Filtern
Erscheinungsjahr
Dokumenttyp
- Beitrag zu einem Tagungsband (24)
- Zeitschriftenartikel (18)
- Vortrag (6)
- Beitrag zu einem Sammelband (3)
- Buchkapitel (1)
- Posterpräsentation (1)
- Forschungsbericht (1)
Schlagworte
- CFD (7)
- Fire (7)
- Computational fluid dynamics (5)
- Concrete (4)
- FDS (4)
- Tunnel (4)
- Brandszenarien (3)
- Computational Fluid Dynamics (3)
- Modellierung von Bränden (3)
- Rauchausbreitung (3)
Organisationseinheit der BAM
Paper des Monats
- ja (2)
Eingeladener Vortrag
- nein (6)
Fire smoke contains a variety of highly toxic substances and can lead to unconsciousness within a few minutes and to death for critical concentrations. Currently the engineer’s methods of fire safety include various procedures to calculate the fire propagation and smoke spread in buildings.
However, up to now the evaluation and calculation of smoke concerning its optical properties and toxic potential on the basis of a detailed combustion is still a field of research. Since smoke composition is highly variable and not fully characterised it has to be examined whether and how the Chemical composition and the optical properties of smoke are correlating. A method has been developed that establishes the relation between the smoke components and smoke toxicity.
Lithium-ion batteries are a key technology to achieve the goals of limiting climate change due to the important role as traction technology for Electric Vehicles and in stationary energy storage systems. Over(dis) charge, mechanical damage due to accidents or thermal abuse such as fires can initiate an accelerated self-heating process of the batteries, called thermal runaway. A thermal runaway can propagate from cell to cell within a larger assembly of cells such as modules or battery packs and can cause rapid heat and toxic gas emissions. The resulting battery fire can spread to adjacent facilities, e.g. other cars in underground car parks or to a whole building in case of a large stationary energy storage.
For proof of fire protection requirements or to design suitable fire protection systems, Computational Fluid Dynamic (CFD) simulations are getting more and more important. The aim of CFD fire simulations is to predict the global hazards of a fire to its surroundings, that is mainly characterized by the release of heat and smoke and its spread in the fire environment. There are many numerical investigations of lithium-ion batteries in the literature. One class of models is used to simulate the charge and discharge process of lithium-ion batteries and to predict the temperature or voltage evolution inside the battery. On the other hand, there are models describing batteries under abuse conditions to predict the consequences of a thermal runaway event to the local environment, like the temperatures inside a battery or at the battery surface. Henriksen et al. use a generic battery gas mixture to simulate an explosion of vented gases from a Lithium Iron Phosphate battery and compare experimental results for the explosion pressure and the position of the flame front to the outcomes of a simulation with Xifoam. Larsson et al. used a combination of CFD simulations with FDS and thermal model with COMSOL to predict the temperature development of neighboring cells in a thermal runaway propagation. Truchot et al. use a design Heat Release Rate (HRR) curve for a battery based on experimental measurements to build up an overall HRR curve for a truck loaded with 100 lithium-ion batteries. This summed up HRR and corresponding smoke production curve is then used as an input for a simulation of a truck fire in a tunnel with Fire Dynamics Simulator (FDS). The pre-definition of the HRR curve is a frequently used method in fire engineering. It has the disadvantage, that the heat release cannot be influenced by physical processes, such as changed ventilation conditions or extinguishing measures. In this paper, a model is presented that determines the release of heat and gases based on the thermal runaway mechanisms of the battery, which can be used in CFD fire simulations with focus on prediction of fire hazards to nearby environment.
Bei der Erstellung von brandschutztechnischen Nachweisen für Industriebauten werden häufig Ingenieurmethoden des Brandschutzes genutzt. Dazu zählen die Modellierung und Berechnung von Brandszenarien mittels numerischer Strömungsmechanik (computational fluid dynamics, CFD). In dieser Arbeit wurde ein auf numerischer Strömungs- und Strukturmechanik basierendes Verfahren zur brandschutztechnischen Bemessung von Bauteilen am Beispiel einer Industriehalle angewendet. Instationäre Temperaturverläufe aus der Heißgasschicht dienten dabei als Eingangswerte für die Bauteilberechnung. Aus den Ergebnissen wurde die äquivalente Branddauer berechnet, mit der die rechnerisch erforderlichen Feuerwiderstandsdauern der Bauteile bestimmt werden konnte.
