- nein (2)
A systematic approach was used to investigate the weathering-induced degradation of a common water–based intumescent coating. In this study, the coatings are intended for humid indoor applications on steel substrates. The coating contains ammonium polyphosphate, pentaerythritol, melamine, and polyvinyl acetate. By replacing each ingredient with a less water-soluble substance, the most vulnerable substances, polyvinyl acetate and pentaerythritol, were identified. Furthermore, the weathering resistance of the system was improved by exchanging the ingredients. The coatings were stressed by artificial weathering tests and evaluated by fire tests. Thermogravimetry and Fourier-transform infrared spectroscopy were used to study the thermal decomposition. This study lays the foundation for the development of a new generation of water-based intumescent coatings.
Products and by-products of the invertebrate and vertebrate farming, respectively, are shown to be promising bio-based flame retardant adjuvants in epoxy thermosets. While the addition of bone meal results in the formation of an inorganic shield, protein-based powders from insects provide an intumescent behavior under forced flaming conditions. Combining the latter with a common flame retardant such as ethylene diamine phosphate, the charring efficiency and self-extinguishing properties can be further enhanced.
Intumescent coatings for fire protection offer advantages over (non-intumescent) cementitious coatings and boards regarding speed of construction, architectural aesthetics, sometimes costs, and other features. However, conventional organic intumescent coatings as well as soluble silicate (waterglass) coatings form foams with low mechanical stability, and the latter coatings generally suffer from low resistance against humidity. Therefore, the search for novel intumescent coatings for more demanding conditions (e.g., abrasive environments) is a necessity in the context of steadily increasing requirements of society and industry.
In this contribution, we present results on intumescent aluminosilicate coatings for fire protection that form foams with significantly increased mechanical strength. Two base formulations, a metakaolin/silica-based mix, adapted from Krivenko et al., and a silica/corundum-based mix, developed at Curtin University, as well as formulations modified with additives (Al(OH)3, Mg(OH)2, B2O3, Na2B4O7), were applied to steel plates (75 mm × 75 mm) and exposed to simulated fire conditions (fire curve according to ISO 834-1:1999). Temperature-time curves were recorded to assess the degree at which the coatings insulated the substrate. In addition, XRD, TG, oscillatory rheometry, and SEM were employed to characterise the coatings.
The coatings were observed to partly expand during hardening due to H2 formation. When the hardened coatings were exposed to elevated temperatures they intumesced as expected, with the degree and nature of expansion dependent on the formulation. Oscillatory rheometry provided insights into the intumescent processes in an apparently brittle material. It revealed that the hardened aluminosilicate coatings became viscous (loss factor > 1) at 75–225 °C, in the temperature range of major water release, as opposed to a “standard” metakaolin-based geopolymer, which continued to behave as a solid. This explains the intumes¬cent behavior of the coatings, i.e. further expansion and foam formation. Microstructural analysis confirmed pore expansion and coalescence; XRD showed that the phases formed after heating (max. temperature ~840 °C) were of ceramic-type.
The fire protection (defined here as the time for the steel substrate to reach the critical temperature of 500 °C) depended mainly on the thick¬ness of the fully expanded coating, i.e. after intumescence. An alumino¬silicate coating free of additives with an original thickness of 12 mm was able to protect the steel for >30 min. The addition of 10 % anhydrous borax (Na2B4O7) caused a significant improvement, such that an original coating thickness of only 6 mm was sufficient to protect the steel for ~30 min. This was caused by the formation of sodium metaborate dihydrate (NaB(OH)4) in the coating that led to a significantly extended dehydration plateau in the temperature-time curve at ~100 °C during the fire exposure.
Nowadays there are intumescent coatings available for diverse applications. There is no established assessment of their protection performance besides the standard time-temperature curve, but natural fire scenarios often play an important role. A reliable straightforward performance-based assessment is presented. The effective thermal conductivity per thickness is calculated based on intermediate-scale fire tests. The optimum thermal insulation, the time to reach it, and the time until contingent failure of the coating are used for an assessment independent of the heating curve. The procedure was conducted on four different commercially intumescent coatings for steel construction, one solvent-based, one waterborne, one epoxy-based, and a bandage impregnated with a waterborne coating. The performance was studied under four different but similar shaped heating curves with different maximum temperatures (standard time-temperature curve, hydrocarbon curve and two self-designed curves with reduced temperature). The thermal protection performance is crucially affected by the residue morphology. Therefore, a comprehensive morphology analysis, including micro-computed tomography and scanning electron microscopy, was conducted on small-scale residues (7.5 x 7.5 cm2). Two different types of inner structures and the residue surface after different heat exposures were discussed in terms of their influence on thermal protection performance.
FR additives were incorporated during tanning process. The mode of action of an intumescent system and each component individually, was methodically investigated in a semi-finished leather. Vertical flammability test results showed that the investigated semi-finished leather satisfies the regulations of the Federal Aviation Administration; in addition, afterglow time is strong minimized and forced fire behavior pointed out an important reduction on smoke production.