TY - JOUR A1 - Schiaroli, Alice A1 - Mata, Christian A1 - Scarponi, Giordano Emrys A1 - Habib, Abdel Karim A1 - Kluge, Martin A1 - Ustolin, Federico A1 - Cozzani, Valerio T1 - Digital image processing for the advanced characterization and simulation of experimental fire tests N2 - The fire engulfment of storage tanks of hazardous materials is among the most critical scenarios in hazard assessment of industrial value chains. Laboratory and full-scale experimental trials are used to test the tank performance and integrity in such scenarios. However, strong uncertainties usually affect the actual fire load experienced by the tank, in particular when large-scale experiments are carried out in open test fields. Such uncertainties arise from several factors difficult to control during experimental tests, such as the atmospheric conditions as there is the influence of wind drifts influencing the actual fire engulfment, the flame temperature and the flame dynamic distribution around the target. Consequently, verifying the concordance of an experimental test with standard test criteria and defining accurate boundary conditions in correlated model simulations is challenging. In this study, the development of a novel method for the analysis of fire conditions based on image processing is presented. The approach allows identifying the flame coverage on the target surface during the test and provides an accurate map of the flame distribution on the equipment over time. The approach is tested using experimental data from a full-scale fire test campaign carried out on liquid hydrogen cryogenic tanks. The results prove to be accurate in replicating the experimental temperatures measured on the outer tank shell during the test. The proposed methodology can be used to better understand the results of experimental fire tests and to characterize realistic fire scenarios, also supporting the definition of fire test requirements. Moreover, the approach produces results that can be implemented as advanced space-time-varying boundary conditions in simulation models, improving their accuracy in reproducing real cases. KW - Fire test KW - Digital image processing KW - Flame coverage KW - Storage tank KW - Boundary conditions KW - Fire engulfment PY - 2025 UR - https://nbn-resolving.org/urn:nbn:de:kobv:b43-636956 DO - https://doi.org/10.1016/j.psep.2025.107571 SN - 0957-5820 VL - 201 IS - B SP - 1 EP - 15 PB - Elsevier Ltd. AN - OPUS4-63695 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Habib, Abdel Karim A1 - Kluge, Martin A1 - van Wingerden, Kees T1 - Untersuchung der Freisetzung von Flüssigwasserstoff auf und unter Wasser N2 - In einer Reihe von Experimenten wurden die möglichen Folgen der Freisetzung von verflüssigtem Wasserstoff (LH2) auf, bzw. unter Wasser untersucht. Die Experimente zielten darauf ab, eine unbeabsichtigte Freisetzung von LH2 (z.B. durch Schlauchabriss) insbesondere bei der Betankung eines Schiffes zu simulieren. Für verflüssigtes Erdgas (LNG) wurden dabei sog. RPT’s (rapid phase transition) nachgewiesen, bei denen die spontane Verdampfung relevante Druckwellen erzeugt. Es kann nicht ausgeschlossen werden, dass RPTs auch im Falle von LH2 möglich sind. Die Versuche wurden auf dem Testareal Wasserstoffsicherheit auf dem Testgelände Technische Sicherheit der Bundesanstalt für Materialforschung und -prüfung (BAM-TTS) in Horstwalde, im Rahmen einer Forschungskooperation zwischen der BAM und Gexcon im Rahmen des SH2IFT-Programms durchgeführt. Die LH2-Freisetzungen erfolgten direkt aus einem LH2-Tanklastwagen über eine lange, flexible, vakuumisolierte Transferleitung. Während die Freisetzung oberhalb und unterhalb der Wasseroberfläche jeweils vertikal orientiert war, wurde bei der Unterwasserfreisetzung zusätzlich eine horizontale Ausströmung, parallel zur Wasseroberfläche realisiert. Zur Bestimmung des Massenstromes, wurde ein Wägesystem unter dem Tankwagen eingesetzt. Spezielle Drucksensoren wurden verwendet, um die durch die Freisetzungsvorgänge erzeugten Stoßwellen sowohl im Wasser als auch in der Luft zu messen. Die Gaskonzentrationen über dem Wasserbecken wurden an verschiedenen Positionen gemessen. Hochgeschwindigkeits-, Infrarot- (IR) und normale Kameras wurden eingesetzt, um die Phänomenologie der Freisetzung aufzuzeichnen und das Verhalten der Gaswolke im Zeitverlauf zu verfolgen. Neben den fest installierten Systemen an Land, kamen auch Unterwasserkameras sowie eine Drohne mit Normal- und IR-Kameras zum Einsatz. Zwei Wetterstationen wurden zur Messung von Windgeschwindigkeit, Windrichtung, Temperatur und Luftfeuchtigkeit während