Anwendung und Vergleich von Verfahren zur Berechnung der äquivalenten Branddauer im Industriebau
(2013)
Die äquivalente Branddauer tä wird zur Bestimmung der Feuerwiderstandsdauer erftp von Bauteilen in Industriebauten verwendet. Die Berechnung erfolgt bislang auf der Grundlage des normativenAnsatzes nach DIN 18230 (Verfahren I) und gilt im Zusammenhang mit der Muster-Industriebaurichtlinie (M IndBauRL). Im Rahmen von brandschutztechnischen Nachweisen für Industriebauten ist es ebenfalls möglich, die äquivalente Branddauer unter Anwendung numerischer Methoden zu berechnen (Verfahren II). Die Anwendung solcher Ingenieurmethoden des Brandschutzes ermöglichen die Berücksichtigung komplexer Gebäudegeometrien und Ventialtionsbedingungen sowie lokaler Brandwirkungen auf Bauteile infolge inhomogener Brandlastverteilungen.
Am Beispiel einer Industriehalle werden die Verfahren I und II angewendet und die Ergebnisse gegenübergestellt.
Approaches towards a generic methodology for storage of hazardous energy carriers and waste products
(2013)
Energy carriers – either conventional or 'new' ones – have to be provided in large amounts to meet the requirements of permanent availability and reliable supply of electricity. Depending on their state of aggregation, energy carriers are either stored in large masses (if solid or liquid) or at elevated pressures (if gaseous). Both impose the hazard of large-scale fire, in the latter case additionally the danger of explosion or unintended release. Very similar hazards occur for wastes. Solid wastes are present in large masses and only a small part is recycled. Most of the solid wastes are used in energy conversion. The main gaseous waste is CO2. During capturing also the hazard of unintended release exists. In this article, existing approaches for safe storage and fire prevention are discussed and a generic methodology is outlined. This methodology consists of the following steps:
gaining knowledge about the behaviour of the material stored (reactivity, thermal stability, etc.),
assessing the environmental conditions for the storage site (neighbourhood, safety distances, etc.),
assessment of prospective consequences of an incident and
development of individual loss prevention conceptions.
All steps require both experimental testing and theoretical considerations about accident scenarios as integral parts of the methodology.
Brandverhalten von Bauprodukten: Brauchen wir Regelungen für die Menge und Giftigkeit der Rauchgase?
(2008)
In urban areas the demand for public transportation is constantly growing. Underground railway systems overcome the problem of limited space on the ground and are therefore one of the most powerful systems in urban public transportation. These facilities can be very complex and are used by a large amount of passengers. Therefore, it is important to maintain the safety for people and buildings. Especially in the case of fire or arson attack.
This paper focusses on a fire scenario in a complex subway station for different weather conditions. The purpose is to identify the influences of different weather conditions on the smoke spread and the ability of self-rescue in case of a burning luggage.
The evaluation of the fire simulations will focus on toxicity and visibility taking into account the FED concept.
CFD modeling approach of smoke toxicity and opacity for flaming and non-flaming combustion processes
(2016)
Current engineer’s methods of fire safety design include various approaches to calculate the fire Propagation and smoke spread in buildings by means of computational fluid dynamics (CFD). Because of the increased computational capacity, CFD is commonly used for prediction of time-dependent safety parameters such as critical temperature, smoke layer height, rescue times, distributions of chemical products, and smoke toxicity and visibility. The analysis of smoke components with CFD is particularly complex, because the composition of the fire gases and also the smoke quantities depends on material properties and also on ambient and burning conditions. Oxygen concentrations and the temperature distribution in the compartment affect smoke production and smoke gas toxicity qualitatively and quantitatively. For safety designs,
it can be necessary to take these influences into account. Current smoke models in CFD often use a constant smoke yield that does not vary with different fire conditions. If smoke gas toxicity is considered, a simple approach with the focus on carbon monoxide is often used. On the basis of a large set of experimental data, a numerical smoke model has been developed. The developed numerical smoke model includes optical properties, production, and toxic potential of smoke under different conditions. For the setup of the numerical model, experimental data were used for calculation of chemical components and evaluation of smoke toxicity under different combustion conditions. Therefore, averaged reaction equations were developed from experimental measurements and implemented in ANSYS CFX 14.0.
