Experimental investigation on an energy-efficient floor heating system with intelligent control: A case study in Chengdu, China

  • The space heating system accounts for 20%~50% of building energy consumption, and may lead to energy waste due to unreasonable controls. In this study, an energy-efficient floor heating system with intelligent control was proposed to improve energy efficiency of the system. In order to validate the concept of the proposed intelligent control, an experimental system was designed and constructed in Chengdu, China. Temperature, control cycle and energy consumption were then studied under different control strategies. The result shows that a larger flow rate of supply water will result in a longer control cycle and a lower control frequency, i.e., the average control cycle at 7 L min−1 is 1.7 h during the test day, while it is 1.5 h at 5 L min−1. Moreover, adopting water with a higher temperature and flow rate could achieve a higher efficiency of the system. The energy consumptions in case 1 (5 L min−1, 50 °C), case 2 (5 L min−1, 55 °C), case 5 (7 L min−1, 55 °C) and case 6 (7 L min−1, 60The space heating system accounts for 20%~50% of building energy consumption, and may lead to energy waste due to unreasonable controls. In this study, an energy-efficient floor heating system with intelligent control was proposed to improve energy efficiency of the system. In order to validate the concept of the proposed intelligent control, an experimental system was designed and constructed in Chengdu, China. Temperature, control cycle and energy consumption were then studied under different control strategies. The result shows that a larger flow rate of supply water will result in a longer control cycle and a lower control frequency, i.e., the average control cycle at 7 L min−1 is 1.7 h during the test day, while it is 1.5 h at 5 L min−1. Moreover, adopting water with a higher temperature and flow rate could achieve a higher efficiency of the system. The energy consumptions in case 1 (5 L min−1, 50 °C), case 2 (5 L min−1, 55 °C), case 5 (7 L min−1, 55 °C) and case 6 (7 L min−1, 60 °C) are 4746 kJ, 3534 kJ, 3093 kJ and 3028 kJ, respectively. Based on the experimental data, the supply water temperature is suggested to set lower than 60 °C considering human comfort.zeige mehrzeige weniger

Metadaten exportieren

Weitere Dienste

Teilen auf Twitter Suche bei Google Scholar Anzahl der Zugriffe auf dieses Dokument
Metadaten
Autor*innen:C. Jiang, G. Xie, Dejian WuORCiD, T. Yan, S. Chen, P. Zhao, Z. Wu, W. Li
Dokumenttyp:Zeitschriftenartikel
Veröffentlichungsform:Verlagsliteratur
Sprache:Englisch
Titel des übergeordneten Werkes (Englisch):Case Studies in Thermal Engineering
Jahr der Erstveröffentlichung:2021
Organisationseinheit der BAM:2 Prozess- und Anlagensicherheit
2 Prozess- und Anlagensicherheit / 2.1 Sicherheit von Energieträgern
Veröffentlichende Institution:Bundesanstalt für Materialforschung und -prüfung (BAM)
Verlag:Elsevier Ltd.
Jahrgang/Band:26
Aufsatznummer:101094
Erste Seite:1
Letzte Seite:14
DDC-Klassifikation:Technik, Medizin, angewandte Wissenschaften / Ingenieurwissenschaften / Angewandte Physik
Freie Schlagwörter:Control strategy; Energy consumption; Experimental; Floor heating; Intelligent control
Themenfelder/Aktivitätsfelder der BAM:Energie
DOI:10.1016/j.csite.2021.101094
URN:urn:nbn:de:kobv:b43-550522
ISSN:2214-157X
Verfügbarkeit des Dokuments:Datei für die Öffentlichkeit verfügbar ("Open Access")
Lizenz (Deutsch):License LogoCreative Commons - CC BY-NC-ND - Namensnennung - Nicht kommerziell - Keine Bearbeitungen 4.0 International
Datum der Freischaltung:20.06.2022
Referierte Publikation:Ja
Datum der Eintragung als referierte Publikation:20.06.2022
Schriftenreihen ohne Nummerierung:Wissenschaftliche Artikel der BAM
Einverstanden