Purpose – The purpose of this paper is to investigate the performance of intumescent coating on tension rod systems and their components. Steel tension rod systems consist of tension rods, fork end connectors and associated intersection or gusset plates. In case of fire, beside the tension rods themselves, the connection parts require appropriate fire protection. Intumescent fire protection coatings prevent a rapid heating of the steel and help secure the structural load-carrying capacity. Because the connection components of tension rod systems feature surface curvature and a complex geometry, high demand is placed on the intumescence and thermal protection performance of the coatings.
Design/methodology/approach – In this paper, experimental studies were carried out for steel tension rod systems with intumescent coating. The examined aspects include the foaming and cracking behaviour, the influence of different dry film thicknesses, the heating rate of the steel connecting parts in comparison to the tension rods, and the mounting orientation of the tension rods together with their fork end connectors.
Findings – The results show that a decrease in surface curvature and/or an increase inmass concentration of the steel components leads to a lower heating rate of the steel. Moreover, the performance of the intumescent coating on tension rod systems is influenced by themounting orientation of the steel components.
Originality/value – The findings based on fire tests contribute to a better understanding of the intumescent coating performance on connection components of tension rod systems. This subject has not been extensively studied yet.
Intumescent fire protection coatings are used to improve the fire resistance of steel members. Due to slender cross-sections typically used for tension members, high demands are placed on the effectiveness and reliability of the intumescent coatings. This paper describes real-scale fire tests of intumescent coatings applied to steel tension members with circular solid and hollow sections. First, the current regulations for the application of intumescent coatings on steel tension members are discussed. After that, a comparison between the foaming behaviour and failure mechanisms of intumescent coatings applied to steel tension members with different cross-sections and loading conditions is given. Next, the experimental setup and procedure of the performed fire tests are presented. In addition, the influences of various parameters on the performance of the intumescent coating are analysed, including the geometry of the steel profile, dry film thickness of the intumescent coating, load utilisation level as well as the orientation of the member. Based on the theoretical considerations and results of the fire tests, it is evidenced that mechanically loaded fire tests are essential to assess accurately the contribution of intumescent fire protection coatings to the fire resistance of steel tension members with circular solid sections.