This paper analyses the suitability of the Sensible Enthalpy Rise Approach for measuring the heat release rate of electric-vehicle-scale lithium-ion batteries. An apparatus is designed that meets the conditions of an electric-vehicle-scale lithium-ion battery fire by using cement board as wall material. Modifications of the Sensible Enthalpy Rise Methodology are presented due to the high emissivity and inhomogeneous temperature distribution of the apparatus wall material: a power 4 approach for the heat flow from the walls to the ambient air and an alternative determination methodology for the wall temperature. A one factor at a time parameter study is performed with Computational Fluid Dynamics simulations, investigating a new calibration method based on a fit approach compared to common methods, the wall temperature determination, the approach for the ambient heat flow, the calibration power and the volume flow at the outlet. The simulations show, that suitable estimations of the heat release rate are obtained by using the modifications for wall temperature determination and the power 4 approach for the ambient heat flow. The three calibration methods provide suitable constants, if the calibration power in the same order of magnitude as the mean of the heat release rate profile of the test object.
Based on forensic evidence, a smouldering fire was observed to have occurred at a murder scene. Identification of a reasonable timeline – specifically the fire dynamics of the ignition and fire growth that occurred coincident with the death that took place – became an important focus of the criminal investigation that followed. The fire service was called when a neighbour saw a grey smoke escaping through the ventilation system of the bathrooms on the roof of the house. One flat door with elevated temperatures was found. The fire fighter who entered the flat first reported later that the flat was completely filled with smoke and all windows were closed. When the fire fighter opened the balcony door, he saw flames on the sofa that he extinguished. Then he found a body on the floor. The autopsy showed later that the victim was dead before the fire started. The police suspected that the murderer probably had deliberately set the fire to destroy evidence. One suspect had been witnessed to be in the flat approximately 2 h before the fire was detected by the neighbour. The aim of this project was to investigate how the fire most likely started and developed.
Based on methane from renewable resources, LNG is an alternative fuel for heavy and long-distance traffic in land transport. Contrary to its positive properties, the fuel contains risks from an explosion and extremely low temperatures for personal and infrastructure safety. CFD-models are suitable for doing risk analyses for arbitrary scenarios. For examining how to model for risk research the dispersion of LNG-vapor, this paper contains a model variant study, with an evaluation by experiments.
This paper describes the use of the CFD-code ANSYS Fluent for simulating experiments of the ‘LNG Safety Program Phase II‘. The content of the well-documented experiments was the research of the vaporization rate of LNG on land and the dispersion of LNG-vapor in the air. Based on the comparison to two experiments, overall 12 CFD-model variants with varying thermal and turbulence parameters were examined how they affect the transient LNG-vapor dispersion in air.
The definition of turbulence-boundary-condition at the domain borders had the biggest impact on modeling, followed by the turbulence model. The most accurate model variant had been applied for observing the spreading behavior of LNG-vapor in the air after evaporation on land and analyzing the influence of the LNG-composition to the dispersion. The results show that the mixture of LNG-vapor and the air in the free field is cooler than the ambient air and spreads like a heavy gas on the ground.
Vor dem Hintergrund der Zurückziehung der DIN 18230 Teil 2 zur Bestimmung des m-Faktors von Materialien für die Brandlastbewertung im Industriebau müssen neue Wege gefunden werden, wie das Abbrandverhalten alternativ quantifiziert werden kann. Der Beitrag fasst die Entstehung und die Entwicklung der Bestimmungsweise von Abbrandfaktoren zusammen und gibt Ausblick auf eine neue Möglichkeit zur Bewertung von Brandlasten, die Verbrennungseffizienz.
Nach DIN 18230-1 erfolgt in Deutschland die Brandlastberechnungen unter Anwendung
des Abbrandfaktors m. Der Abbrandfaktor m ist ein dimensionsloser Beiwert mit dem die
Brandlast aus einem Stoff oder Stoffgemisch bewertet wird. Neben dem Brandverhalten
des Stoffes berücksichtigt er das Temperatur-Zeit-Verhalten im Bauteil. Die einzige
Prüfapparatur, mit der Abbrandfaktoren bestimmt wurden, ist jedoch nicht mehr existent.
Ein Wiederaufbau der abgeschafften Prüfapparatur wurde wegen apparateabhängigen
Messunsicherheiten und auch aus wirtschaftlichen Gründen als nicht sinnvoll angesehen.
Die Erarbeitung eines äquivalenten Verfahrens zum Abbrandfaktor m unter Verwendung
der Verbrennungseffektivität und unter Berücksichtigung der Bauteilerwärmung war daher
Gegenstand dieses Forschungsvorhabens. Ziel war es für Brandlastberechnungen
nach DIN 18230-1 die Verbrennungseffektivität anzuwenden. Die Verbrennungseffektivität
beschreibet jedoch nur den verringerten Energieumsatz von Stoffen im Brandraum.
