For reaction monitoring and process control using NMR instruments, in particular, after acquisition of the FID the data needs to be corrected in real-time for common effects using fast interfaces and automated methods. When it comes to NMR data evaluation under industrial process conditions, the shape of signals can change drastically due to nonlinear effects. Additionally, the multiplet structure becomes more dominant because of the comparably low-field strengths which results in overlapping of multiple signals. However, the structural and quantitative information is still present but needs to be extracted by applying predictive models.
We present a range of approaches for the automated spectra analysis moving from statistical approach, (i.e., Partial Least Squares Regression) to physically motivated spectral models (i.e., Indirect Hard Modeling). By using the benefits of traditional qNMR experiments data analysis models can meet the demands of the PAT community (Process Analytical Technology) regarding low calibration effort/calibration free methods, fast adaptions for new reactants, or derivatives and robust automation schemes.
Die Geräteentwicklungen im Bereich der Niederfeld-NMR-Spektroskopie im vergangenen Jahrzehnt ermöglichen den Einsatz kompakter, portabler Magnete mit geringen Streufeldern in Laborumgebungen und industriellen Produktionsanlagen. Somit werden neue Möglichkeiten für hochauflösende NMR-Experimente zur Reaktionsüberwachung eröffnet. Im Rahmen des EU-Projekts CONSENS wurden die Möglichkeiten dieser Methode umfassend anhand einer technisch bedeutenden Reaktion (elektrophile aromatische Substitutionsreaktionen) evaluiert.
Um die Flexibilität einer kontinuierlichen und modularen Pilotanlage durch Echtzeit- Qualitätskontrolle zu fördern, wurde ein vollständig automatisiertes Online- NMR-Modul entwickelt. Der Einsatz eines kommerziellen Niederfeld-NMR-Geräts im industriellen Umfeld wurde durch die entwickelten Lösungen der automatisierten Datenanlyse sowie durch ein zertifiziertes Sicherheitskonzept für den Betrieb in explosionsgefährdeten Zonen ermöglicht. Neben der Überwachung der Produktqualität wurden Online-NMR-Daten in einem neuen iterativen Optimierungsansatz zur Maximierung des Anlagenertrags eingesetzt und dienten als zuverlässige Referenz für die Kalibrierung eines Nahinfrarot-Spektrometers.
Für die Entwicklung einer robusten Datenauswertung der NMR-Spektren, die dem Anspruch der Flexibilität bei Produktwechseln genügt, wurden zunächst Versuche im Labormaßstab durchgeführt, um eine Datenbasis zu schaffen. In diesen Versuchen wurden die aromatischen Amine Anilin, p-Toluidin und p-Fluoranilin mit o-Fluornitrobenzol gekoppelt. Durch Zugabe einer Organolithium-Verbindung (Li- HMDS) findet ein Protonenaustausch zwischen dem primären Amin und Li-HMDS statt. Dies führt zu einer hohen Reaktionsenthalpie und instabilen Aryllithium-Verbindungen. Die Reaktionen wurden hinsichtlich anfallender Zwischenprodukte mittels Hochfeld-NMR-Spektroskopie analysiert.
Nachfolgend wurden die Reaktionen sowohl im Semi-Batch-Verfahren als auch im kontinuierlichen Laborbetrieb mit Online-Niederfeld-NMR-Spektroskopie und Online- Hochfeld-NMR-Spektroskopie untersucht. Da die gemessenen NMR-Spektren besonders im aromatischen Spektralbereich hohe Signalüberlappungen der Reaktanden aufweisen, wurden chemometrische Modelle entwickelt und anhand der Hochfeld-NMR-Methode validiert. Die verwendeten Durchflusszellen für die Niederfeld-NMR-Spektroskopie wurden hinsichtlich ihrer Anwendbarkeit für quantitative Messungen im kontinuierlichen Durchfluss untersucht. Es konnte gezeigt werden, dass Messungen mit einer additiv gefertigten Keramikdurchflusszelle prinzipiell möglich sind.
