Steel tension rod systems consist of tension rods, fork connectors and associated intersection or connecting plates. They are used for truss systems, bracings or suspensions owing to slender design and increased economic efficiency. In case of fire, beside the tension rods themselves, the connection parts require appropriate fire protection. The use of intumescent fire protection coatings prevents a rapid heating of the steel and helps to ensure the load-carrying capacity of the structures. Because the connection components of the tension rod systems feature surface curvature as well as a complex geometry, high demand is placed on the intumescence and thermal protection effectiveness of the reactive fire protection coatings. Experimental studies were carried out to investigate the performance of intumescent coatings applied to the components of tension rod systems. The examined aspects include the foaming and cracking behaviour of the intumescent coatings, the influence of different dry film thicknesses (DFT), the heating rate of the steel connecting parts in comparison to the tension rods, as well as the mounting orientation of the tension rods together with their associated fork connectors. The results show that a decrease in the surface curvature and/or an increase in the mass concentration of the steel components lead to a lower heating rate of the steel. Moreover, the performance of the intumescent coating on tension rod systems is influenced by the mounting orientation of the steel components.
Purpose – The purpose of this paper is to investigate the performance of intumescent coating on tension rod systems and their components. Steel tension rod systems consist of tension rods, fork end connectors and associated intersection or gusset plates. In case of fire, beside the tension rods themselves, the connection parts require appropriate fire protection. Intumescent fire protection coatings prevent a rapid heating of the steel and help secure the structural load-carrying capacity. Because the connection components of tension rod systems feature surface curvature and a complex geometry, high demand is placed on the intumescence and thermal protection performance of the coatings.
Design/methodology/approach – In this paper, experimental studies were carried out for steel tension rod systems with intumescent coating. The examined aspects include the foaming and cracking behaviour, the influence of different dry film thicknesses, the heating rate of the steel connecting parts in comparison to the tension rods, and the mounting orientation of the tension rods together with their fork end connectors.
Findings – The results show that a decrease in surface curvature and/or an increase inmass concentration of the steel components leads to a lower heating rate of the steel. Moreover, the performance of the intumescent coating on tension rod systems is influenced by themounting orientation of the steel components.
Originality/value – The findings based on fire tests contribute to a better understanding of the intumescent coating performance on connection components of tension rod systems. This subject has not been extensively studied yet.
The application of intumescent coatings for fire protection of steel constructions is increasing.
Thanks to the relative thin thickness of the coatings, the typical visual appearance of the
structures can be preserved. In Germany, the applicability of the systems is regulated by the
national as well as European technical approvals. According to the approvals, the application
on steel members in tension is only allowed with limitations. Especially, the application on
solid steel rods in tension is currently not covered. The paper will explain the actual state of
the art of the application of reactive fire protection systems applied to steel structures.
Physical and technical background information will be provided. After that, the latest
scientific results of an on-going research project funded by the German National Institute of
Building Technology (DIBt) and conducted by the Federal Institute for Materials Research
and Testing (BAM) will be described.
Intumescent fire protection coatings are used to improve the fire resistance of steel members. Due to slender cross-sections typically used for tension members, high demands are placed on the effectiveness and reliability of the intumescent coatings. This paper describes real-scale fire tests of intumescent coatings applied to steel tension members with circular solid and hollow sections. First, the current regulations for the application of intumescent coatings on steel tension members are discussed. After that, a comparison between the foaming behaviour and failure mechanisms of intumescent coatings applied to steel tension members with different cross-sections and loading conditions is given. Next, the experimental setup and procedure of the performed fire tests are presented. In addition, the influences of various parameters on the performance of the intumescent coating are analysed, including the geometry of the steel profile, dry film thickness of the intumescent coating, load utilisation level as well as the orientation of the member. Based on the theoretical considerations and results of the fire tests, it is evidenced that mechanically loaded fire tests are essential to assess accurately the contribution of intumescent fire protection coatings to the fire resistance of steel tension members with circular solid sections.
Intumescent coatings are commonly used in civil engineering to improve the fire resistance of steel constructions. Especially in the case of tension bars, where mostly circular or rectangular solid sections are used, intumescent coatings offer an efficient measure to improve the fire resistance taking advantage of profile-following application and low coating thickness requirements. Thus, the architectural appearance of slender profiles can be preserved. The paper describes real-scale mechanically loaded and unloaded fire tests of circular and rectangular solid steel tension bars with intumescent coating. The aim of these tests is to investigate the influence of the different profile types as well as different bar orientations on the performance of intumescent coatings. The results are used to specify a normative test and assessment procedure to be implemented in a new European standard for determining the contribution of intumescent coatings to the fire resistance of circular or rectangular bars used as tension members.
