Measurements of downburst wind loading acting on an overhead transmission line in northern Germany
(2017)
Along an overhead transmission line in Northern Germany, a unique instrumentation of anemometers and force measurements is installed. Details of this test line with wind measurements along a horizontal axis are given. A recent event of a presumable downburst wind event is analyzed by means of available data and precedent works on thunderstorm analysis. The measured response of the conductors at the suspension tower is investigated and compared with time domain simulation of a finite element model.
Measurements of downburst wind loading acting on an overhead transmission line in Northern Germany
(2017)
Along an overhead transmission line in Northern Germany, a unique instrumentation of anemometers and force measurements is installed. Details of this test line with wind measurements along a horizontal axis are given. A recent event of a presumable downburst wind event is analyzed by means of available data and precedent works on thunderstorm analysis. The measured response of the conductors at the suspension tower is investigated and compared with time domain simulation of a finite element model.
Windeinwirkungen auf Freileitungen wurden in der Vergangenheit meist an exponierten Standorten bestimmt. In einem Langzeitversuch wurden seit 2012 an einer mit moderner Messtechnik ausgerüsteten 380-kV-Leitung der 50 Hertz Transmission GmbH, die im nicht besonders exponierten Gelände verläuft und somit den Leitungen im Netz entspricht, die Windgeschwindigkeiten entlang der Leiter und deren Auswirkungen auf die Stützpunkte gemessen. Die Messungen und die begleitenden Auswertungen bestätigen die heute verwendeten normativen Vorgaben für die Windwirkung auf die Leiter von Freileitungen, soweit dies in der relativ kurzen Zeit von fünf Jahren möglich ist.
Aerodynamic damping is a decisive parameter influencing the dynamic response of overhead transmission line conductors. Methods of how to account for the effects of aerodynamic damping differ significantly and so might do the results. In this work, the source of aerodynamic damping being the result of the relative velocity between the structure and wind flow will be revised. Based on wind tunnel tests and validated by simulations, the differences of linear movement compared to a pendulum movement of a sagging cable are shown. The reasons for that Deviation are the large deflections, resulting in a movement non-parallel to the acting wind flow. For analysis in frequency domain, it is not possible to incorporate aerodynamic damping implicitly by fluid structure interaction. If the dynamic movement can be linearized at a working point of the mean deflection, a modification to the linear approach is suggested. This approach is validated by simulation with a finite element model of an existing overhead transmission line, calibrated with full scale measurements. Aerodynamic damping is incorporated in time step analysis by Rayleigh damping and modal damping. The differences between both approaches are emphasized and modal damping is shown to be the most adequate.
To cope with future requirements, the transfer capacities of distribution systems as well as of transmission systems in Europe need to be increased. Therefore repowering of existing overhead lines with high temperature low sag con-ductors (HTLS) can be one interesting possibility. Because of limited experiences with that technology, current re-search of TU Dresden, the Federal Institute for Materials Research and Testing (BAM) and 50Hertz Transmission GmbH investigates the ageing behaviour of several differ-ent HTLS technologies in a consortium with other Euro-pean partners. In this context, accelerated ageing tests of conductors and its corresponding fittings with combined mechanical and electrical loads are done. To evaluate the changes due to ageing, several mechanical tests of the con-ductors are carried out and the contact behaviour of the fittings is analysed.
Accelerated electrical and mechanical ageing tests of high temperature low sag (HTLS) conductors
(2017)
As part of the Best Paths project, work package 6 of the DEMO #4 combines the R&D tasks for repowering of transmission overhead line corridors. The aim of the presented research work is the electrical and mechanical investigation of high temperature low sag conductors (HTLS) and their respective accessories. In contrast to the conventional ACSR (aluminum conductor steel reinforced) conductors, new material combinations of HTLS technologies result in a better sagging behavior combined with an operation at higher temperatures. Because of missing operational experience, the ageing behavior of HTLS conductor technologies shall be analyzed regarding the operating parameters such as electrical, thermal and mechanical load.
In dieser Blockveranstaltung lernen die Studierenden die Grundlagen der stahlbaulichen Bemessung zum Thema Stabilität. Inhalt ist eine kurze Einführung in die Problematik des Stabilitätsversagens. Danach wird eingegangen auf die Grundlagen des Bemessungsverfahrens nach EC 3, gefolgt von einer Nachweisführung anhand eines Beispiels.
Vorschlag zur möglichen Lebensdauerverlängerung einzelner Bauteile einer im Betrieb befindlichen Offshore-Windenergieanlage durch Beschreibung der Versagenswahrscheinlichkeiten
Beschreibung der Versagenswahrscheinlichkeit durch geeignete Schädigungsmodelle
Aktualisierung der Versagenswahrscheinlichkeiten aufgrund von Inspektionsergebnissen und möglichen Reparaturen auf Basis der Bayes‘schen Entscheidungstheorie
Quantifizierte Bewertung von Inspektionsmethoden und Reparaturmaßnamen im Hinblick auf die Zuverlässigkeit der Bauteile
Grundlage für Entscheidungen für Inspektionen und Reparaturen
Die Beanspruchung von Freileitungen erfolgt hauptsächlich durch Naturlasten. Dabei spielt für die bemessungsbestimmenden Lastfälle häufig der Wind eine entscheidende Rolle. Die Leiter, die mehrere hundert Meter weit spannen, tragen einen wesentlichen Anteil zur Gesamtbeanspruchung von Tragmasten bei, die wiederum Eigengewicht und Windlasten der Leiter zwischen zwei Abspannmasten abtragen. Wenn die Reaktion der Seile auf Starkwindereignisse abgeschätzt werden soll, müssen sowohl geometrische Nichtlinearitäten durch die großen Verformungen wie auch aerodynamische Nichtlinearitäten berücksichtigt werden. Insbesondere für die Anwendung und Berücksichtigung in Bemessungsvorschriften werden hierfür Vereinfachungen vorgenommen. In diesem Beitrag wird eine umfassende Untersuchung vorgestellt, über Naturmessungen, FEM-Simulationen kombiniert mit Windkanalversuchen und generierten Windzeitreihen. Ziel ist es, existierende Bemessungsvorschriften im Hinblick auf die Abschätzung der Beanspruchung aus Wind auf Leiter zu validieren. Hierbei sind insbesondere die Turbulenzannahmen und das dynamische Verhalten von weitgespannten Leitern wichtig, um die Extremschnittgrößen zu beschreiben. Mithilfe von so genannten Spannweitenfaktoren sollen die relevanten Parameter, wie Spannweite und Windturbulenz, bei der Beanspruchungsabschätzung berücksichtigt werden.