Monitoring chemical reactions is the key to chemical process control. Today, mainly
optical online methods are applied. NMR spectroscopy has a high potential for direct
loop process control. Compact NMR instruments based on permanent magnets
are robust and relatively inexpensive analysers, which feature advantages like low
cost, low maintenance, ease of use, and cryogen-free operation. Instruments for
online NMR measurements equipped with a flow-through cell, possessing a good
signal-to-noise-ratio, sufficient robustness, and meeting the requirements for
integration into industrial plants (i.e., explosion safety and fully automated data
analysis) are currently not available off the rack.
Intensified continuous processes are in focus of current research. Flexible (modular)
chemical plants can produce different products using the same equipment with short
down-times between campaigns and quick introduction of new products to the
market. In continuous flow processes online sensor data and tight closed-loop control
of the product quality are mandatory. If these are not available, there is a huge risk of
producing large amounts of out-of-spec (OOS) products. This is addressed in the
European Unionʼs Research Project CONSENS (Integrated Control and Sensing)
by development and integration of smart sensor modules for process monitoring and
control within such modular plant setups.
The presented NMR module is provided in an explosion proof housing of 57 x 57 x
85 cm module size and involves a compact 43.5 MHz NMR spectrometer together
with an acquisition unit and a programmable logic controller for automated data
preparation (phasing, baseline correction) and evaluation. Indirect Hard Modeling
(IHM) was selected for data analysis of the low-field NMR spectra. A set-up for
monitoring continuous reactions in a thermostated 1/8” tubular reactor using
automated syringe pumps was used to validate the IHM models by using high-field
NMR spectroscopy as analytical reference method.
Online low-field NMR spectroscopy of an industrial lithiation reaction step for process control
(2016)
Online monitoring and process control requires fast and noninvasive analytical methods, which are able to monitor the concentration of reactants in multicomponent mixtures with parts-per-million resolution. Online NMR spectroscopy can meet these demands when flow probes are directly coupled to reactors, since this method features a high linearity between absolute signal area and sample concentration, which makes it an absolute analytical comparison method being independent on the matrix. Due to improved magnet design and field shimming strategies portable and robust instruments have been introduced to the market by several manufacturers during the last few years. First studies with this technology showed promising results to monitor chemical reaction in the laboratory.
Within the project CONSENS, the continuous production of high-value products in small production scale is advanced by introducing benchtop NMR spectroscopy. CONSENS is a research and innovation project on integrated control and sensing for sustainable operation of flexible intensified processes.
This poster will present the first steps of the process integration of a benchtop NMR instrument for a lithiation process and outlines further fields of activity and potential challenges. Hereby, the following issues are going to be addressed: explosion-proof housing for the spectrometer, automation of signal processing (data pretreatment, evaluation and communication to the control system), flow cells and measuring conditions. Furthermore, first online spectra of the lithiation reaction in batch mode were acquired in lab scale. The reaction was performed in a 25 mL glass reactor with thermal jackets for temperature control of the reaction mixture. The Li-HMDS was dosed stepwise by using a glass syringe. First spectra in the proton and fluorine domain were recorded online using a flowrate of 3.5 mL min–1 and a simple 5 mm polytetrafluoroethylene tube (PTFE) as a flow cell.
Online monitoring and process control requires fast and noninvasive analytical methods, which are able to monitor the concentration of reactants in multicomponent mixtures with parts-per-million resolution. Online NMR spectros-copy can meet these demands when flow probes are directly coupled to reactors, since this method features a high linearity between absolute signal area and sample concentration, which makes it an absolute analytical com-parison method being independent on the matrix. Due to improved magnet design and field shimming strategies portable and robust instruments have been introduced to the market by several manufacturers during the last few years. First studies with this technology showed promising results to monitor chemical reaction in the laboratory.
Wthin the project CONSENS (www.consens-spire.eu), the continuous production of high-value products in small production scale is advanced by introducing benchtop NMR spectroscopy. CONSENS is a research and innovation project on inte-grated control and sensing for sustainable operation of flexible intensified processes.
