From a fire safety point of view, the burning behavior of lithium-ion batteries is of high interest. The heat release rate (HRR) is the most important fire parameter to analyze the fire hazards of burning objects, so that an accurate determination of it is crucial. In this paper, two different measurement techniques, the Oxygen Consumption Calorimetry (OCC) and the Sensible Enthalpy Rise Approach (SERA) are simultaneously performed in the same calorimeter to measure the HRR of two different types of lithium-ion batteries. HRR values as well as total energies determined by SERA are higher than measured with OCC: The total energy released is about 10–12 times (SERA) and 6–9.5 times (OCC) the electrical stored energy for both battery types, whereas the timescales of the release differ strongly between the types, resulting in maximum HRRs of 3.4 MW (SERA) and 1.5 MW (OCC)
for one module of type A and 0.8 MW (SERA) and 0.6 (OCC) of type B respectively. Furthermore, a sensitive dependency of the HRR measurement with SERA on the position of the wall temperature measurement is observed.
Safety concerns on cable tray fires in urban utility tunnels, which may further trigger huge casualties, ceiling structure damages, power failures and other domino effects, attract increasing attention in recent years. Determining the maximum excess ceiling gas temperature (MECT) induced by cable tray fires in urban utility tunnels is crucial to evaluate the fire risks. A series of one-layer horizontal cable tray fire experiments to explore the MECT were carried out in a large-scale utility tunnel without mechanical ventilations. The number of cables on the tray was varied from 8 to 18 in the experiments. The experimental results showed that the cable tray fire burning could be divided into three distinct stages, including ignition, self-sustaining and decaying stages. In the self-sustaining combustion stage, the cable tray was found to burn relatively steady. The mean MECT was also investigated since it represents one of the main characteristics of the cable tray fire. By redefining two parameters (the heat release rate and the effective ceiling height) in three classical MECT models proposed originally based on pool-fire, these three models could be extended to be able to predict the mean MECT generated from the cable tray fire (solid combustible) within 20% deviations. Consequently, two novel models were respectively proposed to predict the mean MECT at the self-sustaining burning period and the instantaneous MECT of one-layer horizontal cable tray fire in utility tunnel, which would be useful in the field of fire protection engineering.
The standard cone calorimeter according to ASTM E 1354 and ISO 5660 enables reaction-to-fire tests to be performed in ambient atmospheric conditions. A controlled-atmosphere chamber modifies the standard apparatus in a way that allows tests to be performed in nonambient conditions as well. The enclosed chamber is placed underneath the standard exhaust hood and does not have a closed connection to the hood. With this open arrangement, the exhaust gases are diluted by excess air drawn in from the laboratory surroundings. Heat-induced changes in the consequential dilution ratio affect the calculation of fire quantities and, when neglected, lead to deviations of up to 30% in heat release rate. The paper introduces a test protocol and equations to calculate the heat release rate taking dilution effects into account. A mathematical correction is shown that compensates for the dilution effects while avoiding extensive mechanical changes in the equipment.
A controlled-atmosphere cone calorimeter that is built by modifying the Standard apparatus with the addition of a controlled-atmosphere chamber offers a time- and cost-saving approach for reaction-to-fire testing in vitiation- and ventilation-controlled atmospheres. Due to the design of the added enclosure no mechanical changes on cone calorimeter’s Standard ductwork are required. This offers some advantages but also important limitations. The design has an open connection between the outlet of the added enclosure and the cone calorimeter’s exhaust hood. Therefore, sufficient ambient air from the laboratory surroundings is drawn into the System to introduce effects which have the potential to affect test results significantly.
A procedure which is is suitable to consider physical effects of the ambient air on the calculation of the heat release rate is presented as well as initial results of an application towards toxic potency assessment. Signs for Chemical effects of the ambient air such as post reactions are shown but subject of an ongoing work.