Approaches towards a generic methodology for storage of hazardous energy carriers and waste products
(2013)
Energy carriers – either conventional or 'new' ones – have to be provided in large amounts to meet the requirements of permanent availability and reliable supply of electricity. Depending on their state of aggregation, energy carriers are either stored in large masses (if solid or liquid) or at elevated pressures (if gaseous). Both impose the hazard of large-scale fire, in the latter case additionally the danger of explosion or unintended release. Very similar hazards occur for wastes. Solid wastes are present in large masses and only a small part is recycled. Most of the solid wastes are used in energy conversion. The main gaseous waste is CO2. During capturing also the hazard of unintended release exists. In this article, existing approaches for safe storage and fire prevention are discussed and a generic methodology is outlined. This methodology consists of the following steps:
gaining knowledge about the behaviour of the material stored (reactivity, thermal stability, etc.),
assessing the environmental conditions for the storage site (neighbourhood, safety distances, etc.),
assessment of prospective consequences of an incident and
development of individual loss prevention conceptions.
All steps require both experimental testing and theoretical considerations about accident scenarios as integral parts of the methodology.
Vehicle fires in tunnels can have catastrophic consequences for the road users, the property and traffic inffastructure. To support an evacuation planning, this study simulates the fire smoke toxicity and the smoke layer of a vehicle fire in a full-size test tunnel. The three dimensional prediction of the fire smoke toxicity in the test tunnel is realized by implementing the Fractional Effective Dose and the Fractional Summation concept in a CFD environment. The developed model facilitates to calculate fire scenarios for various types of tunnels and to quantify the hazard e.g. during an evacuation scenario.
Fire smoke contains a variety of highly toxic substances and can lead to unconsciousness within a few minutes and to death for critical concentrations. Currently the engineer’s methods of fire safety include various procedures to calculate the fire propagation and smoke spread in buildings.
However, up to now the evaluation and calculation of smoke concerning its optical properties and toxic potential on the basis of a detailed combustion is still a field of research. Since smoke composition is highly variable and not fully characterised it has to be examined whether and how the Chemical composition and the optical properties of smoke are correlating. A method has been developed that establishes the relation between the smoke components and smoke toxicity.
Safety measures like tunnel emergency Ventilation Systems cause high financial costs. Hence, safety measures have to be chosen with the focus on the expected reduction of the consequences like fatalities or damage on structures and in conjunction with the investments. Since 2004, the European directive EU 2004/54/EC proposes therefore the application of risk assessments. Because the EU directive provides only few legal requirements on risk assessments, the methodologies developed on this basis have large differences. After one decade of intensive research, the comparative study now highlights common aspects and differences of several methodologies.
Brände in Wohnungen entwickeln sich heutzutage sehr schnell, weil der Anteil an brennbaren Materialien in Einrichtungsgegenständen und elektrischen Geräte in den letzten Jahren signifikant zugenommen hat. Insbesondere Brände in Kinderzimmern können sehr gefährlich sein, was mehrere Brände in Deutschland in den letzten Jahren belegen. Um die Brand- und Rauchentwicklung bei einem solchen Brand zu untersuchen, wurde ein Testraum wie ein typisches Kinderzimmer möbliert und mit 36 Thermoelementen sowie einem Druckmessgerät ausgestattet. Zusätzlich wurden Rauchmelder installiert. Der Brand wurde mittels eines Teelichts initiiert, das für ca. eine Sekunde mit einer Matratze in Kontakt gebracht wurde. Der Feuerüberschlag fand nach nur vier Minuten statt. Sowohl die Brandlast als auch die Brand- und Rauchentwicklung wurden untersucht. Vorschriften zur Brandsicherheit von Einrichtungsgegenständen, elektrischen Geräten und Spielzeugen wurden diskutiert. Ergänzend wurde der Temperaturanstieg im Brandraum unter Anwendung des Verfahrens von McCaffrey vorhergesagt.-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Fires in homes develop very fast nowadays, because the amount of
combustible materials in furniture and electrical devices has increased
significantly in recent years. Especially fires in children's
rooms can be very hazardous as several recent fires in Germany
showed. To investigate the fire and smoke development in such a fire
the test room was furnished like a typical childrens room and
equipped with 36 thermocouples and a pressure measurement device.
Also smoke detectors were installed. The fire was ignited by a small
candle which was in contact with a mattress only for one second.
Flashover occurred only after 4 minutes. The fire load and the fire and
smoke development were investigated. The fire safety regulations for
the furnishings, electrical devices and toys were discussed. Additionally
the temperature rise in the compartment was predicted according
to the method of McCaffrey.
