Several fires involving external thermal insulating (ETIC) systems with polystyrene in Germany started an extensive discussion about fire safety of such systems. The Frankfurt fire service started to collect reports about real fire cases which involved ETICS with polystyrene two years ago. This collection shows that especially fires, which started in front of the buildings led to more severe fires of the facades than fires inside the buildings. In several fires the ignition sources were burning waste containers. Three of the real cases are discussed in more detail: a serious fire in Frankfurt on a building site and two fires of apartment buildings, which developed quite differently. Additionally the plastic waste containers, which started several fires are investigated regarding ignitability and heat release rates. The investigation shows that plastic waste containers are very effective as ignition source and that the usual placement directly in front of combustible facades can be a problem for fire safety. Moving these containers and unintentional contact with the facade can lead to damage of the facade coating. These damages were investigated qualitatively and quantitative on a wide collection of buildings. After classifying the damage intermediate scale tests were performed in a modified Single Burning Item (SBI) Test. The damage of the coating was varied as well as the power of the sand bed burner of the SBI apparatus. The damage significantly influenced the fire development on the specimen. In some tests the damaged rendering of the ETIC system collapsed and resulted in a sudden fire growth: after the collapse of the rendering the whole specimen was suddenly on fire. Several effects, which could be seen in the intermediate scale tests correspond to observations which were made in the real cases. As a consequence of the investigations challenges and possible measures to enhance fire safety of ETIC systems are discussed.
Gegenstand des Aufsatzes ist die experimentelle Untersuchung der Auswirkungen verschiedener Zündquellen sowie der Systembeschaffenheit auf das Brandverhalten EPS-basierter Wärmedämm-Verbundsysteme (WDVS). Dazu wurden Brände ausgewertet, die mit EPS-basierten WDVS in Verbindung stehen. Ergebnis dieser Auswertung war, dass nicht wie bisher angenommen der Brand in dem Gebäude (z. B. der Wohnungsbrand), sondern vielmehr der Brand außerhalb des Gebäudes, insbesondere der des Abfallbehälters, das häufigste und kritischste Brandszenario für EPS-basierte WDVS darstellt. Daraufhin wurden an der BAM Bundesanstalt für Materialforschung und -prüfung Brandversuche in der Single Burning Item-Prüfeinrichtung (SBI) an nicht intakten EPS-basierten WDVS-Ausschnitten durchgeführt. Mit zunehmender Beschädigungsgröße und -tiefe stieg die vom System freigesetzte Wärmefreisetzungsrate an. Zusätzlich werden Brandversuche eines Sockelbrandszenarios mit einer abfallbehälteräquivalenten Brandlast vorgestellt. Aus den Brandversuchen werden Empfehlungen zur Verbesserung der Systemsicherheit abgeleitet.-------------------------------------------------------------------------------------------------------------------------------------------------
The influence of different ignition sources and conditions of the systems on the fire behaviour of external thermal insulating systems (ETICS) have been investigated experimentally. As a basis of the investigations real cases with EPS based ETICS have been analysed. The analysis showed that the fire in front of the building is the most common and critical fire scenario for these systems. These fires are often caused by waste containers. This result contradicts the former common assumption that the fire inside the building is the most critical fire scenario for ETICS. Intermediate scale experiments in the Single Burning Item (SBI) test apparatus have been performed at BAM with ETICS specimens. The render of the systems was partially damaged. The measured heat release rate of the specimens increased significantly with size and depths of the damages. Additionally results of large scale experiments with a waste container equivalent ignition source are presented and recommendations to enhance fire safety of these systems are given.
Nach dem großen Baustellenbrand in Frankfurt 2012 hatte die Bauministerkonferenz (BMK) beschlossen, das Brandverhalten von Wärmedämmverbundsystemen [WDVS] hinsichtlich von Brandquellen vor der Fassade zu untersuchen. Die Feuerwehr Frankfurt hat eine Sammlung von Bränden, bei denen WDVS beteiligt waren, initiiert. Wertet man diese Sammlung hinsichtlich der Brandentstehung aus, fällt auf, dass von den insgesamt 57 Bränden 79 % (45 Brände) vor der Fassade begannen. 25 dieser 45 Brände wurden durch brennenden Müll oder Müllcontainer ausgelöst. Die meisten der gesammelten Brände (50) waren in den letzten fünf Jahren (2010 - 2014). Auf Grund dieser Erkenntnisse wurden an der BAM Müilcontainer (aus Plastik) hinsichtlich ihrer Entflammbarkeit und Wärmefreisetzung untersucht. Außerdem wurden im Auftrag der BMK Müllcontainer hinsichtlich ihrer Wärmefreisetzung und Brandentwicklung im Großversuch an der MFPA Leipzig untersucht. Mit Hilfe dieser Voruntersuchungen wurde eine Brandquelle identifiziert, die Zündquellen wie einen brennenden, Müllcontainer oder kleinere Ansammlungen von Sperrmüll repräsentiert: Es wurde eine 200 kg Holzkrippe gewählt, da die Holzkrippe bessere Ergebnisse hinsichtlich der Reproduzierbarkeit der Ergebnisse darstellt als z.B. ein Müllcontainer. Mit dieser Zündquelle wurden Großversuche an der MFPA Leipzig mit einem zugelassenen WDVS durchgeführt. Das WDVS zeigte unter diesen Prüfbedingungen ein nicht akzeptables Brandverhalten. Die folgenden zwei Versuche wurden mit Ertüchtigungsmaßnahmen durchgeführt, die eine signifikante Verbesserung des Brandverhaltens brachten. Zusätzlich wurde an der BAM eine Serie von Brandversuchen im Kieinmaßstab in der Single Burning Item (SBI) Prüfeinrichtung durchgeführt. Dabei wurde die auf das WDVS wirkende Wärmefreisetzungsrate variiert und der Einfluss von Grad und Größe von Beschädigungen der Putzschicht hinsichtlich des Brandverhaltens untersucht. Deutliche Unterschiede im Brandverhalten konnten sowohl quantitativ als auch qualitativ nachgewiesen werden. Neben der den Versuchsbedingungen zugrunde liegenden Wärmefreisetzungsrate konnten Art und Lage der Beschädigung in der Putzschicht als auch brandbeeinflussende Größen charakterisiert und beschrieben werden.