The main gaseous products and the mass loss during the self-ignition of combustible materials
(2006)
Experiments were performed to investigate the self-ignition behaviour of accumulations of four different technical dusts at oxygen volume fractions ranging from 1.3 to 21%. For this purpose a laboratory oven used for hot storage testing was modified to allow flushing with the pre-mixed oxygen/nitrogen mixture of the desired composition. It was found that for all sample volumes investigated the self-ignition temperatures were higher the lower was the oxygen volume fraction. In addition, the type of reaction changed obviously, since the apparent activation energy significantly decreased at oxygen volume fractions below 6%. However, it was still possible to observe exothermic effects at oxygen volume fractions as low as 1.3%. A numerical model was established to simulate the process of self-ignition including the coupled heat and mass transfer within the dust accumulation using a finite element solver. The model consists of six balance equations for the heat transfer and the transport of five chemical species. It shows that the model reflects self-ignition in dust accumulations with satisfying accuracy, as long as the input data generated by preceding experiments are reliable.
Self-ignition of deposited combustibles is a possible reason for excessive fires occurring on deposits for recycling materials or on waste dumps. Two series of experiments were performed to assess the hazard of self-ignition: hot storage tests with different homogeneous mixtures of combustible material and inert material and tests with pockets of combustible material embedded in inert matter. In the first test series considerable exothermicity (ΔT>60K) was observed for mass fractions of combustible material as low as 2.5%. In the second series it could be shown that the heat transfer from a pocket of burning material through the inert matter can ignite a second pocket of combustible matter.
Based on the experimental data, numerical simulations were performed to predict self-ignition on real-scale waste deposits. For a deposit of specific size and shape, the influence of the ambient temperature on the occurrence of self-ignition has been investigated.