This poster will present the first steps of the process integration of a benchtop NMR instrument for a lithiation process and outlines further fields of activity and potential challenges. Hereby, the following issues are going to be addressed: explosion-proof housing for the spectrometer, automation of signal processing (data pretreatment, evaluation and communication to the control system), flow cells and measuring conditions. Furthermore, first online spectra of the lithiation reaction in batch mode were acquired in lab scale. The reaction was performed in a 25 mL glass reactor with thermal jackets for temperature control of the reaction mixture. The Li-HMDS was dosed stepwise by using a glass syringe. First spectra in the proton and fluorine domain were recorded online using a flowrate of 3.5 mL min–1 and a simple 5 mm polytetrafluoroethylene tube (PTFE) as a flow cell.
Online monitoring and process control requires fast and noninvasive analytical methods, which are able to monitor the concentration of reactants in multicomponent mixtures with parts-per-million resolution. Online NMR spectroscopy can meet these demands when flow probes are directly coupled to reactors, since this method features a high linearity between absolute signal area and sample concentration, which makes it an absolute analytical comparison method being independent on the matrix. Due to improved magnet design and field shimming strategies portable and robust instruments have been introduced to the market by several manufacturers during the last few years. First studies with this technology showed promising results to monitor chemical reaction in the laboratory.
Within the project CONSENS, the continuous production of high-value products in small production scale is advanced by introducing MR-NMR spectroscopy. CONSENS is a research and innovation project on integrated control and sensing for sustainable operation of flexible intensified processes.
This poster will present the first steps of the process integration of a benchtop NMR instrument for a lithiation process and outlines further fields of activity and potential challenges. Hereby, the following issues are going to be addressed: explosion-proof housing for the spectrometer, automation of signal processing (data pretreatment, evaluation and communication to the control system), flow cells and measuring conditions. Additionally, the first results of the lithiation reaction in lab scale regarding the pure components and reaction mixtures are going to be discussed.
Online monitoring and process control requires fast and noninvasive analytical methods, which are able to monitor the concentration of reactants in multicomponent mixtures with parts-per-million resolution. Online NMR spectroscopy can meet these demands when flow probes are directly coupled to reactors, since this method features a high linearity between absolute signal area and sample concentration, which makes it an absolute analytical comparison method being independent on the matrix. Due to improved magnet design and field shimming strategies portable and robust instruments have been introduced to the market by several manufacturers during the last few years. First studies with this technology showed promising results to monitor chemical reaction in the laboratory.
Within the project CONSENS, the continuous production of high-value products in small production scale is advanced by introducing MR-NMR spectroscopy. CONSENS is a research and innovation project on integrated control and sensing for sustainable operation of flexible intensified processes.
This poster will present the first steps of the process integration of a benchtop NMR instrument for a lithiation process and outlines further fields of activity and potential challenges. Hereby, the following issues are going to be addressed: explosion-proof housing for the spectrometer, automation of signal processing (data pretreatment, evaluation and communication to the control system), flow cells and measuring conditions. Additionally, the first results of the lithiation reaction in lab scale regarding the pure components and reaction mixtures are going to be discussed.
Simple calibration concept of an online NMR module demonstrated in a modularised production plant
(2017)
Monitoring specific information (such as physico-chemical properties, chemical re-actions, etc.) is the key to chemical process control. Within the CONSENS Project, the challenge to adapt a commercially available benchtop NMR spectrometer to the full requirements of an automated chemical production environment was tack-led. The developed online NMR module was provided in an explosion proof housing and involves a compact 43.5 MHz NMR spectrometer together with an acquisition unit, a programmable logic controller for automated triggering, flow con-trol, as well as data communication.