aller durchgeführten Tests eingesetzt. Des Weiteren kamen Bolometer zur Wärmestrahlungsmessung zum Einsatz. Zwar führten die Freisetzung zu einer hochturbulenten LH2/Wasser Mischzone, jedoch zu keinen nennenswerten Überdrücken durch RPT. Im Gegensatz dazu wurde unerwartet, aber reproduzierbar, eine Zündung der Gaswolke in freier Luft in einiger Entfernung von den Instrumenten und dem Ort der Freisetzung beobachtet. Die daraus resultierenden Gaswolkenexplosionen führten zu relevanten Überdrücken und zur Wärmeabstrahlung in die Umgebung. T2 - Magdeburg-Köthener Brandschutz- und Sicherheitstagung 2024 CY - Magdeburg, Germany DA - 14.03.2024 KW - Flüssigwasserstoff KW - LH2 KW - Freisetzung KW - RPT KW - Gaswolkenexplosion PY - 2024 SN - 978-3-948749-42-2 SP - 127 EP - 136 CY - Magedburg AN - OPUS4-59709 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - Bernardy, Christopher A1 - Habib, Abdel Karim A1 - Kluge, Martin A1 - Schalau, Bernd A1 - Kant, Hanjo A1 - Schulze, Marcel A1 - Orchini, Alessandro T1 - Large-scale investigations of the thermal radiation of hydrogen jet flames N2 - For industrial applications dealing with hydrogen, the definition of safety distances and the assessment of possible hazards emanating from releases is mandatory. Since hydrogen is usually stored and transported under pressure, one scenario to be considered is the momentum driven release of hydrogen from a leakage with subsequent ignition. In this scenario, the emitted heat radiation from the resulting jet flame to the surroundings has to be determined to define adequate safety distances. For hydrocarbon flames, different jet flame models are available to assess the hazards resulting from an ignited jet release. Since hydrogen flames differ from hydrocarbon flames in their combustion behavior, it has to be checked if these models are also applicable for hydrogen. To evaluate the accuracy of these models for hydrogen jet flames, tests with a horizontal outlet at large-scale are carried out at the BAM Test Site for Technical Safety (BAM-TTS). Herein, the flame geometry and the heat radiation at defined locations in the surroundings are recorded for varying release parameters such as release pressure (currently up to max. 250 bar), mass flow (up to max. 0.175 kg/s) at an outlet diameter of 30 mm (with an upstream nozzle of 7.7 mm). The challenge here is the characterization of the flame geometry in an open environment and its impact on the thermal radiation. Existing heat radiation data from the literature are mostly based on unsteady outflow conditions. For a better comparability with the steady state jet flame models, the experiments presented here are focused on ensuring a constant mass flow over the release duration (currently 120 s) to obtain a stationary jet flame. In addition, stationary outflow tests with hydrocarbons (methane) were also carried out, which are intended to serve as reference tests for checking flame models based on hydrocarbon data. The comparison of the flame geometry shows that hydrogen jet flames with the same outlet mass flow have a greater flame length (average deviation of 15 %) but a smaller flame diameter than methane jet flames (average deviation of 17 %). Conclusions regarding thermal radiation show that the proportion of total combustion energy emitted as thermal radiation is lower for hydrogen (x_rad= 0.04–0.09) than for methane (x_rad = 0.06–0.1). A comparison of the surface emissive power (SEP) of the jet flame shows a SEP range of 7 kW/m2-15 kW/m2 for hydrogen and 3 kW/m2 - 9,5 kW/m2 for methane. KW - Hydrogen KW - Release KW - Thermal radiation KW - Jet flame KW - Radiant heat fraction PY - 2025 UR - https://nbn-resolving.org/urn:nbn:de:kobv:b43-622891 DO - https://doi.org/10.1016/j.jlp.2024.105491 SN - 1873-3352 VL - 94 SP - 1 EP - 6 PB - Elsevier B.V. AN - OPUS4-62289 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Bernardy, Christopher A1 - Habib, Abdel Karim A1 - Kluge, Martin A1 - Schalau, Bernd A1 - Schulze, Marcel A1 - Kant, Hanjo A1 - Orchini, Alessandro ED - Di Benedetto, Almerinda ED - Portarapillo, Maria T1 - Investigation of the thermal radiation from hydrogen jet flames N2 - For industrial applications dealing with hydrogen, the definition of safety distances and the assessment of possible hazards emanating from releases is mandatory. Since hydrogen is usually stored and transported under pressure, one scenario to be considered is the momentum driven release of hydrogen from a leakage with subsequent ignition. In this scenario, the emitted heat radiation from the resulting jet flame to the surroundings