Intumescent coatings are used in civil engineering to improve the fire resistance of steel constructions. Due to the thin coating thickness and the profile-following application, the architectural appearance of the steel structure can be preserved. EN 13381-8 provides regulations to determine the contribution to the fire resistance of intumescent coatings applied to steel beams and columns. The scope of this standard excludes tension members and steel members with solid sections. For products that have already been successfully tested and assessed on beams and columns, EN 13381-10 offers the possibility based on unloaded fire tests to extend the scope of application of intumescent coatings to tension bars with solid sections. This approach contradicts the national safety level in Germany, where mechanically loaded testing is mandatory. Therefore, a new part of the test standard series EN 13381 is currently developed to enable the application of intumescent coatings on steel tension bars with solid section based on mechanically loaded fire tests. BAM has already carried out numerous fire tests on loaded steel tension members with intumescent coatings. Currently, in the BAM research project FIRESTEMIC, the influence of the steel bar orientation and the profile type on the thermal performance of intumescent coatings are investigated. Both questions concerning the thermal protection ability of intumescent coatings were analysed based on three different test sets, which were carried out in the tension furnace (Fig. 1a). The fire exposure corresponds to the standard temperature-time curve according to EN 1363-1.
This paper summarises the main findings from the fire tests conducted in the FIRESTEMIC project. The results serve as an experimental background for the proposal of the new standard. Regarding the bar orientation, a new test setup was developed and proposed for the new standard. The two tested commercial water-based intumescent coatings with applied dry film thickness from 1.5 mm to 2.5 mm showed only a slight dependence on the bar orientation. In terms of the steel profile type, circular and rectangular solid sections with identical section factor and applied dry film thickness were tested. It was observed that the circular solid bars with diameter 30 mm heat up faster compared to the solid rectangular bars with dimension 30×30 mm (Fig. 1b). Also at larger steel bars, i.e. diameter 40 mm and dimension 40×40 mm, the same trend occurred. Thus, it is recommended for the new test standard to allow a transfer of the test results from circular to rectangular solid sections. In addition, the paper will describe and explain the test and assessment procedure proposed for the newly developed standard.
In civil engineering, steel tension members are normally used for bracings, suspensions and underbracing systems. Typically, slim circular solid sections (CSS) are used for such tension members. However, sufficient knowledge about the performance of reactive fire protection systems (RFPS) applied to solid steel tension members has so far been missing. The application of RFPS on such members was not covered by national German approvals (abZ) as well as European technical assessments (ETA) and therefore only possible by approvals in individual case by the building authority. This paper describes the world’s first scientifically investigated fire tests of RFPS applied to steel tension members with CSS. The influence of various parameters such as profile geometry, dry film thickness of the RFPS, level of the load utilization as well as member orientation was tested. In addition, the foaming and cracking behaviour and thermal protection of the RFPS used are investigated and failure mechanisms are identified. To measure the steel temperature of the tension member without weakening the cross-section a special method for the application of thermocouples was developed. The fire tests show that an application of RFPS on steel tension members with solid section is generally possible. However, due to the slim cross-sections and the missing possibility of load distribution within the tension member, high requirements are placed particularly on the effectiveness and reliability of the RFPS. In particular, the testing of mechanically loaded tension members is essential, since the necessary three-dimensional foaming results in the highest stress level for the RFPS. The findings obtained from the performed fire tests are of general nature. Recommendations for the testing and assessment of RFPS applied to steel tension members with solid section are briefly described in this paper and explained in detail in [1] and [2]. Based on this research, the German building authority (DIBt) has defined national approval guidelines for the testing and the assessment of RFPS applied to tension members with solid section. Since November 2015, a general building approval for a RFPS is available in Germany.
The application of intumescent coatings for fire protection of steel constructions is
increasing. Thanks to the relative thin thickness of the coatings, the typical visual
appearance of the structures can remain essentially unchanged. In Germany, the
applicability of the systems is regulated by the national as well as European technical
assessments. According to the approvals, the application on steel members in tension is
only allowed with limitations. Especially, the application on solid steel rods in tension is
currently excluded from the approval. The paper explains the actual state of the art of the
application of reactive fire protection systems applied to steel structures. Physical and
technical background information are provided. Furthermore, the latest scientific results
of an on-going research project funded by the German National Institute of Building
Technology (DIBt) and conducted by the Federal Institute for Materials Research and
Testing (BAM) will be described.