Intumescent coatings for fire protection offer advantages over (non-intumescent) cementitious coatings and boards regarding speed of construction, architectural aesthetics, sometimes costs, and other features. However, conventional organic intumescent coatings as well as soluble silicate (waterglass) coatings form foams with low mechanical stability, and the latter coatings generally suffer from low resistance against humidity. Therefore, the search for novel intumescent coatings for more demanding conditions (e.g., abrasive environments) is a necessity in the context of steadily increasing requirements of society and industry.
In this contribution, we present results on intumescent aluminosilicate coatings for fire protection that form foams with significantly increased mechanical strength. Two base formulations, a metakaolin/silica-based mix, adapted from Krivenko et al., and a silica/corundum-based mix, developed at Curtin University, as well as formulations modified with additives (Al(OH)3, Mg(OH)2, B2O3, Na2B4O7), were applied to steel plates (75 mm × 75 mm) and exposed to simulated fire conditions (fire curve according to ISO 834-1:1999). Temperature-time curves were recorded to assess the degree at which the coatings insulated the substrate. In addition, XRD, TG, oscillatory rheometry, and SEM were employed to characterise the coatings.
The coatings were observed to partly expand during hardening due to H2 formation. When the hardened coatings were exposed to elevated temperatures they intumesced as expected, with the degree and nature of expansion dependent on the formulation. Oscillatory rheometry provided insights into the intumescent processes in an apparently brittle material. It revealed that the hardened aluminosilicate coatings became viscous (loss factor > 1) at 75–225 °C, in the temperature range of major water release, as opposed to a “standard” metakaolin-based geopolymer, which continued to behave as a solid. This explains the intumes¬cent behavior of the coatings, i.e. further expansion and foam formation. Microstructural analysis confirmed pore expansion and coalescence; XRD showed that the phases formed after heating (max. temperature ~840 °C) were of ceramic-type.
The fire protection (defined here as the time for the steel substrate to reach the critical temperature of 500 °C) depended mainly on the thick¬ness of the fully expanded coating, i.e. after intumescence. An alumino¬silicate coating free of additives with an original thickness of 12 mm was able to protect the steel for >30 min. The addition of 10 % anhydrous borax (Na2B4O7) caused a significant improvement, such that an original coating thickness of only 6 mm was sufficient to protect the steel for ~30 min. This was caused by the formation of sodium metaborate dihydrate (NaB(OH)4) in the coating that led to a significantly extended dehydration plateau in the temperature-time curve at ~100 °C during the fire exposure.
The present study aims to investigate the use of geopolymer mortars as passive fire protection system for steel structures. Coal fly ashes were used as aluminosilicate source and perlite was employed as aggregate to obtain a lightweight system. In addition, a geopolymer mortar containing quartz aggregate was produced for comparison. The geopolymer mortars were applied on stainless steel plates and exposed to both, cellulosic and hydrocarbon standard fire curves, according to ISO 834-1 and EN 1363-2, respectively. Acoustic emission measurements were conducted to analyze cracking phenomena during the high temperature exposure. The resulting temperature-time curves showed that the investigated system is effective in retarding the temperature rise of the steel plates. When the cellulosic fire curve was applied, a 20 mm [0.79 in.] thick layer of lightweight geopolymer mortar protected the steel substrate from reaching the critical temperature of 500 °C [932 °F] for at least 30 minutes, avoiding the rapid decrease of its mechanical properties and thus representing an important safety measure against accidental fires. No spalling phenomena on heating were detected; however, significant cracking was observed on cooling.
Alkali-activated fly ashes have been proposed for various applications where resistance against high temperatures is required, yet several details regarding the response of these materials to heat-exposure need to be clarified. In the present study, heat-induced cracking in fly ash-based alkali-activated pastes and lightweight mortars was analyzed by in-situ acoustic emission (AE) detection during complete heating-cooling cycles (up to ∼1100 °C), augmented by thermogravimetry and ex-situ SEM and XRD analyses. The applicability of the lightweight mortars as passive fire protection coatings was assessed by recording temperature-time curves of mortar-coated steel plates. Cracking during heating was limited and associated exclusively with the dehydration of the materials in the temperature range ∼90–360 °C. However, samples heated to temperatures above ∼600 °C exhibited intense cracking on cooling. This was attributed to differential deformations caused by local sintering and partial melting at the glass transition temperature, and subsequent quenching on cooling.