has to be determined to define adequate safety distances. For hydrocarbon flames, different jet flame models are available to assess the hazards resulting from an ignited jet release. Since hydrogen flames differ from hydrocarbon flames in their combustion behavior, it has to be checked if these models are also applicable for hydrogen. To evaluate the accuracy of these models for hydrogen jet flames, tests at real-scale are carried out at the BAM Test Site for Technical Safety (BAM-TTS). Herein, the flame geometry and the heat radiation at defined locations in the surroundings are recorded for varying release parameters such as leakage diameter (currently up to 30 mm), release pressure (currently up to max. 250 bar) and mass flow (up to max. 0.5 kg/s). The challenge here is the characterization of the flame geometry in an open environment and its impact on the thermal radiation. Existing heat radiation data from the literature are mostly based on unsteady outflow conditions. For a better comparability with the steady state jet flame models, the experiments presented here are focused on ensuring a constant mass flow over the release duration to obtain a (quasi) stationary jet flame. In addition, stationary outflow tests with hydrocarbons (methane) were also carried out, which are intended to serve as reference tests for checking flame models based on hydrocarbon data. T2 - 15th International Symposium on Hazards, Prevention and Mitigation of Industrial Explosions (ISHPMIE) CY - Neaples, Italy DA - 10.06.2024 KW - Hydrogen KW - Release KW - Jet flame KW - Thermal radiation PY - 2024 UR - https://nbn-resolving.org/urn:nbn:de:kobv:b43-605107 DO - https://doi.org/10.5281/zenodo.12515710 VL - 2024 SP - 1322 EP - 1333 PB - Zenodo CY - Geneva AN - OPUS4-60510 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Bernardy, Christopher A1 - Habib, Abdel Karim A1 - Kluge, Martin A1 - Schalau, Bernd A1 - Kant, Hanjo A1 - Schulze, Marcel A1 - Orchini, Alessandro ED - Nabizada, A. ED - Dechany, A. ED - B. Carré, B. ED - Stendardo, E. ED - Lappa, F. ED - Vanlaere, J. ED - Mendoza, M.J. ED - Dejonghe, M. ED - Daese, M. ED - Namazifard, N. ED - Jacops, R. ED - Jottrand, S. ED - Pahlavan, S. T1 - Real scale safety investigations of hydrogen jet flames at high pressure N2 - In order to reduce the human footprint of CO2 emissions and limit global warming effects hydrogen combustion is becoming increasingly important. To enable fuel cells and gas turbines to operates this carbon free fuel, unprecedently large amounts of hydrogen need to be produced and safely transported and stored. The investigation of the effects of accidents involving hydrogen is therefore becoming of outmost importance. Since hydrogen is usually stored and transported under pressure, one scenario to be considered is the release of hydrogen from a leakage with subsequent ignition. The resulting jet flame must be characterized with respect to the thermal radiation emitted into the environment to define safety regulations. Various models that characterize the resulting flame shape and radiation already exist in the literature, but these are mainly based on empirical data from hydrocarbon jet flames.[1-4] To verify these models, a H2 Jet Flame project conducted at BAM, is investigating the safety of momentum driven hydrogen jet flames. For this purpose, large-scale tests are carried out at the Test Site Technical Safety (BAM-TTS). The object of the investigations is to assess the effects of real scale release scenarios regarding flame geometry and the thermal radiation emitted. Parameters such as release angle, leakage diameter (currently 1 mm to 10 mm), pressure (currently up to max. 250 bar) and mass flow (up to max. 0.5 kg/s) are varied. In addition, influences such as the type of ignition, ignition location as well as delayed ignition can also be investigated. The gained knowledge will be compared with existing jet flame models, to validate these and identify a possible need for further development. In particular, the focus will be laid on the thermal radiation of hydrogen flames. The challenge here is the visualization and characterization of the flame geometry in an open environment. Visualization is performed using infrared (IR) camera systems from at least two viewing angles. Measurements of the heat radiation of jet flames, which can be found in the literature, are mostly based on unsteady outflow conditions. The experimental setup used here allows for the generation of a steady-state outflow for several minutes and thus a direct comparability with existing (steady-state) models. Furthermore, the