Round robin tests of odour and VOC emissions from building products – What have we learned so far?
(2023)
Emission testing of volatile organic compounds (VOC) and odour from materials and products is commonly based on emission test chamber measurements. These measurements are often the basis of mandatory or voluntary labelling procedures. To ensure the comparability of results from different testing laboratories their performance must be verified. For this purpose, round robin tests (RRTs) are conducted. Bundesanstalt für Materialforschung und - prüfung (BAM) offers such a RRT every two years using well characterised test materials with defined VOC emissions. In addition to the VOC quantification, the evaluation of odour is also implemented in the round robin tests. At the beginning, only perceived intensity (PI) was tested but over the years also the acceptance evaluation was considered. In principle, the results of PI and acceptance evaluation are comparable. The advantage of PI is the lower number of panel members necessary for one evaluation.
VOC-emissions and their odours from building products and furnishings present indoors should not have an impact on personal well-being or health. Odours can be measured by applying the standard ISO 16000-28. Indoor air determination of odour emissions from building products using test chambers. One of the described procedures is the assessment of perceived intensity using a comparative scale by a group of panellists. In this paper, the perceived intensity sampling procedure and its evaluation method are investigated and shown to need improvement. New technical developments in the methodology used to increase the reproducibility of measurement results are discussed. Since odour tests are used for labelling, they have a major influence on the assessment of construction products, similar to the procedure of the German Committee for Health Evaluation of Building Products (AgBB). In the original ISO standard, the evaluation is typically performed using a sampling container separated from the emission chamber. For a better sample presentation, an adapter was developed to connect the emission test chamber to the evaluation funnel and thus enable an odour assessment which is comparable to a direct measurement. The investigations show that losses of odourous substances can be greatly reduced, which is very desirable when seeking to obtain reliable results in odour measurement. Another experimental series was carried out to reduce the measurement effort in the evaluation of perceived intensity. Application of the developed greater than or less than/equal to. query could be helpful here. The results show that the query mostly leads to the same result as the evaluation of the perceived intensity using the method according to the standard but is much easier to perform. Overall, the results can contribute to improving the acceptance of the evaluation of perceived intensity using ISO 16000-28 and to determining odours from building materials increasingly more precisely.
One criterion to evaluate the odour of a sample is perceived
intensity П which is evaluated with the aid of a comparative scale. The procedure is well accepted but also time consuming and extensive. The study should help simplify the testing procedure by asking the panel members to only indicate whether a sample is perceived as less to equally intense or of greater intensity in comparison to a given acetone concentration of 7 pi on the comparative scale. In Germany a value of 7 pi is required for products to be suitable for the indoor use. The results show that the simplified test is basically suitable.
The presentation gives a brief overview of the main goals, the used methods and the first results of the PMARS OdourSense project. In cooperation with the Moulay Ismaïl University in Meknès (Morocco), a multi-gas sensor system for odour nuisance monitoring in outdoor air and a method for testing/calibration of such devices are being developed in this project.
Emissions from building products can considerably impair the quality of indoor air. The AgBB scheme is employed to evaluate the emissions of volatile organic compounds (VOC) from building products. The hygienic evaluation according to the AgBB scheme requires product-specific measuring procedures.
These are available for a range of products. They have been validated in co-operation with several research and testing institutes and have been included in the criteria for awarding the Blue Angel ecolabel.
The evaluation is, however, stricter and generally has lower limits. VOC emissions and odours can cause health problems so testing using sensors is an important element in the evaluation of building products and has – for reasons of precaution – been set down in the AgBB scheme. The main goal of the project was to derive a method of evaluation using sensors and limits for awarding the Blue Angel and for the AgBB scheme. Based on the research conducted (see Chapter 5 Results and Discussion), perceived intensity and hedonics were suggested as a suitable Evaluation method. The derivation of limits for the evaluation using sensors on the 28th day was effected in the present study through the additional questioning of the test subjects on the reasonability of a sample.
For the Blue Angel, there could be different limits of perceived intensity and hedonics for each group of products. A preliminary suggestion for possible limits – for all product groups – is a perceived intensity of 7 pi (5 pi + 2 pi as confidence coefficient, Chapter 5.1.5) and -1 (0+/-0.8, rounded to -1) for the hedonic value.
In this study 50 construction products were tested in emission test chambers according to the requirements of the AgBB-scheme: 7 acrylic and 6 silicone sealants, 6 paste-like synthetic resin plasters, 13 wood based products, 4 adhesives, 5 lacquers, 6 wall paints and 3 further construction products. VOC and odour emissions were tested on the 1st, 3rd, 10th, and 28th day. In addition to the VOC-measurements, a test procedure was developed to evaluate odour emission of construction products.This test is planned to be implemented into the AgBB-Scheme. A direct evaluation by a sensory panel in the emission test chamber was not possible. So the odour samples were collected in 300- litre tedlar bags which were evaluated later. Odour intensity of the samples was compared with different acetone concentrations. Within this study an interlaboratory comparison was conducted using the newly developed odour test method. Additionally, VVOC emissions, detection of carcinogenic compounds, repeatability of emission test chamber tests, and other issues are presented. This project has shown that construction products can be evaluated in accordance with the AgBB scheme. A sensory evaluation is intended to be introduced in the AgBB scheme. A method for this evaluation is described in this study. The test procedure should be enhanced and validated for practical utilisation.