The amount of heat, which is released by fire loads during the combustion
process, depends on the material characteristics, the ventilation
conditions, the storage density and the distribution. To evaluate the
structural stability of buildings in case of fire, the fire load has to be
quantified. In Germany, the fire load is quantified by using the combustion
factor m, while internationally the combustion efficiency χ is
applied. Both factors assess the burning behavior of materials, but the
determination is carried out in different ways. Since the testing facility
was abolished fifteen years ago, it is not possible to determine the combustion
factor m anymore. So, it should be found out, if the combustion
efficiency χ is a convenient method to quantify the fire load under the
consideration of the German standards. As a part of the research, combustion
efficiencies χ were determined for eight materials in the cone
calorimeter and the single burning item test at different heat fluxes.
The values of the combustion efficiencies χ as well as the corresponding
combustion factors m were discussed and compared to the values of the
literature. The results show an influence of the testing facility on the
combustion efficiency. The values of the combustion efficiency determined
in the single burning item test were higher than the values from
the cone calorimeter.
The Fractional Effective Dose model was used to predict the fire smoke toxicity numerically. In this context fire tests were carried out for three different building materials: polyurethane, flame retardant polyurethane and polyvinyl chloride. The fire tests were performed for flaming and smoldering combustion. The aim of the fire tests was to determine the light extinction, the smoke density and the combustion products at varying oxygen concentrations, different temperatures and different irradiance levels. The fire tests were performed in the German DIN-tube and also in the Cone Calorimeter. Stoichiometric coefficients at varying oxygen concentrations and temperatures were determined from measurements. With these stoichiometric coefficients reaction equations were defined and implemented in the Computational Fluid Dynamics (CFD) program, ANSYS CFX. The implemented reaction equations were used to account for different ventilation and temperature conditions in the simulation. The fire and smoke propagation was calculated numerically with CFD in the room corner test geometry. Equations to account for toxicity and light extinction were also implemented and were used to analyse the toxicity and the optical properties of fire smoke with CFD.