Based on forensic evidence, a smouldering fire was observed to have occurred at a murder scene. Identification of a reasonable timeline – specifically the fire dynamics of the ignition and fire growth that occurred coincident with the death that took place – became an important focus of the criminal investigation that followed. The fire service was called when a neighbour saw a grey smoke escaping through the ventilation system of the bathrooms on the roof of the house. One flat door with elevated temperatures was found. The fire fighter who entered the flat first reported later that the flat was completely filled with smoke and all windows were closed. When the fire fighter opened the balcony door, he saw flames on the sofa that he extinguished. Then he found a body on the floor. The autopsy showed later that the victim was dead before the fire started. The police suspected that the murderer probably had deliberately set the fire to destroy evidence. One suspect had been witnessed to be in the flat approximately 2 h before the fire was detected by the neighbour. The aim of this project was to investigate how the fire most likely started and developed.
The amount of heat, which is released by fire loads during the combustion
process, depends on the material characteristics, the ventilation
conditions, the storage density and the distribution. To evaluate the
structural stability of buildings in case of fire, the fire load has to be
quantified. In Germany, the fire load is quantified by using the combustion
factor m, while internationally the combustion efficiency χ is
applied. Both factors assess the burning behavior of materials, but the
determination is carried out in different ways. Since the testing facility
was abolished fifteen years ago, it is not possible to determine the combustion
factor m anymore. So, it should be found out, if the combustion
efficiency χ is a convenient method to quantify the fire load under the
consideration of the German standards. As a part of the research, combustion
efficiencies χ were determined for eight materials in the cone
calorimeter and the single burning item test at different heat fluxes.
The values of the combustion efficiencies χ as well as the corresponding
combustion factors m were discussed and compared to the values of the
literature. The results show an influence of the testing facility on the
combustion efficiency. The values of the combustion efficiency determined
in the single burning item test were higher than the values from
the cone calorimeter.
The time dependent thermal behavior is analyzed with FLUENT for the fluid as well as the solid region (concrete component) in case of a 100 MW n-heptane fire. To study the effect of parameters in mathematical-physical models several sensitivity studies were carried out to investigate the effect on the fluid flow as well as on the component. The influence of soot was additionally considered. FDS simulations as well as empirical calculations considering underlying assumptions are additionally used to examine the plausibility of results from the FLUENT simulations. This is an appropriate method if no experimental results are available. Recommendations are given for choosing parameters in mathematical-physical models e.g. radiation models. The results of the CFD investigations show that considering the influence of soot provides maximum temperatures which were 200 K lower than without soot.
Methodologies on fire risk analysis in road tunnels consider numerous factors affecting risks (risk indicators) and express the results by risk measures. But only few comprehensive studies on effects of risk indicators on risk measures are available. For this reason, this study quantifies the effects and highlights the most important risk indicators with the aim to Support further developments in risk analysis. Therefore, a system model of a road tunnel was developed to determine the risk measures.
The system model can be divided into three parts: the fire part connected to the fire model Fire Dynamics Simulator (FDS); the evacuation part connected to the evacuation model FDS+Evac; and the frequency part connected to a model to calculate the frequency of fires. This study shows that the parts of the system model (and their most important risk indicators) affect the risk measures in the following order: first, fire part (maximum heat release rate); second, evacuation part (maximum preevacuation time); and, third, frequency part (specific frequency of fire). The plausibility of These results is discussed with view to experiences from experimental studies and past fire incidents.
Conclusively, further research can focus on these most important risk indicators with the aim to optimise risk analysis.
CFD modeling approach of smoke toxicity and opacity for flaming and non-flaming combustion processes
(2016)
Current engineer’s methods of fire safety design include various approaches to calculate the fire Propagation and smoke spread in buildings by means of computational fluid dynamics (CFD). Because of the increased computational capacity, CFD is commonly used for prediction of time-dependent safety parameters such as critical temperature, smoke layer height, rescue times, distributions of chemical products, and smoke toxicity and visibility. The analysis of smoke components with CFD is particularly complex, because the composition of the fire gases and also the smoke quantities depends on material properties and also on ambient and burning conditions. Oxygen concentrations and the temperature distribution in the compartment affect smoke production and smoke gas toxicity qualitatively and quantitatively. For safety designs,
it can be necessary to take these influences into account. Current smoke models in CFD often use a constant smoke yield that does not vary with different fire conditions. If smoke gas toxicity is considered, a simple approach with the focus on carbon monoxide is often used. On the basis of a large set of experimental data, a numerical smoke model has been developed. The developed numerical smoke model includes optical properties, production, and toxic potential of smoke under different conditions. For the setup of the numerical model, experimental data were used for calculation of chemical components and evaluation of smoke toxicity under different combustion conditions. Therefore, averaged reaction equations were developed from experimental measurements and implemented in ANSYS CFX 14.0.