In the industry there is a lack of data on the Minimum Ignition Temperature of decomposition of tetrafluoroethylene in industrial sized equipment. In order to determine the Minimum Ignition Temperature of Decomposition of tetrafluoroethylene in large scale vessels, a facility was designed and constructed. Tests were carried out in a cylindrical reactor with a volume of 100 dm³ with initial pressures of 5 and 10 bar(a). In agreement with previous experiments with small scale cylindrical vessels, the Minimum Ignition Temperature of Decomposition of tetrafluoroethylene was observed to decrease with the initial pressure. The current paper describes the test setup and summarizes the experimental results achieved. The effect of the reactor adjustment (vertical or horizontal) is discussed. Moreover, simplified equations from the Semenov thermal explosion theory are used to attempt extrapolations of previous and current data on the Minimum Ignition Temperature of Decomposition of tetrafluoroethylene to other initial pressures and vessel volumes.
Fast growing softwood species such as pine are preferred for biomass-based heat as well as electricity production and stored in large quantities. A newly established outdoor pile of freshly cut pine-wood chips was monitored to analyze exothermic processes. Inside the pile, a mean temperature increase of up to 44 °C was measured after six days of piling which was paralleled by a decrease of O2-concentration and an increase of CO2-concentration. Thereafter four additional CO2 maxima were observed, while O2-concentration remained at ambient concentration. The fungal community structure remained almost unchanged after four weeks, while the bacterial community structure was characterized by continuous shifts over time. The rapid heating in the early stage of storage corresponded to high relative abundance of microbial strains belonging to the genera Pseudomonas, Luteibacter and Caulobacter, ascomycetous genera Sphaeropsis and Cadophora and basidiomycetous order Polyporales and genus Sistotremastrum. The late stage was composed by a broader diversity of microorganisms, and heating processes inside the wood pile were attributed mainly to physicochemical processes. Taken together, these observations suggest that the early bacterial and fungal communities are key players in exothermic processes and were replaced by a broader diversity of highly adapted microorganisms.
The exothermic reactions of thermally unstable materials have been studied using self-heating methods in a wire-mesh-reactor as well as temperature-programmed methods utilizing a differential scanning calorimeter (DSC). Samples of lignite coal dust, cork dust, detergent powder and riboflavin (vitamin B2) were investigated. The overall activation energy E could be determined for each method. For lignite coal and cork dust all techniques show very nice agreement in E. For the detergent powder, the values are comparable except for the heat-release (HR) rate method value which is about 5060 kJ/mol higher. Riboflavin on the other hand shows a different behaviour. The DSC-experiments lead to values being significantly higher compared to the self-heating values. The existing differences are clearly worked out.
There is a lack of data on the self-ignition behaviour of tetrafluoroethylene (TFE) in industrial sized
equipment. In order to assess the tendency of TFE for
decomposition in large scale vessels, , a facility was
designed and constructed. Tests were
carried out in a cylindrical reactor with a volume of 100 L with initial
pressures of 5 and 10 bar(a). The effect of the reacto
r adjustment (vertical or horizontal) was taken into
account. The current work describes the test set
up and summarizes the experimental results achieved.
Furthermore, this paper reports on a numerical model for
the prediction of the self
-heating of TFE in closed
vessels, which was previously developed for small scale reactors and has been here validated for larger
dimensions with the experiments performed in the new facility.
Miscanthus x Giganteus (Miscanthus) energy crop was examined at laboratory scale to assess its self-heating and self-ignition risks during storage. Chipped Miscanthus (18 mm) from February and March harvests, in 2012, were assessed as well as ground Miscanthus (3 mm) from the March harvest. February and March crops had moisture contents of 41.6 and 20.2%, respectively. Self-ignition temperatures were independent of moisture although moisture did affect the time from the beginning of storage until storage temperature was reached. Ground Miscanthus had lower self-ignition temperatures than chipped Miscanthus. Isothermal respirometric tests carried out showed increase risk of self-heating in the February crop compared to the March crop due to increased microbial activity. Numerical simulations were used to determine critical enhanced start temperatures, e.g. caused by microbial decomposition, of the stored Miscanthus. Safe storage conditions have been derived from the investigations. The numerical simulations demonstrated that self-ignition was possible in Miscanthus chip piles with a height greater than 6 m if there was significant heat release from microbiological activity. Reliable assessment of self-heating and self-ignition risks in large scale Miscanthus energy crop clamps or piles are required to prevent losses due to decomposition and fire damage.
Miscanthus x giganteus energy crop grown in Ireland was harvested on 21st of February and 28th of March 2012 to examine the effects of harvesting time on self-heating during storage of Miscanthus chips in clamps (98 m³) under weather sheltered conditions. There was a relatively large difference in moisture content, of 21.4%, between Miscanthus crop harvested in February and March (41.6 and 20.2%, respectively). Temperature evolution over a storage period of up to 125 days was monitored at different heights and distances from the centre within the clamps. Maximum temperature in the February constructed clamp reached 69 °C compared to 28 °C in the March constructed clamp. Microbial activity was monitored via carbon dioxide and oxygen gas measurements. The high moisture clamp showed higher microbial activity and a volume yield loss of 4.3% due to decomposition in the top section of the clamp. Quality indices post-storage were also assessed. Calorific values from Miscanthus sampled 1 m below the top surface were similar after storage for both February and March constructed clamps, i.e. 18.52 and 18.70 MJ kg-1, respectively. A reliable assessment of self-heating in Miscanthus chip clamps has important consequences for both self-ignition risk and biomass quality.