tests can be carried out for comparative measurements with hydrocarbons (methane, etc.) as well as mixtures of hydrogen and hydrocarbons. T2 - European PhD Hydrogen Conference 2024 (EPHyC2024) CY - Gent, Belgium DA - 20.03.2024 KW - Thermal radiation KW - Release KW - Hydrogen KW - Jet flame PY - 2024 SP - 551 EP - 556 AN - OPUS4-59910 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - van Wingerden, K. A1 - Kluge, Martin A1 - Habib, Abdel Karim A1 - Skarsvag, H. L. A1 - Ustolin, F. A1 - Paltrinieri, N. A1 - Odsaeter, L. H. ED - Pierucci, S. ED - Klemes, J. J. T1 - Experimental Investigation into the Consequences of Release of Liquified Hydrogen onto and under Water N2 - Large-scale experiments have been performed to investigate the possible consequences of realistic amounts of liquified hydrogen (LH2) encountering water. The experiments aimed at simulating an accidental release of LH2 onto water, for instance during the fuelling of a ship. For liquified natural gas (LNG), it has been demonstrated that physical explosions may occur when it is spilled onto water. These phenomena are referred as rapid phase transitions (RPTs). It cannot be excluded that RPTs are also possible in the case of LH2. The tests were performed at the Test Site Technical Safety of the Bundesanstalt für Materialforschung und –prüfung (BAM) in Horstwalde, Germany. The tests were performed in a 10 m x 10 x 1.5 m basin filled with water. LH2 releases of up to about 1 kg/s were established releasing directly from a trailer carrying LH2. The releases occurred from a height of 50 cm above the water surface pointing downwards, 30 cm under the water surface pointing downwards and 30 cm under the water surface pointed along the water surface. All release configurations resulted in a very chaotic LH2-water mixing zone, causing considerable evaporation and resulting in minor over pressures. No RPTs were observed. The main phenomenon to be observed is, however, an ignition of the released gas cloud resulting in significant blast wave overpressures and heat radiation to the surroundings. The ignition occurred in all under-water releases and in about 90 % of the releases above the water surface. T2 - 17th EFCE International Symposium on Loss Prevention and Safety Promotion in Process Industries CY - Prague, Czech Rebpublic DA - 05.06.2022 KW - Liquid Hydrogen KW - LH2 KW - Release KW - RPT KW - Rapid Phase Transition PY - 2022 DO - https://doi.org/10.3303/CET2290091 SN - 2283-9216 VL - 90 SP - 541 EP - 546 PB - AIDIC CY - Milano AN - OPUS4-55324 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - van Wingerden, K. A1 - Kluge, Martin A1 - Habib, Abdel Karim A1 - Ustolin, F. A1 - Paltrinieri, N. ED - Pierucci, S. ED - Klemes, J. J. T1 - Medium-scale tests to investigate the possibility and effects of BLEVEs of storage vessels containing liquified hydrogen N2 - Experiments have been performed to determine the consequences of a storage vessel containing liquified hydrogen (LH2) is engulfed by a fire. The tests were performed at the Test Site Technical Safety of the Bundesanstalt für Materialforschung und –prüfung (BAM) in Germany within a research cooperation between BAM and Gexcon as part of the SH2IFT program. Three tests were performed using double-walled vacuum insulated vessels of 1 m3 volume varying the orientation of the vessel and the effect of the insulation material used (perlite or multi-layer insulation (MLI)). The degree of filling of the vessel was approximately 35 % in each of the tests performed. The fire load was provided by a propane fed burner positioned under the storage vessel and designed to give a homogeneous fire load. In one of the tests a rupture of the storage vessel occurred causing a blast, a fireball and fragments. Apart from measuring these consequences, the conditions in the vessel (e.g. temperatures and pressure) during the heating process were monitored in all three tests. The work described was undertaken as part of the project Safe Hydrogen fuel handling and Use for Efficient Implementation (SH2IFT). T2 - 17th EFCE International Symposium on Loss Prevention and Safety Promotion in Process Industries CY - Prague, Czech Republic DA - 05.06.2022 KW - Liquid hydrogen KW - LH2 KW - BLEVE KW - Cryogenic tank PY - 2022 DO - https://doi.org/10.3303/CET2290092 SN - 2283-9216 VL - 90 SP - 547 EP - 552 PB - AIDIC CY - Milano AN - OPUS4-55323 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Kluge, Martin A1 - Habib, Abdel Karim A1 - van Wingerden, Kees ED - Beyer, Michael ED - Lucassen, Arnas T1 - Large-scale tests to investigate