Quick Seasonal Performance Testing for Heat Pumps
- To determine the seasonal performance of heat pumps for energy labelling this study proposes a two-point-method that could conceivably be an alternative to the European standard EN 14825 and similar test standards such as ISO 13256. Heat pumps were tested in line with the EN 14825. The reduction of measurement points, from between five to seven (EN 14825) to only two (two-point-method), leads to 60 % savings in cost and time. It is shown that the shortened method can be used to determine the seasonal energy efficiency of heat pumps with the same degree of precision compared to EN 14825.
Autor*innen: | Carsten Palkowski, Anne Simo |
---|---|
Dokumenttyp: | Beitrag zu einem Tagungsband |
Veröffentlichungsform: | Graue Literatur |
Sprache: | Deutsch |
Titel des übergeordneten Werkes (Deutsch): | ECEEE Summer Study 2019 Proceedings |
Jahr der Erstveröffentlichung: | 2019 |
Organisationseinheit der BAM: | S Qualitätsinfrastruktur |
S Qualitätsinfrastruktur / S.3 Ökodesign und Energieverbrauchskennzeichnung | |
Erste Seite: | 1547 |
Letzte Seite: | 1552 |
DDC-Klassifikation: | Technik, Medizin, angewandte Wissenschaften / Ingenieurwissenschaften / Angewandte Physik |
Freie Schlagwörter: | Coefficient of performance; Energy label; Heat pump; Screening; Testing |
Themenfelder/Aktivitätsfelder der BAM: | Energie |
Veranstaltung: | ECEEE Summer Study 2019 |
Veranstaltungsort: | Hyerès, France |
Beginndatum der Veranstaltung: | 03.06.2019 |
Enddatum der Veranstaltung: | 08.06.2019 |
Verfügbarkeit des Dokuments: | Datei im Netzwerk der BAM verfügbar ("Closed Access") |
Datum der Freischaltung: | 24.06.2019 |
Referierte Publikation: | Nein |