Eingeladener Vortrag
- nein (2)
The use of renewable energy technologies, such as photovoltaics (PV) should be sustainable and environmentally compatible and therefore protect the environment from risks and damaging impacts. Regarding the growing number of installed photovoltaic systems, the end-of-life management of the pv-modules will become increasingly important. Thin film panels contain hazardous substances that may harm the environment if they are not recycled or disposed properly after reaching the end of their service life. Heavy metals, for example, can be toxic as well as carcinogenic or teratogenic. Processing methods for the recycling of PV thin film modules have to take these facts into account. Currently the available recycling techniques usually utilise chemicals such as acids for a wet-chemical treatment of end-of-life modules. The aim of RESOLVED was to identify and test alternative methods for a wet-mechanical treatment in order to reduce the consumption of chemicals in the recycling of thin film modules. Furthermore, the recovered Cadmium-Telluride (CdTe) and Copper-Indium-Diselenide/Disulfide (CIS) should be helping to save scare resources especially for limited elements such as tellurium and indium. The project RESOLVED investigated the recovery of semiconductors material as secondary raw material and the decontamination of the residues of the PV thin film modules. These goals were achieved by testing and optimising existing technologies for the recycling process as well as for the enrichment of the semiconductor materials. The target is to re-use the enriched recovered material in the production of new PV modules. Special efforts were made to look into life cycle analysis, process sustainability, economical aspects, and resource availability.
Remote sensing of hazardous substances is a key task that can be achieved with the help of remotely operated platforms equipped with specific sensors. A huge variety of methods and used vehicles have been developed for different purposes in recent years. The term smart dust refers to a science fiction novel and develop shortly after into a research proposal at UC Berkley funded by DARPA. Subsequently, the topic gained attraction but was overall considered as to complex for the technologies available at that time. In the launched passive smart dust project, we shift to a simple “chemical intelligent” passive sensor particle on the ground combined a read-out active sensor attached to an Unmanned Aerial Vehicle (UAV). The reactive particle surface can be preadjusted in the lab for exact desired properties regarding certain reactions to hazardous substances.
Moreover, the aimed interaction with the active sensor can be modified. Planed applications allow for different materials e.g., for short time measurement, being ecologically degradable, or weather stable for long time monitoring.
Synchrotron radiation X-ray fluorescence spectroscopy, in conjunction with atomic absorption and Raman spectroscopy, was used to analyze a set of top brand tattoo inks to investigate the presence of toxic elements and hazardous substances. The Cr, Cu, and Pb contents were found to be above the maximum allowed levels established by the Council of Europe through the resolution ResAP(2008)1 on requirements and criteria for the safety of tattoos and permanent makeup. Raman analysis has revealed the presence of a set of prohibited substances mentioned in ResAP(2008)1, among which are the pigments Blue 15, Green 7, and Violet 23. Other pigments that were identified in white, black, red, and yellow inks are the Pigment White 6, Carbon Black, Pigment Red 8, and a diazo yellow, respectively. The present results show the importance of regulating tattoo ink composition.
Safety experts, carriers or traders must be able to rely on the validity of the method and on correct results of safety tests and assessments in the laboratory.
Bundesanstalt für Materialforschung und –prüfung (BAM), Berlin and Physikalisch-Technischen Bundesanstalt (PTB), Braunschweig have extensive experience in the field of testing and assessment of physical hazards of chemicals.
Interlaboratory tests on different test methods have been performed by BAM and PTB during the last 10 years. Significant differences between the results of the participating laboratories were observed in all interlaboratory test. The deviations of the test results were not caused only by laboratory faults but also by deficiencies of the test method; i.e. many of the method descriptions are too ambiguous and allow divergences for interpretation.
Therefore, it is necessary to know exactly how good the method is that is used to classify dangerous goods or hazardous substances or to determine safety-relevant parameters. A key criterion is the measurement uncertainty.
One can choose simple methods with large error limits, but the measurement uncer-tainties should be known and always communicated together with the test results. This would allow safety specialists to be able to assess test results correctly and make well-founded decisions, e.g. for adequate protective measures.
Interlaboratory tests play a decisive role in assessing the reliability of test results. Participation in interlaboratory tests is not only a crucial element of the quality as-surance of laboratories; as such it is explicitly recommended in DIN EN ISO/IEC 17025. In addition, interlaboratory tests are also used to develop and validate test methods and can be used for the determination of the measurement uncertainty.
Therefore, the BAM and PTB continue to support the further development of the interlaboratory test programme of CEQAT-DGHS (Centre for quality assurance for testing of dangerous goods and hazardous substances, www.ceqat-dghs.bam.de), established in 2007. This programme is run by BAM in collaboration with the PTB and the QuoData Gesellschaft für Qualitätsmanagement und Statistik mbH, Dresden.
A new interlaboratory test for methods validation on the test method UN Test N.5 "Test method for substances which in contact with water emit flammable gases” is currently being prepared and will be carried out in 2018. Laboratories that specialise in this test are invited to participate in the interlaboratory test. Interested laboratories can check the details and register to participate in the interlaboratory test at the CEQAT-DGHS website.
