Investigations of corrosion on small cathodes in reinforced concrete - observations and suggestions
(2009)
Corrosion of steel reinforcement in concrete exposed to chloride containing environments is a serious
problem in civil engineering practice. The standards and guidelines contain only minimum
requirements regarding concrete quality and concrete cover. In very critical cases, for example the
ingress of chlorides, the application of different coatings is currently the only possibility to protect the
reinforced concrete structures. In this case the modelling of reinforcement corrosion would be more
practical. One sub-project of a DFG-research project (FOR 537) is currently performed at the Federal
Institute for Materials Research and Testing (BAM). Aim of the sub-project is the description of
corrosion propagation and the characterization of the corrosion on specimens with small cathodes by
electrochemical parameters. The electrochemical parameters are determined by suitable
electrochemical measurements, considering concrete parameters as well as different environmental
conditions.
Im Jahr 1986 wurde in Deutschland die erste kathodische Korrosionsschutzanlage für ein Stahlbetonbauwerk in Betrieb genommen. Die Installation, die Inbetriebnahme sowie die laufende Überwachung wurden wissenschaftlich begleitet.
Im Zuge notwendiger verkehrstechnisch bedingter Umbaumaßnahmen wurde die Anlage nach etwa 15 Jahren außer Betrieb genommen. Die in dieser Zeit durchgeführten Untersuchungen dienten dem Ziel, die an Laborversuchen gewonnenen Ergebnisse an einem praktischen Bauwerk zu überprüfen sowie Informationen über das Langzeitverhalten hinsichtlich Dauerhaftigkeit, Potentialverteilung, Temperaturabhängigkeit, Chloridmigration usw. zu bekommen.
Mit zunehmender Betriebsdauer konnten die Schutzkriterien nur durch Erhöhung der Gleichrichterspannung eingehalten werden (die Anlage wurde im Konstantspannungsmodus betrieben). Umfangreiche Untersuchungen an Anodenmaterialproben (leitfähiger Polymerdraht mit einem Kupferkern) nach 15-jährigem Einsatz zeigten, dass irreversible Veränderungen die Leitfähigkeit des Polymers erheblich vermindert haben, wodurch letztendlich die Funktionsfähigkeit der Anode nicht mehr gegeben war. Diese Art von Anoden werden aber heutzutage nicht mehr für den kathodischen Korrosionsschutz von Stahlbetonbauwerken eingesetzt.
Translated Abstract
Long-term experiences with a cathodic protection system for steel in concrete
In 1986 in Germany the first cathodic protection system for reinforced concrete structures was put into service. Installation, commissioning and the regular monitoring were scientifically supported.
Due to necessary traffic related reconstruction measures the system was switch off after 15 years of service. Investigations carried out during that period should verify laboratory test results at a real structure and furthermore yield information on the long-term behaviour concerning durability, temperature dependence, potential distribution, chloride migration etc.
With increasing time of service the protection criteria could only be met by increasing the transformer rectifier voltage (the system worked in the constant voltage mode). Extensive investigations of the anode material (conductive polymer wire with a copper core) after 15 years of service showed that irreversible changes substantially decreased the polymer's conductivity limiting the functionality. Today, these kind of anodes are not used any more for the application in cathodic protection systems of reinforced concrete structures.
Im Rahmen einer Bauwerksuntersuchung an einer in nachträglicher Verbundbauweise hergestellten Brücke wurden Anrisse an Spannstählen der Quervorspannung festgestellt, ohne daß Verpreßmängel oder korrosionsfördernde Substanzen vorlagen. Bei dem verwendeten Werkstoff handelt es sich um einen in der ehemaligen DDR hergestellten vergüteten Stahl der Festigkeitsklasse St 140/160. Ursache für die Anrisse ist die in Laborversuchen nachgewiesene Empfindlichkeit dieses Stahles gegenüber wasserstoffinduzierter Spannungsrißkorrosion, die unter ungünstigen Bedingungen dazu führen kann, daß Vorschädigungen vor dem Verpressen eintreten. Zusätzlich durchgeführte Magnetpulverprüfungen an ausgewählten Bereichen der Längsvorspannung ergaben keinerlei Hinweise auf Anrisse.
Translated Abstract
Stress corrosion cracking of prestressing steels
During the investigation of a post-tensioned bridge structure incipient cracks of the prestressing steels of the transverse prestressed members were observed. Defects related to non-injected ducts or the presence of corrosion inducing substances could not be detected. The prestressing steel used is a quenched and tempered steel, strength class St 140/160, which was produced in the former GDR. The cause for the cracks is the susceptibility of this type of steel to hydrogen-induced stress corrosion cracking as could be shown in laboratory tests. Under unfavourable conditions cracks can be initiated before grouting. Additional magnetic particle tests at selected areas of the longitudinal prestressed members did not indicate any signs for incipient cracks.
Prestressing steels can be exposed in prestressed concrete structures in construction stage (ungrouted duct) to environmental conditions causing formation and growth of hydrogen induced cracks with brittle fracture of the steel. The risk of this hydrogen induced stress corrosion cracking can be minimized by appropriate treatment, but there is a requirement for construction to approve only prestressing steel having no enhanced susceptibility to stress corrosion cracking. The paper describes the historical development of the different test methods proposed in the past and gives an overview on the general requirements for a suitable test method to assess the hydrogen-induced stress corrosion susceptibility of prestressing steels.
Since 1982, based on investigations on construction sites and transfer of the results into laboratory tests, a test method is available enabling realistic estimation of suitable application possibilities of prestressing steels. This so called DIBt-test is approved to distinguish between prestressing steels susceptible to hydrogen induced stress corrosion cracking and those suitable and therefore approvable steels at practical environmental conditions. Furthermore the test enables estimation of corrosion risk for newly developed prestressing steels with higher strength.
Translated Abstract
Beurteilung der Prüfverfahren zur Untersuchung der Spannungsrisskorrosionsempfindlichkeit von Spannstählen
Spannstähle können in Spannbetonbauwerken im Bauzustand (unverpresstes Hüllrohr) Umgebungsbedingungen ausgesetzt sein, die zur Bildung und Ausbreitung wasserstoffinduzierter Risse mit Sprödbruch des Stahles führen können. Das Risiko dieser wasserstoffinduzierten Spannungsrisskorrosion kann einerseits durch eine sachgemäße Verarbeitung der Spannstähle minimiert werden, andererseits besteht die Notwendigkeit nur solche Spannstähle für die Baupraxis zuzulassen, die unter baupraktischen Bedingungen keine erhöhte Empfindlichkeit für Spannungsrisskorrosion besitzen. Die vorliegende Arbeit beschreibt die historische Entwicklung der verschiedenen vorgeschlagenen Prüfverfahren und gibt einen Überblick über die allgemeinen Anforderungen an ein geeignetes Verfahren zur Beurteilung der wasserstoffinduzierten Spannungsrisskorrosionsempfindlichkeit von Spannstählen.
Seit 1982 steht, begründet durch Untersuchungen auf Baustellen und Umsetzung der Ergebnisse in Laborversuchen, ein Prüfverfahren zur Verfügung, das eine wesentlich realistischere Einschätzung der Einsatzmöglichkeiten von Spannstählen zulässt. Dieser sog. DIBt-Test hat sich bewährt, um unter praktischen Umgebungsbedingungen gegen H-induzierte Spannungsrisskorrosion empfindliche Spannstähle von geeigneten und damit zulassungswürdigen Stählen zu unterscheiden. Des weiteren erlaubt die Prüfung ebenfalls eine Abschätzung des Korrosionsrisikos für neuentwickelte, höherfeste Spannstähle.