There are several standardized ignition sources in use for the determination of explosion characteristics of gases, vapors and dusts. In the standards the ignition source is stated, but they vary in stating other characteristics like burning duration, energy or burning volume. Since heat is not visible under normal circumstances a Schlieren-Technique was used to make the full heating volume and not just the flames visible.
While an earlier paper of the authors focused on the ignition energy and burning duration of four standardized ignition sources, this paper focuses on the initial igniting volume, the ratio between initial igniting volume and the test-vessel size and other phenomena that were observed with the Schlieren-Technique-.
For the determination of safety characteristics of gases, vapors and dusts different types of ignition sources are used in international standards and guidelines. The paper presents test results of a comparative calorimetric and visual study between four different types of ignition sources. The ignition procedures were analyzed visually with a high-speed camera and electric recordings. In addition to that, the influence of the electrode-orientation, -distance as well as ignition energy on the reproducibility of the exploding wire igniter was tested.
The exploding wire is already in use for standardized determination of safety characteristics of gases, first tests on the suitability of the exploding wire igniter for dust testing have been carried out but are not standardized yet. Using the exploding wire, the ignition energy can be varied from 2 J to 10 000 J (2 x 5000 J) and thus it could be used for gases, vapors, dusts and hybrid mixtures. Moreover it can be used at high initial pressures and it is the only ignition source with an easily measurable ignition energy release. Furthermore, it does not introduce another chemical reaction into the system.
Finally, a proposal for a standard ignition source for explosion tests on hybrid mixtures is derived from the test results.
For the determination of safety characteristics of gases, vapors and dusts different types of ignition sources are used in international standards and guidelines. Table 1 compares technical relevant ignition sources with their main features. The paper presents test results of a comparative calorimetric and visual study between four different types of ignition sources. The ignition procedures were analyzed visually with a high-speed camera and electric recordings. In addition to that, the influence of the electrode-orientation, -distance as well as ignition energy on the reproducibility of the exploding wire igniter was tested.
The exploding wire is already in use for standardized determination of safety characteristics of gases, first tests on the suitability of the exploding wire igniter for dust testing have been carried out by Scheid et al. Using the exploding wire, the ignition energy can be varied from 2 to 10 000 J (2 x 5 000 J) and thus it could be used for gases, vapors, dusts and hybrid mixtures. Moreover it can be used at high initial pressures and it is the only ignition source with an easily measurable ignition energy release. Furthermore, it does not introduce another chemical reaction into the system.
Finally, a proposal for a standard ignition source for explosion tests on hybrid mixtures is derived from the test results.
There are several standardized ignition sources in use for the determination of explosion characteristics of gases, vapors and dusts. In the standards the ignition source is stated, but they vary in stating other characteristics like burning duration, energy or burning volume. Since heat is not visible under normal circumstances a Schlieren-Technique was used to make the full heating volume and not just the flames visible. While an earlier paper of the authors focused on the ignition energy and burning duration of four standardized ignition sources, this paper focuses on the initial igniting volume, the ratio between initial igniting volume and the test-vessel size and other phenomena that were observed with the Schlieren-Technique.
For the determination of safety characteristics of gases, vapors and dusts different types of ignition sources are used in international standards and guidelines. Table 1 compares technical relevant ignition sources with their main features. The paper presents test results of a comparative calorimetric and visual study between four different types of ignition sources. The ignition procedures were analyzed visually with a high-speed camera and electric recordings. In addition to that, the influence of the electrode-orientation, -distance as well as ignition energy on the reproducibility of the exploding wire igniter was tested.
The exploding wire is already in use for standardized determination of safety characteristics of gases, first tests on the suitability of the exploding wire igniter for dust testing have been carried out by Scheid et al. Using the exploding wire, the ignition energy can be varied from 2 to 10 000 J (2 x 5 000 J) and thus it could be used for gases, vapors, dusts and hybrid mixtures. Moreover it can be used at high initial pressures and it is the only ignition source with an easily measurable ignition energy release. Furthermore, it does not introduce another chemical reaction into the system.
Finally, a proposal for a standard ignition source for explosion tests on hybrid mixtures is derived from the test results.
According to international standards several safety characteristics of dusts are determined in the 20-L sphere (also known as SIWEK-Chamber). Dust cloud ignition is carried out using pyrotechnical igniters. Due to various disadvantages of pyrotechnical igniters the need for alternative ignition sources arises again and again. An alternative ignition source could be the so-called 'exploding wire' or 'fuse wire'. The paper presents test results of a comparative study between both ignition sources for the determination of the safety characteristics Maximum Explosion Pressure and Maximum Rate of Explosion Pressure Rise of selected dusts in the 20-L sphere. In addition the propagation of flame and electrical arc was analysed by high speed camera recordings. Tests in a windowed autoclave were performed to get information on the influence of turbulence during ignition on the shape of the generated flame (electrical arc) and its propagation. Turbulence measurements with a LDA system in the windowed autoclave as well as in the 20-L sphere allowed investigation if the ignition sources led to an additional turbulence increase at the moment of ignition in comparison to tests without ignition.
