TY - CONF A1 - Lüth, Peter A1 - Frost, K. A1 - Kurth, Lutz A1 - Malow, Marcus A1 - Michael-Schulz, Heike A1 - Schmidt, Martin A1 - Uhlig, S. A1 - Zakel, S. T1 - CEQAT-DGHS Interlaboratory tests for method validation and measurement uncertainty determination N2 - An explosion in a chemical plant or a fire on a dangerous goods vessel - the reason for such accidents can be numerous. Prevention starts in the laboratory where chemicals are tested for their hazardous properties in order to be able to assess the risks involved in their handling. For this purpose, test methods have been developed and published. They are applied globally nowadays. Safety experts, manufacturers, suppliers, importers, employers or consumers must be able to rely on the validity of safety-related test methods and on correct test results and assessments in the laboratory. Interlaboratory tests play a decisive role in assessing the reliability of test results. Participation in interlaboratory tests is not only a crucial element of the quality assurance of laboratories; as such it is explicitly recommended in DIN EN ISO/IEC 17025. In addition, interlaboratory tests are also used to develop and validate test methods and can be used for the determination of the measurement uncertainty. Interlaboratory tests on different test methods have been performed by Bundesanstalt für Materialforschung und –prüfung (BAM) and Physikalisch-Technische Bundesanstalt (PTB) in collaboration with the QuoData GmbH during the last 10 years. Significant differences between the results of the participating laboratories were observed in all interlaboratory tests. The deviations of the test results were not caused only by laboratory faults but also by deficiencies of the test method (see interlaboratory test reports of the CEQAT-DGHS Centre for quality assurance for testing of dangerous goods and hazardous substances: www.ceqat-dghs.bam.de). In view of the interlaboratory test results the following conclusions can be drawn: • To avoid any discrepancy on classification and labelling of chemicals it should become state of the art to use validated test methods and the results accompanied by the measurement uncertainty. • A need for improvement is demonstrated for all examined test methods. Thus, interlaboratory tests shall initially aim at the development, improvement and validation of the test methods (including the determination of the measurement uncertainty) and not on proficiency tests. • The laboratory management and the practical execution of the tests need to be improved in many laboratories. • The term "experience of the examiner" must be seen critically: A "long experience with many tests" is not necessarily a guarantee for correct results. T2 - Eurachem International Workshop Uncertainty from sampling and analysis for accredited laboratories CY - Berlin, Germany DA - 19.11.2019 KW - Gefahrgut KW - Gefahrstoff KW - Ringversuch KW - Prüfmethode KW - Validierung KW - Qualitätssicherung KW - Messunsicherheit KW - Dangerous goods KW - Hazardous substances KW - Interlaboratory comparison KW - Quality assurance KW - Round robin test KW - Test method KW - Validation KW - Measurement uncertainty PY - 2019 UR - https://www.eurachem.org/index.php/events/completed/277-wks-mu2019#posters AN - OPUS4-49832 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Lüth, Peter A1 - Brandes, E. A1 - Frost, K. A1 - Kurth, Lutz A1 - Malow, Marcus A1 - Schmidt, Martin A1 - Michael-Schulz, Heike A1 - Uhlig, S. T1 - CEQAT-DGHS Interlaboratory test programme for chemical safety - status and activities N2 - Safety experts, carriers or traders must be able to rely on the validity of the method and on correct results of safety tests and assessments in the laboratory. Bundesanstalt für Materialforschung und –prüfung (BAM), Berlin and Physikalisch-Technischen Bundesanstalt (PTB), Braunschweig have extensive experience in the field of testing and assessment of physical hazards of chemicals. Interlaboratory tests on different test methods have been performed by BAM and PTB during the last 10 years. Significant differences between the results of the participating laboratories were observed in all interlaboratory test. The deviations of the test results were not caused only by laboratory faults but also by deficiencies of the test method; i.e. many of the method descriptions are too ambiguous and allow divergences for interpretation. Therefore, it is necessary to know exactly how good the method is that is used to classify dangerous goods or hazardous substances or to determine safety-relevant parameters. A key criterion is the measurement uncertainty. One can choose simple methods with large error limits, but the measurement uncertainties should be known and always communicated together with the test results. This would allow safety specialists to be able to assess test results correctly and make well-founded decisions, e.g. for adequate protective measures. Interlaboratory tests play a decisive role in assessing the reliability of test results. Participation in interlaboratory tests is not only a crucial element of the quality assurance of laboratories; as such it is explicitly recommended in DIN EN ISO/IEC 17025. In addition, interlaboratory tests are also used to develop and validate test methods and can be used for the determination of the measurement uncertainty. Therefore, the BAM and PTB continue to support the further development of the interlaboratory test programme of CEQAT-DGHS (Centre for quality assurance for testing of dangerous goods and hazardous substances, www.ceqat-dghs.bam.de), established in 2007. This programme is run by BAM in collaboration with the PTB and the QuoData Gesellschaft für Qualitätsmanagement und Statistik mbH, Dresden. A new interlaboratory test for methods validation on the test method UN Test N.5 "Test method for substances which in contact with water emit flammable gases” is currently being prepared and will be carried out in 2018. Laboratories that specialise in this test are invited to participate in the interlaboratory test. Interested laboratories can check the details and register to participate in the interlaboratory test at the CEQAT-DGHS website. T2 - MEETINGS OF IGUS EOS GROUP CY - Shanghai, P. R. China DA - 09.04.2018 KW - Dangerous goods KW - Hazardous substances KW - Test methods validation KW - Quality assurance PY - 2018 AN - OPUS4-44858 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER -