersetzung sowohl in der festen, als auch in der flüssigen Phase nach dem Schmelzen stattfindet, was bei den durchgeführten Simulationsrechnungen berücksichtigt werden musste. Die berechneten SADT Werte stimmen mit den experimentell bestimmten sehr gut überein.
Das Abbrandverhalten und die thermische Strahlung von Poolfeuern organischer Peroxide (OP) wurden bereits in der Vergangenheit ausführlich untersucht. Dabei ergaben sich zum Teil erhebliche Unterschiede hinsichtlich der Abbrandraten, Temperaturen, Strahlungsintensitäten und Flammenlängen im Vergleich zu flüssigen Kohlenwasserstoffen. Das größere Gefahrenpotenzial von OP führt zu strikteren Sicherheitsbestimmungen für Lagerung und Transport. Da das Gefahrenpotenzial maßgeblich von den tatsächlich auftretenden Szenarien abhängt, ist eine Bewertung solcher Ereignisse unumgänglich um nachhaltig die Gesundheit von Mensch und Umgebung zu sichern. Ein Metallfass, gefüllt mit 200 Litern DTBP (Di-tertiär-butylperoxid), wurde auf dem Testgelände Technische Sicherheit der BAM einem Außenfeuer ausgesetzt. Durch den starken Wärmeeintrag erhöht sich die Massenabbrandrate des Peroxids um ein Vielfaches und das Fass entleert sich schließlich unter Ausbildung mehrerer Feuerbälle. Die Flammengröße, Flammentemperatur und damit die thermische Strahlung überschreiten die der gewöhnlichen OP-Poolfeuer. Die resultierenden höheren Sicherheitsabstände sind abschließend berechnet.
Fire and explosion hazards associated with storage and transportation of flammable materials have been a matter of great interest in the recent times. BLEVE is a scenario that occurs when a closed fuel container is subjected to heat for a longer duration. Such events are disastrous to human beings and assets both. In the past there have been numerous studies on BLEVEs and fireballs of hydrocarbon fuels, e.g. kerosene, gasoline, LPG, LNG and others. Though, the fireballs of peroxy-fuels are not looked into detail as such. This article tries to overcome this lack of knowledge. Both, experimental investigation and CFD simulations are performed to measure and predict the fireball characteristics of a peroxy-fuel. Due to thermal decomposition in the liquid phase and active oxygen content a peroxy-fuel fireball burns at a very fast rate and emit higher thermal radiation whereas exhibits smaller diameter and elevation compared to hydrocarbons. That eventually leads to consideration of larger safety distances from them which are also verified by CFD results.
Scenarios of underground gas pipeline failure, crater formation, dispersion of gas, explosion and subsequent fires are investigated with semi-empirical and with CFD (Computational Fluid Dynamics) modelling. In order to strengthen the accident based learning approaches present investigations are performed in the context of recent GAIL (Gas Authority of India Limited) natural gas pipeline incident occurred in India. The foreseeability of damages to lives of people and assets due to explosion overpressure and thermal radiation are assessed. The released gas is considered as slightly dense-than-air i.e. 1.5 times. Depending on the LFL (Lower Flammability Limit) of gas the dispersion diameter and heights are predicted which followed the visual evidences appropriately. The model was furthermore tested with an even denser medium and was found to be worked well there too. The estimated explosion overpressures with the standard methods and also with CFD reproduced the scenario nicely. The effects of congestion VBR (Volume Blockage Ratio) in form of vegetation on stable atmospheric boundary layer flow is analysed and its contribution towards turbulence and hazard enhancement is studied.
It is found that the major source of fatalities was higher thermal radiation emitted by pool fires of methane. The estimated thermal safety distances clearly demonstrate the ignorance/under estimation of likelihood and consequence of such hazardous events. For such incidents CFD demonstrated a strong capability to assess the pre or/and post events foreseeabilities within a reasonable amount of time and with an acceptable level of accuracy meeting the industrial needs for risk analysis.
CFD (Computational Fluid Dynamics) simulations have been carried out to investigate the behavior of turbulent, subsonic jet fires of the peroxy-fuel Di-tert-butyl peroxide (DTBP) using the SAS-SST turbulence model, the discrete transfer radiation model, the eddy dissipation combustion model and the Magnussen soot model. Safety relevant parameters, such as flame length, temperature and thermal radiation are predicted to give recommendations on safety distances.
A volumetric source based CFD (Computational Fluid Dynamics) model for estimating the wind and gravity driven spread of an elevated released dense hazardous cloud on a flat terrain without and with obstacles is demonstrated. The model considers the development of a worst-case scenario similar to that occurred at Bhopal. Fully developed clouds of a dense gas having different densities, under ABL (Atmospheric Boundary Layer) with calm ground wind conditions are first obtained. These clouds are then allowed to spread under ABL with different ground wind speeds and gravity conditions. The developed model is validated by performing the grid independent study, the fluid dynamical evidences, post-disaster facts, the downwind MIC (Methyl Isocynate) concentrations estimated by earlier models and experiments on dense plume trajectories. It is shown that in case of an active dispersion under calm wind conditions the lateral spread would prevail over the downwind spread. The presence of a dense medium behaves like a weak porous media and initiates turbulence at much smaller downwind distances than that normally would occur without the dense medium. The safety distances from toxic exposures of MIC are predicted by specifying an isosurface of a minimum concentration above the ground surface. Discrepancies in near-field predictions still exist. However, the far-field predictions agree well with data published before.
Dampening of energetic properties and the effects of blending proportions of isododecane on the diffusive burning behaviour of peroxy-fuels are experimentally studied. Blended peorxy-fuels are obtained by adding isododecane in the proportions of 25 wt.%, 50 wt.% and 75 wt.%, respectively, in technical pure peroxy-fuels. The fuels were burned in form of pool fires with diameters 0.02 m ≤ d ≤ 1 m. The mass burning rates and relative flame lengths are found to be weakened with increasing diluent proportions. By measuring the mass burning rates and visible flame lengths of pool fires of different samples of fuel blends an optimum blending criterion is developed. Furthermore, it is shown that the dilution proportions and flame characteristics can be correlated by empirical equations.