How can the risk of a BLEVE be reduced? That is the main question based on different research projects. In various large scale fire tests fire protection coating systems were used of different manufacturers. The degree of the coating as well as the layer thickness and the processing were varied. These experimental configurations were partly tested with and without pressure relief valve. The pressure relief valves were not protected again the thermal Load from the test fire. The ambition is to find a minimum of the thickness from the fire protection coating witch delay a BLEVE up to 90 minutes. Here are given the most interested configurations of tanks in fire and a description of the test-rigs.
Liquefied propane gas (LPG) tanks in a fully engulfing accidental fire experience a fast increase in internal pressure. The result is often a Boiling Liquid Expanding Vapor Explosion (BLEVE) that can result in a large fireball and flying debris over a radius of more than 100 meters.
In the last 30 years BAM has carried out more than 30 real scale fire tests on propane storage vessels across three test sites. The primary research goal was to identify systems that can delay or prevent a BLEVE. Early studies started with water deluge systems, and have since moved on to consider alternative protection systems.
It has been shown that an unprotected vessel fails within 10 minutes or less. Tests with different oil and propane fueled fires have given an overview on possible real accidents involving full-engulfing scenarios. LPG tanks of various sizes (2.7 m³, 3.6 m³, 4.8 m³, 6.7 m³) were used with different filling levels. Numerous protection systems, ranging from active systems like water systems to passive thick- and thin-film layers. Also, the degree of thickness of these layers was variated. Pressure relief valves (PRV) have also been investigated, both alone and in combination with protection systems.
This paper gives an overview of the work performed by BAM in the field of BLEVE prevention of protecting system since the last 30 years. It has been shown that e.g. with a full applied coating degree on the tank with and without PRV can be reached an exposition in a test fire scenario a duration of more than 60min. For partly coated tanks with and without PRV the duration time is like an unprotected vessel. Furthermore, it could be shown that the active water system also protects with technically correct design.
Fire testing
(2013)
Fire testing
(2013)
The phenomenon whereby the tank fails in a fire is described as a BLEVE. BLEVE Stands for boiling liquid expanding vapour explosion. This describes the sudden Vaporisation of a boiling, liquid under pressure followed by ignition. BLEVE are very complex phenomena which are influenced by a number of factors.
Die Vorhersage der Beanspruchung bei plastischem Versagen von zylindrischen Druckbehältern wird häufig mittels Finite Elemente Berechnungen durchgeführt. Die Berechnung der zulässigen Beanspruchung erfordert ein elastisch-plastisches Werkstoffmodell und die Berücksichtigung von nichtlinearen geometrischen Effekten. Das plastische Versagen verursacht eine gesamte Strukturinstabilität und kann nicht direkt aus der Finite Elemente Analyse bestimmt werden. In dem vorliegenden Beitrag wird die Beanspruchung für plastisches Versagen eines zylindrischen Druckbehälters mittels eines analytischen Verfahrens basierend auf einem linear elastischen ideal-plastischen Materialmodell bestimmt. Wenn Plastizität auftritt, wird zum einen der Werkstoff als inkompressibel und zum anderen der Tensor der plastischen Dehnungen als parallel zum Spannungsabweichungstensor angenommen. In diesem Fall kann die Spannungs-Dehnungs-Beziehung von Henkel angewendet werden, um den Druck zu berechnen, bei dem plastisches Fließen und Versagen eintritt. Die analytischen Ergebnisse werden von den Finite Elemente Berechnungen vollkommen bestätigt.
A new tank design for Hazmat
(2016)
Initial studies have shown pre-deformed honeycomb structure
pressure vessels to have comparable burst pressure to straight steel vessels.
It was shown that honeycomp structured tanks have a higher energy absorption than straight steel tanks.
Future studies will investigate optimization of the deformed plate, to determine if increased payloads or a reduced wall thickness can be achieved.
