Composition and Explosibility of Gas Emissions from Lithium-Ion Batteries Undergoing Thermal Runaway
(2023)
Lithium-based batteries have the potential to undergo thermal runaway (TR), during which mixtures of gases are released. The purpose of this study was to assess the explosibility of the gaseous emission from LIBs of an NMC-based cathode during thermal runaway. In the current project, a series of pouch lithium-based battery cells was exposed to abuse conditions (thermal) to study the total amount of gases released and the composition of the gas mixture. First, the battery cells were placed in a closed vessel, and the pressure and temperature rise inside the vessel were measured. In a second step, the composition of gases was analysed using a Fourier transform Infrared (FTIR) spectrometer.
We found that the amount of released gases was up to 102 ± 4 L, with a clear dependence on the battery capacity. This study showed that the concentration of gaseous emissions such as carbon monoxide (CO), methane (CH4), ethylene (C2H4), ethane (C2H6), and hydrogen cyanide (HCN) increased with higher cell capacity. Of the five studied flammable gases, the maximum concentrations of carbon monoxide (16.85 vol%), methane (7.6 vol%), and ethylene (7.86 vol%) were identified to be within their explosible range. Applying Le Chatelier’s law, a calculated lower explosion limit (LEL) of 7% in volume fraction was obtained for the gas mixture. The upper explosion limit (UEL) of the gas mixture was also found to be 31% in volume. A filter comprising pyrobubbles was used for the removal of the studied gas components released during the thermal abuse. The investigation revealed that the pyrobubbles filter was highly effect in the removal of HCN (up to 94% removal) and CO2 (up to 100% removal). Herein, we report the dependency of the method of thermal runaway trigger on the measured maximum temperature.
Es wird eine Methode zur sicherheitstechnischen Untersuchung von Mikroreaktoren und mikrostrukturierten Komponenten, die im Explosionsbereich betrieben werden sollen, vorgestellt. Mikrostrukturierte Reaktoren sind nicht inhärent sicher, wenngleich der Bereich der sicheren Betriebsbedingungen gegenüber konventionellen Reaktoren erweitert ist. Der Explosionsbereich kann durch die Mikrostrukturen eingeengt werden. Am Beispiel von Ethylen/Sauerstoff-Gemischen und Ethylen/N2O-Gemischen wird hinsichtlich der Ausbreitung von Detonationen durch Kapillarrohre gezeigt, dass die sogenannte λ/3-Regel angewandt werden kann. Darüber hinaus werden erste Ergebnisse der Untersuchung der Ausbreitung von Explosionen durch einen Mikroreaktor mit rechteckigem Strömungskanal vorgestellt.
International and European dangerous substances and dangerous goods regulations refer to the standard ISO 10156 (1996). This standard includes a test method and a calculation procedure for the determination of the flammability of gases and gas mixtures in air. The substance indices for the calculation, the so called Tci values, which characterise the fire potential, are provided as well. These ISO Tci values are derived from explosion diagrams of older literature sources which do not take into account the test method and the test apparatus. However, since the explosion limits are influenced by apparatus parameters, the Tci values and lower explosion limits, given by the ISO tables, are inconsistent with those measured according to the test method of the same standard. In consequence, applying the ISO Tci values can result in wrong classifications. In this paper internationally accepted explosion limit test methods were evaluated and Tci values were derived from explosion diagrams. Therefore, an open vessel method with flame propagation criterion was favoured. These values were compared with the Tci values listed in ISO 10156. In most cases, significant deviations were found. A detailed study about the influence of inert gases on flammability is the objective of Part 2.