First results of an aromatic coupling reaction in lab scale showed a general feasibil-ity according to the signal information in the acquired NMR spectra even though with a considerable overlap. Due to the comparatively low field strength of the NMR spectrometer multivariate methods had to be considered for the prediction of con-centration profiles based on spectral data. Typically, for industrial application of those methods, e.g. Partial Least Squares Regression (PLS-R) as well as Indirect Hard Modeling, large amount of calibration data is demanded, which must be ac-quired in time consuming lab-scale experiments and offline analytics. When it comes to changes in raw materials (e.g., varying functional groups, additional stabi-lizing agents) calibration experiments and data evaluation models are developed again. Here we present an approach of automated data analysis tools for low field NMR spectra with minimal calibration effort. The algorithms are based on Indirect Hard Modeling, whereby each component in each mixture spectra can be rep-resented by several flexible peak functions (pure component models). This means, that only pure component NMR spectra are needed to generate a first evaluation model. The flexibility of peak functions in the spectral model can be adjusted via constraints of peak parameters. The area of any pure component model can either be converted to concentrations based on a one-point calibration on raw material concentration or even neat solvent signals. In several cases it has been shown, the IHM works almost independently of the matrix of the real samples. Such a calibration can be repeated daily in the beginning of each process run with minimal time effort. Moreover, additional pure components can be added to the model or even substitut-ed while keeping the previously adjusted peak function constraints. The proposed method exhibited good agreement of resulting concentration data from low field NMR spectra, when compared to an online high field NMR spectrometer as refer-ence instrument.
Monitoring chemical reactions is the key to chemical process control. Today, mainly optical online methods are applied, which are calibration intensive. NMR spectroscopy has a high potential for direct loop process control while exhibiting short set-up times. Compact NMR instruments make NMR spectroscopy accessible in industrial and harsh environments for advanced process monitoring and control.
Within the European Union’s Research Project CONSENS (Integrated CONtrol and SENsing, www.consens-spire.eu) by development and integration of a smart NMR module for process monitoring was designed and delivers online spectra of various reactions. The presented NMR module is provided in an explosion proof housing of 57 x 57 x 85 cm module size and involves a compact spectrometer together with an acquisition unit and a programmable logic controller for automated data preparation (phasing, baseline correction), and evaluation.
For reaction monitoring and process control using NMR instruments after acquisition of the FID the data needs to be corrected in real-time for common effects using fast interfaces and automated methods.
When it comes to NMR data evaluation under industrial process conditions, the shape of signals can change drastically due to nonlinear effects. Additionally, the multiplet structure becomes more dominant because of the comparably low-field strengths which results in overlapping of multiple signals. However, the structural and quantitative information is still present but needs to be extracted by applying predictive models.
We present a range of approaches for the automated spectra analysis moving from statistical approach, (i.e., Partial Least Squares Regression) to physically motivated spectral models (i.e., Indirect Hard Modelling and Quantum Mechanical calculations). By using the benefits of traditional qNMR experiments data analysis models can meet the demands of the PAT community (Process Analytical Technology) regarding low calibration effort/calibration free methods, fast adaptions for new reactants, or derivatives and robust automation schemes.
Already Analyzing or Still Calibrating? - Demonstration of an online NMR analyzer in pilot scale
(2018)
The departure from the current automation landscape to next generation automation concepts for the process industry has already begun. Smart functions of sensors simplify their use and enable plug-and-play integration, even though they may appear to be more complex at first sight. Monitoring specific information (i.e., “chemical” such as physico-chemical properties, chemical reactions, etc.) is the key to “chemical” process control. Here we introduce our smart online NMR sensor module provided in an explosion proof housing as example.
Due to NMR spectroscopy as an “absolute analytical comparison method”, independent of the matrix, it runs with extremely short set-up times in combination with “modular” spectral models. Such models can simply be built upon pure component NMR spectra within a few hours (i.e., assignment of the NMR signals to the components) instead of tedious calibrations runs. We present a range of approaches for the automated spectra analysis moving from statistical approach, (i.e., Partial Least Squares Regression) to physically motivated spectral models (i.e., Indirect Hard Modelling and Quantum Mechanical calculations).
Based on concentration measurements of reagents and products by the NMR analyzer a continuous production and direct loop process control were successfully realized for several validation runs in a modular industrial pilot plant and compared to conventional analytical methods (HPLC, near infrared spectroscopy). The NMR analyser was developed for an intensified industrial process funded by the EU’s Horizon 2020 research and innovation programme (“Integrated CONtrol and SENsing”, www.consens-spire.eu).