Validation of the new ignition source 'exploding wire' for dust explosion testing in the 20-L-sphere
(2014)
The safety characteristics Maximum Explosion Pressure pniB, Maximum Explosion Pressure Rise (dp/dt)™* and Lower Explosion Limit LEL are determined in closed vessels such as the 20-L-sphere according to international Standards. Dust ignition is carried out using pyrotechnical igniters which are defined in the Standards. Due to various disadvantages of pyrotechnical igniters the need for alternative ignition sources arises again and again. Studies at the Federal Institute for Material Research and Testing (BAM) with ignition units which were able to generate ignition energies up to 2000 J showed that the so-called “exploding wire” or “fuse wire“ is suitable as an alternative ignition source. The paper presents further test results for the Validation of the exploding wire for the determination of Pm» and (dp/dt)mx in the 20-L-sphere. The tests were performed with a new ignition unit and improved electrodes which allowed ignition energies up to 10000 J. The paper also analyses propagation of flame and electrical arc on basis of high speed camera recordings. Turbulence measurements with a LDA System in the 20-L-sphere allowed investigation whether the activation of the ignition sources has an influence on the turbulence field generated during dust dispersion and whether the influence differs depending on the ignition source.
Cylinder valves for oxygen service that meet the standard DIN EN ISO 10297 should be safe, if properly handled by the user. In the last few years, however, the number of incidents with oxygen valves that has been reported to Federal Institute for Materials Research and Testing (BAM) has increased. According to the incident reports, incorrect handling can be ruled out. People were seriously injured and in most cases, the causes of these incidents were not clear. Very often, such incidents occurred during opening and closing of the valves. Therefore, the technical-scientific community has put the existing test methods for type testing more and more into question. Besides other mandatory tests, the above-mentioned standard allows to perform the endurance test with air or with nitrogen. This is appropriate for all other gases but not for oxygen. Up to now, this test does not consider the fact that cylinder valves also contain nonmetallic seat materials and lubricants that may react with oxygen in a dangerous way. Because of this unsatisfactory situation, BAM initiated a research project to perform endurance testing of cylinder valves for oxygen service much more practice related with oxygen. This test simulates very well real life situations when the cylinder valve is opened or closed. The first part of this project was the development of a new oxygen operated endurance tester in accordance with DIN EN ISO 10297. In a second part, endurance testing of valves with air and with oxygen was performed and the results were compared. In addition, another mandatory test of the standard, the oxygen pressure surge test was carried out on new valves and on valves that had undergone endurance tests with air or oxygen, to see the influence on the burn-out safety of such pre-stressed valves. This paper presents the main results of the project. The findings clearly speak for implementing the oxygen endurance test not only to DIN EN ISO 10297 but also to various other standards to increase the burn-out safety of oxygen cylinder valves.
Mechanisch erzeugte Schlagfunken stellen in explosionsgefährdeten Bereichen eine potentielle Zündquelle dar. Eine Vielzahl von mechanischen und reaktionskinetischen Einflüssen verursacht dabei eine komplexe Interaktion von Parametern, von deren Auswirkung auf die Zündwahrscheinlichkeit bislang wenig bekannt ist. Die statistisch erfassten Eigenschaften von Schlagfunken in dieser Untersuchung lassen auf stochastische Prozesse schließen, bei denen die Anzahl der durch einen Schlagprozess abgetrennten Partikel und deren Oxidationsverhalten sowie die Höhe der kinetischen Schlagenergie entscheidenden Einfluss auf die Zündwahrscheinlichkeit hat.
Statistisch belastbar konnte in Ergänzung zum BAM Forschungsbericht 279 durch empirische Untersuchungen erstmals die Zündwahrscheinlichkeit von mechanisch erzeugten Stahl-Schlagfunken mit der Werkstoffpaarung unlegierter Stahl/unlegierten Stahl von W = 3 Nm bis 277 Nm ermittelt werden. Ferner wurde die Zündfähigkeit von durch energiereiche Schlagvorgänge (≥ 190 Nm) abgetrennten nicht oxidierten Partikeln erhöhter Temperatur in überstöchiometrischen Gemischen nachgewiesen. Während eine eindeutige Korrelation von Schlagenergie und Zündwahrscheinlichkeit sowie eine Korrelation von Schlagenergie und Anzahl abgetrennter Partikel festgestellt wurden, lieferte die Untersuchung in Hinblick auf die gemessenen einzelnen Parameter (wie z. B. Anzahl, Größe, Geschwindigkeit, mögliche Oxidation und Oxidationszeit und –verhalten der Partikel im Zusammenhang zur Schlagenergie und zur Zündwahrscheinlichkeit) kein eindeutiges Ergebnis. Auch eine Hauptkomponentenanalyse (PCA), die die Interaktion der einzelnen Parameter berücksichtigt, konnte keine spezifische Kombination messbarer Eigenschaften der Partikel finden, die mit einer deutlichen Erhöhung der Zündwahrscheinlichkeit korreliert.