Laboratory test results are of vital importance for correctly classifying and labelling chemicals as “hazardous” as defined in the UN Globally Harmonized System (GHS) / EC CLP Regulation or as “dangerous goods” as defined in the UN Recommendations on the Transport of Dangerous Goods. Interlaboratory tests play a decisive role in assessing the reliability of laboratory test results. Interlaboratory tests performed over the last 10 years have examined different laboratory test methods. After analysing the results of these interlaboratory tests, the following conclusions can be drawn:
1. There is a need for improvement and validation for all laboratory test methods examined.
2. To avoid any discrepancy concerning the classification and labelling of chemicals, the use of validated laboratory test methods should be state of the art, with the results accompanied by the measurement uncertainty and (if applicable) the probability of incorrect classification.
This paper addresses the probability of correct/incorrect classification (for example, as dangerous goods) on the basis of the measurement deviation obtained from interlaboratory tests performed by the Centre for quality assurance for testing of dangerous goods and hazardous substances (CEQAT-DGHS) to validate laboratory test methods. This paper outlines typical results (e.g. so-called “Shark profiles” – the probability of incorrect classification as a function of the true value estimated from interlaboratory test data) as well as general conclusions and steps to be taken to guarantee that laboratory test results are fit for purpose and of high quality.
Laboratory test results are of vital importance for correctly classifying and labelling chemicals as “hazardous” as defined in the UN Globally Harmonized System (GHS) / EC CLP Regulation or as “dangerous goods” as defined in the UN Recommendations on the Transport of Dangerous Goods. Interlaboratory tests play a decisive role in assessing the reliability of laboratory test results. Interlaboratory tests performed over the last 10 years have examined different laboratory test methods. After analysing the results of these interlaboratory tests, the following conclusions can be drawn:
1. There is a need for improvement and validation for all laboratory test methods examined.
2. To avoid any discrepancy concerning the classification and labelling of chemicals, the use of validated laboratory test methods should be state of the art, with the results accompanied by the measurement uncertainty and (if applicable) the probability of incorrect classification.
This paper addresses the probability of correct/incorrect classification (for example, as dangerous goods) on the basis of the measurement deviation obtained from interlaboratory tests performed by the Centre for quality assurance for testing of dangerous goods and hazardous substances (CEQAT-DGHS) to validate laboratory test methods. This paper outlines typical results (e.g. so-called “Shark profiles” – the probability of incorrect classification as a function of the true value estimated from interlaboratory test data) as well as general conclusions and steps to be taken to guarantee that laboratory test results are fit for purpose and of high quality.
CEQAT-DGHS Interlaboratory Test Programme for Chemical Safety - Need of Test Methods Validation
(2019)
Safety experts, manufacturers, suppliers, importers, employers or consumers must be able to rely on the validity of safety-related test methods and on correct test results and assessments in the laboratory. Via the eChemPortal lots of data from the REACH registration dossiers are available. However, the quality and correctness of the information remains in the responsibility of the data submitter. Unfortunately, we found more or less appropriate information on physicochemical properties and concluded that more quality or adequacy of any data submitted will be needed.
Interlaboratory tests play a decisive role in assessing the reliability of test results. Interlaboratory tests on different test methods have been performed by Bundesanstalt für Materialforschung und –prüfung (BAM) and Physikalisch-Technische Bundesanstalt (PTB) in collaboration with the QuoData GmbH during the last 10 years. Significant differences between the results of the participating laboratories were observed in all interlaboratory tests. The deviations of the test results were not caused only by laboratory faults but also by deficiencies of the test method.
In view of the interlaboratory test results the following conclusions can be drawn:
• To avoid any discrepancy on classification and labelling of chemicals it should become state of the art to use validated test methods and the results accompanied by the measurement uncertainty.
• A need for improvement is demonstrated for all examined test methods. Thus, interlaboratory tests shall initially aim at the development, improvement and validation of the test methods and not on proficiency tests.
• The laboratory management and the practical execution of the tests need to be improved in many laboratories.
• The term "experience of the examiner" must be seen critically: A "long experience with many tests" is not necessarily a guarantee for correct results.
Safety experts, carriers or traders must be able to rely on the validity of the method and on correct results of safety tests and assessments in the laboratory.
Bundesanstalt für Materialforschung und –prüfung (BAM), Berlin and Physikalisch-Technischen Bundesanstalt (PTB), Braunschweig have extensive experience in the field of testing and assessment of physical hazards of chemicals.
Interlaboratory tests on different test methods have been performed by BAM and PTB during the last 10 years. Significant differences between the results of the participating laboratories were observed in all interlaboratory test. The deviations of the test results were not caused only by laboratory faults but also by deficiencies of the test method; i.e. many of the method descriptions are too ambiguous and allow divergences for interpretation.
Therefore, it is necessary to know exactly how good the method is that is used to classify dangerous goods or hazardous substances or to determine safety-relevant parameters. A key criterion is the measurement uncertainty.
One can choose simple methods with large error limits, but the measurement uncertainties should be known and always communicated together with the test results. This would allow safety specialists to be able to assess test results correctly and make well-founded decisions, e.g. for adequate protective measures.
