In this study, the test method EN 14825 for testing heat pumps is validated by verifying the sensitivity of the seasonal space heating energy efficiency ηs, (declared on the energy efficiency label) in relation to the nominal heating capacity Pdesign. Therefore, the two major parts of the test method, the measurement part and the calculation part, were investigated. The calculation part was subjected to a sensitivity analysis in order to identify the properties of a heat pump which have a strong influence on ηs. The analysis revealed that the energy consumption in special operating states, the duration in activemode and seasonal performance values in active-mode (SCOPon) significantly affect the sensitivity of ηs. Especially short operating times, in which the heat pump is in active-mode, lead to large changes in ηs with varying Pdesign. In addition, the range of power of Pdesign turned out to have an increasing Impact on ηs with decreasing Pdesign. For Pdesign values ≤10 kW, the sensitivity of ηs increases tremendously.
Especially the determination of the ηs for devices with short operating times in active-mode (1400 h) and low values for Pdesign (≤10 kW) cannot be reproduced anymore.
In this study, the test method EN 14825 for testing air conditioners is validated by verifying the sensitivity of the seasonal energy efficiency ratio SEER (declared on the energy efficiency label) in relation to the nominal cooling capacity Pdesign. Therefore, the two major parts of the test method, the measurement part and the calculation part, were investigated. Measurements were conducted on several single-split units. The calculation part was subjected to a sensitivity analysis in order to identify the properties of an air conditioner which have a strong influence on the SEER. The analysis revealed that the measurement procedure delivers reproducible results. However, the energy consumption in special operating states, the duration in active-mode and seasonal performance values in active mode (SEERon) significantly affect the sensitivity of the SEER. Especially assumption of short operating times for a cooling active mode leads to large changes in the SEER with varying Pdesign. In addition, the range of power of Pdesign turned out to have an increasing impact on the SEER with decreasing Pdesign. For Pdesign values ≤10 kW, which is the most popular type of ACs in the EU, the sensitivity of the SEER increases tremendously.
Especially the determination of the SEER for devices with short operating times in cooling active-mode (350 h) and low values for Pdesign (≤10 kW) cannot be reproduced anymore. In consequence, manufacturer could use the sensitivity of the SEER on Pdesign to artificially “increase” the energy efficiency of their air conditioner for the Energy label about 10 %.