For absorption processes with fluctuating feed gas compositions it is vital to continuously adjust
the operation point to achieve energy efficiency. In this contribution a Raman-based advanced
process control (APC) is introduced for the absorption of carbon dioxide (CO2) using an aqueous
solution of monoethanolamine (MEA). The APC is based on a Raman spectroscopic analysis of
the composition and CO2 load of the scrubbing liquid and a non-linear model predictive control
(NMPC) to adjust the scrubbing liquid cycle. In addition, an outer real-time optimization loop is
set in place to update the set points for the absorption process depending on the current feed gas composition minimizing the energy consumption of the process. Implementation and testing of the APC have been carried out in a mini-plant at TU Berlin. During a plant operation of more than 160 hours robustness and stability of the APC were shown.
Online monitoring and process control requires fast and noninvasive analytical methods, which are able to monitor the concentration of reactants in multicomponent mixtures with parts-per-million resolution. Online NMR spectros-copy can meet these demands when flow probes are directly coupled to reactors, since this method features a high linearity between absolute signal area and sample concentration, which makes it an absolute analytical com-parison method being independent on the matrix. Due to improved magnet design and field shimming strategies portable and robust instruments have been introduced to the market by several manufacturers during the last few years. First studies with this technology showed promising results to monitor chemical reaction in the laboratory.
The Collaborative Research Center InPROMPT aims to establish a novel process concept for the hydroformylation of long-chained olefins, using a rhodium complex as catalyst in the presence of syngas. Recently, the hydroformylation in micro-emulsions, which allows for the efficient recycling of the expensive rhodium catalyst, was found to be feasible. However, the temperature and concentration sensitive multi-phase system demands a continuous observation of the reaction to achieve an operational and economically feasible plant operation. For that purpose, we tested the potential of both NMR and Raman spectroscopy for process control assistance. The lab-scale experiments were supported by sampling for off-line GC-analysis as reference analytics. The results of the NMR experiments will be part of another contribution.
Hydroformylation represents an important homogeneous catalyzed process, which is widely used within chemical industry. Usually applied with simple alkenes like Propene and Butene aldehydes obtained from alkenes >C6 are relevant intermediates in production of plasticizers, surfactants and polymers. Today the active catalyst species is often based on valuable Rhodium complexes in aqueous solution. This implies the problem of limited water solubility of the reactands, which is acceptable for short chain lengths, but states a problem in case of higher alkenes. Along with that efficient separation and recycling of the catalyst becomes more complicated. There are different approaches tackling this problem, e.g., by using of salt formation in the BASF process or downstream distillation within the Shell process
Process monitoring of an intensified continuous production unit with compact NMR spectroscopy
(2016)
Monitoring chemical reactions is the key to chemical process control. Today, mainly optical online methods are applied. NMR spectroscopy has a high potential for direct loop process control. Compact NMR instruments based on permanent magnets are robust and relatively inexpensive analyzers, which feature advantages like low cost, low maintenance, ease of use, and cryogen-free operation. Instruments for online NMR measurements equipped with a flow-through cell, possessing a good signal-to-noise-ratio, sufficient robustness, and meeting the requirements for integration into industrial plants (i.e., explosion safety and fully automated data analysis) are cur-rently not available off the rack. Recently, promising benchtop NMR instruments with acceptable performance came to market and process integrated sensors developed on basis of such laboratory instruments are on their way.
The departure from the current automation landscape to next generation automation concepts for the process industry has already begun. Smart functions of sensors simplify their use and enable plug-and-play integration, even though they may appear to be more complex at first sight. Smart sensors enable concepts like self-diagnostics, self-calibration, and self-configuration/parameterization whenever our current automation landscape allows it. Here we summarize the currently discussed general requirements for process sensors 4.0 and introduce a smart online NMR sensor module as example, which was developed for an intensified industrial process funded by the EU’s Horizon 2020 research and innovation programme (www.consens-spire.eu).
Ugly Spectra and Lousy interfaces – Challenges for Compact NMR Spectroscopy in Process Control
(2016)
With the introduction of advanced process analytical technology, the closeness of key process variables to their limits can be directly controlled and the product can be classified or even released in real time.
Compact NMR instruments can make NMR spectroscopy accessible in industrial and harsh environments for process control.
In this contribution a Raman spectrometer based control structure for the heating of a desorption column is proposed. For this purpose calibration experiments for the absorption of carbon dioxide using monoethanolamine solutions are carried out and calibration models are developed to measure both carbon dioxide liquid loads and monoethanolamine mass fractions. The calibration experiments are supported by online NMR spectroscopy to accurately measure the appearance of all species in the electrolyte system. Both models are tested during the plant operation of a mini-plant for the oxidative coupling of methane and the proof of concept for the control structure is given. The Raman spectroscopy implemented in the ATEX conform mini-plant shows a reliable and robust performance being even indifferent to impurities hindering the GC analysis.
Medium resolution nuclear magnetic resonance spectroscopy (MR-NMR) currently develops to an important analytical tool for both quality control and process monitoring. One of the fundamental acceptance criteria for online MR-MNR spectroscopy is a robust data treatment and evaluation strategy with the potential for automation. The MR-NMR spectra were treated by an automated baseline and phase correction using the minimum entropy method. The evaluation strategies comprised direct integration, automated line fitting, indirect hard modeling, and partial least squares regression.
Currently research in chemical manufacturing moves towards flexible plug-and-play approaches focusing on modular plants, capable of producing small scales on-demand with short down-times between individual cam-paigns. This approach allows for efficient use of hardware, a faster optimization of the process conditions, and thus, an accelerated introduction of new products to the market. Driven mostly by the search for chemical syntheses under biocompatible conditions, so-called “click” chemistry rapidly became a growing field of research. The re-sulting simple one-pot reactions are so far only scarcely accompanied by an adequate optimization via compara-bly straightforward and robust analysis techniques. Here we report on a fast and reliable calibration-free online high field NMR monitoring approach for technical mixtures. It combines a versatile fluidic system, continuous-flow measurement with a time interval of 20 s per spectrum, and a robust, automated algo-rithm to interpret the ob-tained data. All spectra were acquired using a 500 MHz NMR spectrometer (Varian) with a dual band flow probe having a 1/16 inch polymer tubing working as a flow cell. Single scan 1H spectra were recorded with an acquisition time of 5 s, relaxation delay of 15 s.