Interlaboratory tests play a decisive role in assessing the reliability of test results. Participation in interlaboratory tests is not only a crucial element of the quality assurance of laboratories; as such it is explicitly recommended in DIN EN ISO/IEC 17025. In addition, interlaboratory tests are also used to develop and validate test methods and can be used for the determination of the measurement uncertainty.
Therefore, the BAM and PTB continue to support the further development of the interlaboratory test programme of CEQAT-DGHS (Centre for quality assurance for testing of dangerous goods and hazardous substances, www.ceqat-dghs.bam.de), established in 2007. This programme is run by BAM in collaboration with the PTB and the QuoData Gesellschaft für Qualitätsmanagement und Statistik mbH, Dresden.
A new interlaboratory test for methods validation on the test method UN Test N.5 "Test method for substances which in contact with water emit flammable gases” is currently being prepared and will be carried out in 2018. Laboratories that specialise in this test are invited to participate in the interlaboratory test. Interested laboratories can check the details and register to participate in the interlaboratory test at the CEQAT-DGHS website.
CEQAT-DGHS Interlaboratory tests for method validation and measurement uncertainty determination
(2019)
An explosion in a chemical plant or a fire on a dangerous goods vessel - the reason for such accidents can be numerous. Prevention starts in the laboratory where chemicals are tested for their hazardous properties in order to be able to assess the risks involved in their handling. For this purpose, test methods have been developed and published. They are applied globally nowadays. Safety experts, manufacturers, suppliers, importers, employers or consumers must be able to rely on the validity of safety-related test methods and on correct test results and assessments in the laboratory.
Interlaboratory tests play a decisive role in assessing the reliability of test results. Participation in interlaboratory tests is not only a crucial element of the quality assurance of laboratories; as such it is explicitly recommended in DIN EN ISO/IEC 17025. In addition, interlaboratory tests are also used to develop and validate test methods and can be used for the determination of the measurement uncertainty.
Interlaboratory tests on different test methods have been performed by Bundesanstalt für Materialforschung und –prüfung (BAM) and Physikalisch-Technische Bundesanstalt (PTB) in collaboration with the QuoData GmbH during the last 10 years. Significant differences between the results of the participating laboratories were observed in all interlaboratory tests. The deviations of the test results were not caused only by laboratory faults but also by deficiencies of the test method (see interlaboratory test reports of the CEQAT-DGHS Centre for quality assurance for testing of dangerous goods and hazardous substances: www.ceqat-dghs.bam.de).
In view of the interlaboratory test results the following conclusions can be drawn:
• To avoid any discrepancy on classification and labelling of chemicals it should become state of the art to use validated test methods and the results accompanied by the measurement uncertainty.
• A need for improvement is demonstrated for all examined test methods. Thus, interlaboratory tests shall initially aim at the development, improvement and validation of the test methods (including the determination of the measurement uncertainty) and not on proficiency tests.
• The laboratory management and the practical execution of the tests need to be improved in many laboratories.
• The term "experience of the examiner" must be seen critically: A "long experience with many tests" is not necessarily a guarantee for correct results.
For the classification, safe handling and use of the chemicals, special standardized testing procedures have been developed and are used worldwide. Safety experts must be able to fully rely on the precise execution of the respective laboratory tests and assessments. In this context, interlaboratory tests are a crucial element of a laboratory's quality system. Participation in interlaboratory tests is explicitly recommended by the standard ISO/IEC 17025.
The present document reports the results of the interlaboratory test 2015-2016, which was performed on the test method DIN EN 15188:2007 “Determination of the spontaneous ignition behaviour of dust accumulations”. It was organized by BAM in the frame of the co-operation project CEQAT-DGHS Centre for Quality Assurance for Testing of Dangerous Goods and Hazardous Substances.
The test method DIN EN 15188:2007 is applied to characterize the self-ignition behaviour of combustible dusts. The experimental basis for describing the self-ignition behaviour of a given dust is the determination of the self-ignition temperatures (TSI) of differently-sized volumes of the dust sample by isoperibolic hot storage experiments (storage at constant oven temperatures) in commercially available ovens. The results measured this way reflect the dependence of the self-ignition temperatures on the volume of a dust accumulation.
The interlaboratory test 2015-2016 on the method DIN EN 15188:2007 is the latest in a systematic stepwise built up series of method validation interlaboratory tests and internal laboratory investigations. The aim of this interlaboratory test was to determine measurement uncertainties of the modified method DIN EN 15188 for different substances, covering a sufficiently wide range of self-ignition behaviours in the scope of the DIN EN 15188 of the four basket test to extrapolate to storage volumes up to 1000 m³ and the single basket test for a basket volume of 1000 cm³.
The precision of the four basket test and the single basket of the modified method DIN EN 15188 can be assessed as acceptable for the four sample materials investigated in the current interlaboratory test 2015-2016. It was possible to derive a functional equation for the measurement uncertainty U depending on the storage volume V. The measurement uncertainty cannot be ignored and must be considered, if TSI results should be used in practice.