There is no applicable existing standard for the determination of safety characteristics for hybrid mixtures. While developing a new standard in a joint research project in Germany first results from parameter studies led to a standard procedure that can be adopted by laboratories that are already testing dusts in the so called 20L-sphere with as little additional effort as necessary. In fact, one of the main objectives of this research project was to keep modifications and adjustments from the generally accepted dust testing procedures as easy and minimal as possible so as to limit potential deviations from one laboratory to another.
In this first round robin test on hybrid mixtures ever, with methane as gas component and a specific corn starch as dust sample, the practicality of the whole procedure, the scattering of the results and the deviation between the testing apparatuses is investigated. This paper summarizes the experimental procedure adopted and objectives of the first round-robin phase involving three of the four original German companies, plus volunteering laboratories from Australia, Belgium, Czech Republic, France, Poland and P.R. China. The results will have an impact on the new standard and may lead to robust data for later simulation purposes.
Safety characteristics are used to keep processes, including flammable gases, vapors, and combustible dusts, safe. In the standards for the determination of safety characteristics of gases and vapors, the induction spark is commonly used. However, classic transformers are hard to obtain, and replacement with new electronic transformers is not explicitly allowed in the standards. This article presents the investigation of five gases that are normally used to calibrate devices for the determination of safety characteristics, the maximum experimental safe gap (MESG), with an electronic transformer, and the values are compared to the ones that are obtained with the standard transformer. Additionally, calorimetric measurements on the net energy of both ignition sources were performed as well as open-circuit voltage measurements. It is concluded that the classic type of transformer can be replaced by the new type obtaining the same results for the MESG and introducing the same amount of energy into the system.
The hybrid mixture of combustible dusts and flammable gases/vapours widely exist in various industries, including mining, petrochemical, metallurgical, textile and pharmaceutical. It may pose a higher explosion risk than gas/vapor or dust/mist explosions since the hybrid explosions can still be initiated even though both the gas and the dust concentration are lower than their lower explosion limit (LEL) values. Understanding the explosion threat of hybrid mixtures not only contributes to the inherent safety and sustainability of industrial process design, but promotes the efficiency of loss prevention and mitigation. To date, however, there is no test standard with reliable explosion criteria available to determine the safety parameters of all types of hybrid mixture explosions, nor the flame propagation and quenching mechanism or theoretical explanation behind these parameters. This review presents a state-of-the-art overview of the comprehensive understanding of hybrid mixture explosions mainly in an experimental study level; thereby, the main limitations and challenges to be faced are explored. The discussed main contents include the experimental measurement for the safety parameters of hybrid mixtures (i.e., explosion sensitivity and severity parameters) via typical test apparatuses, explosion regime and criterion of hybrid mixtures, the detailed flame propagation/quenching characteristics behind the explosion severities/sensitivities of hybrid mixtures. This work aims to summarize the essential basics of experimental studies, and to provide the perspectives based on the current research gaps to understand the explosion hazards of hybrid mixtures in-depth.
There are several standardized ignition sources in use for the determination of explosion characteristics of gases, vapors and dusts. In the standards the ignition source is stated, but they vary in stating other characteristics like burning duration, energy or burning volume. Since heat is not visible under normal circumstances a Schlieren-Technique was used to make the full heating volume and not just the flames visible.
While an earlier paper of the authors focused on the ignition energy and burning duration of four standardized ignition sources, this paper focuses on the initial igniting volume, the ratio between initial igniting volume and the test-vessel size and other phenomena that were observed with the Schlieren-Technique-.
There are several standardized ignition sources in use for the determination of explosion characteristics of gases, vapors and dusts. In the standards the ignition source is stated, but they vary in stating other characteristics like burning duration, energy or burning volume. Since heat is not visible under normal circumstances a Schlieren-Technique was used to make the full heating volume and not just the flames visible. While an earlier paper of the authors focused on the ignition energy and burning duration of four standardized ignition sources, this paper focuses on the initial igniting volume, the ratio between initial igniting volume and the test-vessel size and other phenomena that were observed with the Schlieren-Technique.
For the determination of safety characteristics of gases, vapors and dusts different types of ignition sources are used in international standards and guidelines. The paper presents test results of a comparative calorimetric and visual study between four different types of ignition sources. The ignition procedures were analyzed visually with a high-speed camera and electric recordings. In addition to that, the influence of the electrode-orientation, -distance as well as ignition energy on the reproducibility of the exploding wire igniter was tested.
The exploding wire is already in use for standardized determination of safety characteristics of gases, first tests on the suitability of the exploding wire igniter for dust testing have been carried out but are not standardized yet. Using the exploding wire, the ignition energy can be varied from 2 J to 10 000 J (2 x 5000 J) and thus it could be used for gases, vapors, dusts and hybrid mixtures. Moreover it can be used at high initial pressures and it is the only ignition source with an easily measurable ignition energy release. Furthermore, it does not introduce another chemical reaction into the system.
Finally, a proposal for a standard ignition source for explosion tests on hybrid mixtures is derived from the test results.
For the determination of safety characteristics of gases, vapors and dusts different types of ignition sources are used in international standards and guidelines. Table 1 compares technical relevant ignition sources with their main features. The paper presents test results of a comparative calorimetric and visual study between four different types of ignition sources. The ignition procedures were analyzed visually with a high-speed camera and electric recordings. In addition to that, the influence of the electrode-orientation, -distance as well as ignition energy on the reproducibility of the exploding wire igniter was tested.
The exploding wire is already in use for standardized determination of safety characteristics of gases, first tests on the suitability of the exploding wire igniter for dust testing have been carried out by Scheid et al. Using the exploding wire, the ignition energy can be varied from 2 to 10 000 J (2 x 5 000 J) and thus it could be used for gases, vapors, dusts and hybrid mixtures. Moreover it can be used at high initial pressures and it is the only ignition source with an easily measurable ignition energy release. Furthermore, it does not introduce another chemical reaction into the system.
Finally, a proposal for a standard ignition source for explosion tests on hybrid mixtures is derived from the test results.
For the determination of safety characteristics of gases, vapors and dusts different types of ignition sources are used in international standards and guidelines. Table 1 compares technical relevant ignition sources with their main features. The paper presents test results of a comparative calorimetric and visual study between four different types of ignition sources. The ignition procedures were analyzed visually with a high-speed camera and electric recordings. In addition to that, the influence of the electrode-orientation, -distance as well as ignition energy on the reproducibility of the exploding wire igniter was tested.
The exploding wire is already in use for standardized determination of safety characteristics of gases, first tests on the suitability of the exploding wire igniter for dust testing have been carried out by Scheid et al. Using the exploding wire, the ignition energy can be varied from 2 to 10 000 J (2 x 5 000 J) and thus it could be used for gases, vapors, dusts and hybrid mixtures. Moreover it can be used at high initial pressures and it is the only ignition source with an easily measurable ignition energy release. Furthermore, it does not introduce another chemical reaction into the system.
Finally, a proposal for a standard ignition source for explosion tests on hybrid mixtures is derived from the test results.