Limit load analysis is a well known method to calculate the allowable design pressure of container components. A limit load of a pressurized container is achieved, when the stress of a wall and the flow stress are equal. In the following paper the transferability of limit load analysis from small scale tank containers up to large scale containers (railway tank) are investigated. Finite element calculations are carried out and compared with experimental results. It can be concluded that the limit load analysis works very well. Furthermore, the yield strength of the material should be used as flow stress.
The prediction of the plastic collapse load of cylindrical pressure vessels is very often made by using expensive Finite Element Computations. The calculation of the collapse load requires an elastic-plastic material model and the consideration of non-linear geometry effects. The plastic collapse load causes overalls structural instability and cannot be determined directly from a finite element analysis. The ASME (2007) code recommends that the collapse load should be the load for which the numerical solution does not converge. This load can be only determined approximately if a expensive nonlinear analysis consisting of a very large number of sub steps is done. The last load sub step leading to a convergent solution will be taken as the critical load for the structure. In the instability regime no standard finite element solution can be found because of the lack of convergence of the numerical procedure. Other methods for the calculation of the allowable pressure proposed by the ASME code are the elastic stress analysis and the limit load analysis. In the present paper the plastic collapse load for a cylindrical pressure vessel is determined by an analytical method based on a linear elastic perfectly plastic material model. When plasticity occurs the material is considered as incompressible and the tensor of plastic strains is parallel to the stress deviator tensor. In that case the finite stress-strain relationships of Henkel can be used for calculating the pressure for which plastic flow occurs at the inside of the vessel wall or in the case of full plasticity in the wall. The analytical results are fully confirmed by finite element predictions both for axisymmetric and high costs three dimensional models. The analytical model can be used for fast predictions of the allowable load for the design of a large variety of pressure vessels under safety considerations. The accuracy of the predicted collapse load largely depends on the quality of the temperature dependent wall material data used both in the analytical and numerical calculations.
Liquefied propane gas (LPG) tanks in a fully engulfing accidental fire experience a fast increase in internal pressure. The result is often a Boiling Liquid Expanding Vapor Explosion (BLEVE) that can result in a large fireball and flying debris over a radius of more than 100 meters. In the last 30 years BAM has carried out more than 30 real scale fire tests on propane storage vessels across three test sites. The primary research goal was to identify systems that can delay or prevent a BLEVE. Early studies started with water deluge systems, and have since moved on to consider alternative protection systems. It has been shown that an unprotected vessel fails within 10 minutes or less. Tests with different oil and propane fueled fires have given an overview on possible real accidents involving full-engulfing scenarios. LPG tanks of various sizes (2.7 m³, 3.6 m³, 4.8 m³, 6.7 m³) were used with different filling levels. Numerous protection systems, ranging from active systems like water systems to passive thick- and thin-film layers. Also, the degree of thickness of these layers was variated. Pressure relief valves (PRV) have also been investigated, both alone and in combination with protection systems. This paper gives an overview of the work performed by BAM in the field of BLEVE prevention of protecting system since the last 30 years. It has been shown that e.g. with a full applied coating degree on the tank with and without PRV can be reached an exposition in a test fire scenario a duration of more than 60min. For partly coated tanks with and without PRV the duration time is like an unprotected vessel. Furthermore, it could be shown that the active water system also protects with technically correct design.
Several geometrical analytical tools can be used for assessing the potential benefits of any alternative tank shape. The quasistatic evaluation of the cargo-vehicle behavior represents a fast way to objectively determine the roll stability benefits of any potentially new tank shape. In this paper, the geometrical, quasistatic rollover performance of a convex bottom tank shape is compared with that of standard tank shapes, finding that in spite of the lower position of the cargo´s center of gravity in such a tank shape for the un-perturbed condition, it has the same performance as the elliptical tank shape when subjected to Steady lateral acceleration. That as a result of the large cargo´s lateral displacement. Consequently, the combination of a lower center of gravity for the cargo when it is not perturbed, and a Minimum lateral shift due to lateral accelerations inputs, define the conditions for an ideal tank shape.