Power-to-Gas: Safety characteristics of hydrogen/natural-gas-mixtures
- LEL, UEL LOC, MESG, pmax and (dp/dt)max of hydrogen/natural gas-mixtures were determined systematically according to international standards. Mixtures of natural gas and hydrogen mainly become more „critical“ with increasing hydrogen fraction. The effect of up to 10 Vol% H2–admixture to natural gas on safety characteristics is very low, no major adaption of existing measures for explosion protection is necessary. More substantial adjustment of measures for explosion protection is necessary at hydrogen fractions of more than 25 Vol%. Some of the safety characteristics can be estimated with good accuracy by calculation methods.
Autor*innen: | Enis AskarORCiD |
---|---|
Koautor*innen: | Volkmar Schröder, A. Seemann, S. Schütz |
Dokumenttyp: | Vortrag |
Veröffentlichungsform: | Präsentation |
Sprache: | Englisch |
Jahr der Erstveröffentlichung: | 2016 |
DDC-Klassifikation: | Technik, Medizin, angewandte Wissenschaften / Ingenieurwissenschaften / Angewandte Physik |
Freie Schlagwörter: | energy storage; explosion protection; hydrogen enriched natural gas; hydrogen safety; methane/hydrogen-mixtures |
Veranstaltung: | 15th International Symposium on Loss Prevention and Safety Promotion in the Process Industries |
Veranstaltungsort: | Freiburg, Germany |
Beginndatum der Veranstaltung: | 05.06.2016 |
Enddatum der Veranstaltung: | 08.06.2016 |
Verfügbarkeit des Dokuments: | Datei im Netzwerk der BAM verfügbar ("Closed Access") |
Datum der Freischaltung: | 30.06.2016 |
Referierte Publikation: | Nein |
Eingeladener Vortrag: | Nein |