Es wurde daher ein Verfahren erarbeitet, dass ergänzend zur Brandlastberechnung unter
Anwendung der Verbrennungseffektivität das Temperatur-Zeit-Verhalten in einem
brandbelastenden Bauteil berücksichtigt.
Brandlasten stellen eine Gefahr für den Menschen sowie für das industrielle Gebäude dar, in dem sie gelagert sind. Das Brandverhalten der Brandlasten bestimmt dabei maßgeblich die Schwere der Gefahr. Brandschutzmaßnahmen dienen dazu, im Brandfall das Schadensausmaß zu minimieren. Um geeignete Brandschutzmaßnahmen ableiten zu können, ist es erforderlich, das Brandverhalten der Materialien zu bewerten. Eine international angewandte Möglichkeit zur Bewertung des Brandverhaltens von Feststoffen und Flüssigkeiten ist die Verbrennungseffizienz χ. Sie ist das Verhältnis der während einer Verbrennung effektiv freigesetzten Wärme (effektive Verbrennungswärme) zu der maximal möglichen Wärmemenge (Heizwert). Die Grundlage zur Bestimmung von Verbrennungseffizienzen stellen die Wärmefreisetzungsrate (HRR) und die Massenverlustrate (MLR) dar. Ein standardisiertes Bestimmungsverfahren existiert nicht. So liegt es in dem Ermessen des Anwenders, in welcher Prüfapparatur die Experimente durchgeführt werden und welcher Zeitbereich der HRR und der MLR zur Berechnung der Verbrennungseffizienz verwendet wird. Im Rahmen dieser Arbeit wurden Versuche im Cone Calorimeter und im Single Burning Item test anhand von hölzernen Materialien durchgeführt. Die Ergebnisse zeigen auf, dass sich in Abhängigkeit von der verwendeten Prüfapparatur und in Abhängigkeit des für die Berechnung betrachten Versuchszeitraumes verschiedene Werte der Verbrennungseffizienz ergeben. Auf Grundlage dieser Erkenntnisse wurde eine Methode entwickelt, mit der reproduzierbare Werte berechnet werden können. Dabei erfolgt die Berechnung lediglich für die Vollbrandphase. Diese Brandphase stellt die Hauptbrandphase dar und ist durch eine gleichmäßige Verbrennung mit wenigen Änderungen in der Branddynamik gekennzeichnet.
From a fire safety point of view, the burning behavior of lithium-ion batteries is of high interest. The heat release rate (HRR) is the most important fire parameter to analyze the fire hazards of burning objects, so that an accurate determination of it is crucial. In this paper, two different measurement techniques, the Oxygen Consumption Calorimetry (OCC) and the Sensible Enthalpy Rise Approach (SERA) are simultaneously performed in the same calorimeter to measure the HRR of two different types of lithium-ion batteries. HRR values as well as total energies determined by SERA are higher than measured with OCC: The total energy released is about 10–12 times (SERA) and 6–9.5 times (OCC) the electrical stored energy for both battery types, whereas the timescales of the release differ strongly between the types, resulting in maximum HRRs of 3.4 MW (SERA) and 1.5 MW (OCC)
for one module of type A and 0.8 MW (SERA) and 0.6 (OCC) of type B respectively. Furthermore, a sensitive dependency of the HRR measurement with SERA on the position of the wall temperature measurement is observed.
In this paper, the influence of a fixed water mist firefighting system on a high-speed non-premixed horizontal methane jet fire is investigated with focus on its effect on temperatures and heat load of the jet fire and on ist surroundings. Six tests are performed in which gas is released out of an orifice with a diameter of 1 mm and a release pressure of up to 186 bar. In addition to temperature and radiation measurements, the release pressure, gas mass flow rate and exhaust gas concentrations are detected to determine the heat release. Video and IRanalysis are used to evaluate the interactions between jet fire and water mist. The experiments show, that water mist reduces the temperatures inside the jet fire flow field and its radiative heat flux. It can lower the Risk of ignition of adjacent surfaces and materials, as temperatures fall below autoignition temperatures of common materials like plastics. Although water mist does not extinguish the fire, it has an impact on the energy release by reducing combustion efficiency due to heat exchange with the water mist and oxygen displacement.