The fire behaviour of carbon fibre (CF) reinforced polymers differs in comparison to polymers. Fibres behave often inert with respect to pyrolysis, they change the melt flow and dripping behaviour, the heat absorption and transfer, the amount and properties of the fire residue and so on. Flame and fire retardancy concepts are needed not only suitable for the different fire protection goals typical for each application, but also tailored for composites. This field is illuminated by examples taken from different projects carried out in the group of the author in the recent years. The examples target on different applications through achieving reduction in reaction to fire controlling the fire risks (flammability, heat release) in the beginning and development of a fire and investigating the fire stability, when a severe flame is directly applied (key property in fully developed fires). Approaches to halogen-free flame retardancy in CF reinforced thermosets are presented as well as building up a bench and an intermediate scale testing of composites in fire applying mechanical load (up to 1 MN compression) and direct flame exposure (180 kW/m2) simultaneously. Indeed, e.g. we have investigated the fire stability of stringer reinforced shell components taken out from the fuselage of an aircraft.
The understanding of fire behaviour, fire resistance, and fire retardant modes of action in composites is a promising basis for target-oriented development. The role of flame inhibition, charring, and protective layer formation is discussed. Successful concepts are presented for fire retardancy tailored for different application as well as general guidelines for future development. Different phosphorus flame retardants are proposed to achieve halogen-free flame retardancy with respect to ignition and developing fires. Different protective approaches are sketched for addressing the fire stability of composites that is the most important fire risk for the fire resistance in structural applications.
Intumescent coatings are used for decades to increase the fire resistance of steel or wood constructions. Intermediate and full scale tests are used to assess their protection performance. For the product development and screening, cheaper and faster bench-scale tests are demanded that provide information about thermal protection, foaming dynamics and mechanical resistance. In the recent years, we have developed several bench-scale fire resistance tests and used them in different research and developing projects. The influence of distinct binders and fillers, respectively, was studied in intumescent coatings using the Standard Time Temperature modified muffle furnace (STT Mufu+). This bench-scale test evaluates the fire resistance (by means of temperature measurements) and the foaming behaviour (by means of a high-temperature endoscope) during a standard time-temperature exposure. The fire residues were suitable for advance residue analysing techniques like nondestructive μ-computed tomography (μ-CT). Also, scanning electron microscopy was used to investigate the microscopic structure of the surface and inside of the residues. The mechanical resistance of the residues was tested by an impact resistance experiment.
The binder influence on the insulation of the coating was small for the investigated systems. Nevertheless, it was interestingly noted, that coatings with high expansion did not provide the best protection. The great influence of the binder material on the inner structure of the foamed residues was revealed by the μ-CT images. Clear differing morphologies were observed. These led to distinct mechanical resistance properties of the tested coatings. Also the change of a low amount of fillers, such as fibres and clay was investigated with similar effects. What is more, a transition of the residue from black, carbonaceous foam with closed cells into an inorganic, residual open cell sponge occurs at high temperatures during the test. This transition is due to the loss of carbon; the change in microstructure is analysed by scanning electron microscopy.
The bench-scale tool presented outreaches screening; the investigation based on the STT Mufu+ delivers a deeper understanding of the phenomena controlling the performance of intumescent coatings.
Intumescent coatings for fire protection offer advantages over (non-intumescent) cementitious coatings and boards regarding speed of construction, architectural aesthetics, sometimes costs, and other features. However, conventional organic intumescent coatings as well as soluble silicate (waterglass) coatings form foams with low mechanical stability, and the latter coatings generally suffer from low resistance against humidity. Therefore, the search for novel intumescent coatings for more demanding conditions (e.g., abrasive environments) is a necessity in the context of steadily increasing requirements of society and industry.
In this contribution, we present results on intumescent aluminosilicate coatings for fire protection that form foams with significantly increased mechanical strength. Two base formulations, a metakaolin/silica-based mix, adapted from Krivenko et al., and a silica/corundum-based mix, developed at Curtin University, as well as formulations modified with additives (Al(OH)3, Mg(OH)2, B2O3, Na2B4O7), were applied to steel plates (75 mm × 75 mm) and exposed to simulated fire conditions (fire curve according to ISO 834-1:1999). Temperature-time curves were recorded to assess the degree at which the coatings insulated the substrate. In addition, XRD, TG, oscillatory rheometry, and SEM were employed to characterise the coatings.
The coatings were observed to partly expand during hardening due to H2 formation. When the hardened coatings were exposed to elevated temperatures they intumesced as expected, with the degree and nature of expansion dependent on the formulation. Oscillatory rheometry provided insights into the intumescent processes in an apparently brittle material. It revealed that the hardened aluminosilicate coatings became viscous (loss factor > 1) at 75–225 °C, in the temperature range of major water release, as opposed to a “standard” metakaolin-based geopolymer, which continued to behave as a solid. This explains the intumes¬cent behavior of the coatings, i.e. further expansion and foam formation. Microstructural analysis confirmed pore expansion and coalescence; XRD showed that the phases formed after heating (max. temperature ~840 °C) were of ceramic-type.
The fire protection (defined here as the time for the steel substrate to reach the critical temperature of 500 °C) depended mainly on the thick¬ness of the fully expanded coating, i.e. after intumescence. An alumino¬silicate coating free of additives with an original thickness of 12 mm was able to protect the steel for >30 min. The addition of 10 % anhydrous borax (Na2B4O7) caused a significant improvement, such that an original coating thickness of only 6 mm was sufficient to protect the steel for ~30 min. This was caused by the formation of sodium metaborate dihydrate (NaB(OH)4) in the coating that led to a significantly extended dehydration plateau in the temperature-time curve at ~100 °C during the fire exposure.
Products and by-products of the invertebrate and vertebrate farming, respectively, are shown to be promising bio-based flame retardant adjuvants in epoxy thermosets. While the addition of bone meal results in the formation of an inorganic shield, protein-based powders from insects provide an intumescent behavior under forced flaming conditions. Combining the latter with a common flame retardant such as ethylene diamine phosphate, the charring efficiency and self-extinguishing properties can be further enhanced.