the consequences of exposing cryogenic storage vessels containing liquid hydrogen to a fire load N2 - Large Scale Experiments have been performed to determine whether a storage vessel containing liquid hydrogen (LH2) and caught in a fire engulfing the vessel can result in a BLEVE (Boiling Liquid Expanding Vapour Explosion) and if so its consequences. The tests were performed at the Test Site Technical Safety of the Bundesanstalt für Materialforschung und –prüfung (BAM) in Germany at the Hydrogen Test Area (H2TA) within a research cooperation between BAM and Gexcon as part of the SH2IFT program. Three tests were performed using double-walled vacuum insulated vessels of 1 m3 volume. The cylindrical Vessels differed in orientation (horizontal or vertical) and the insulation material used (perlite or multi-layer insulation (MLI)). The degree of filling of the vessels was approximately 35-40 % in each of the tests performed. The fire load was provided by a propane fed burner-system positioned under the storage vessel and designed to give a homogeneous fire load. The conditions in the vessel (temperatures and pressure) as well as external effects (heat radiation, blast waves, flame ball development and fragmentation) were measured. All vessels were equipped with K-type thermocouples at several locations at the inner and outer vessel shell. The pressure inside the inner vessel and in the space between the inner and outer vessels (vacuum pressure) was measured. Bolometers were used to measure the heat radiation generated by both the propane fire and that generated by a possible fireball/BLEVE. To measure blast generated by the vessel burst/BLEVEs blast pencils were positioned at up to three locations. Further several cameras were used to monitor the events: normal cameras, infrared (IR)-cameras, high-speed cameras also on board of an UAV. Two of these vessels, a horizontal and a vertical vessel both insulated with perlite withstood the fire loading for 1 hour 20 minutes and 4 hours respectively without catastrophic failure. A horizontal vessel insulated with MLI failed by bursting after 1 hour and 6 minutes resulting in a fireball, fragments, and blast wave. T2 - 14th International Symposium on Hazards, Prevention and Mitigation of Industrial Explosions CY - Braunschweig, Germany DA - 11.07.2022 KW - Prevention KW - Industrial explosions KW - BLEVE KW - LH2 KW - Fire ball KW - Fragments PY - 2022 DO - https://doi.org/10.7795/810.20221124 SP - 168 EP - 181 AN - OPUS4-59440 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Kluge, Martin A1 - Habib, Abdel Karim A1 - van Wingerden, Kees T1 - Unterfeuerung von Flüssigwassersttofftanks - Topologie eines kritischen Behälterversagens N2 - In einer Versuchsreihe im Realmaßstab wurden drei Flüssigwasserstofftanks (LH2) unterfeuert. Hierbei sollte unter anderem geklärt werden, ob es, analog zu druckverflüssigten Gasen, zu einem BLEVE (Boiling Liquid Expanding Vapor Cloud Explosion) kommen kann. Die Experimente wurden auf dem Testareal Wasserstoffsicherheit des Testgeländes Technische Sicherheit der Bundesanstalt für Materialforschung und -prüfung (BAM-TTS) im Rahmen einer Forschungskooperation zwischen der BAM und Gexcon, als Teil des SH2IFT-Programms durchgeführt. Es handelte sich um doppelwandige, vakuumisolierte Tanks von 1 m³ Volumen. Die zylindrischen Tanks unterschieden sich durch ihre Ausrichtung (horizontal oder vertikal) und das verwendete Isoliermaterial (Perlit oder Mehrschichtisolierung (MLI). Der Füllgrad der Tanks betrug bei jedem der durchgeführten Tests etwa 35-40 %. Die Brandlast wurde homogen durch ein propangasbetriebenes Brennersystem erzeugt. Gemessen wurden die Bedingungen im Behälter (Temperaturen und Druck) sowie äußere Randbedingungen und Auswirkungen beim Versagen (Wärmestrahlung, Druckwellen, Flammenballentwicklung und Fragmentierung). Mit Bolometern wurde die Wärmestrahlung gemessen, die sowohl durch das Propanfeuer als auch durch einen möglichen Feuerball/BLEVE erzeugt wurde. Zur Messung der durch das Bersten von Behältern/BLEVEs erzeugten Druckwellen wurden sog. Pencil-Probes verwendet. Des Weiteren wurden mehrere Kameras zur Überwachung der Experimente eingesetzt: Normalbildkameras, Infrarot (IR)-Kameras und Hochgeschwindigkeitskameras, sowohl bodengestützt als auch mittels einer Drohne. Zwei der untersuchten Tanks, ein horizontaler und der vertikale, die beide mit Perlit isoliert waren, hielten der Brandbelastung stand, ohne dass es zu einem Behälterversagen kam. Der mit MLI isolierte horizontale Behälter barst nach 1 Stunde und 6 Minuten und erzeugte dabei einen Feuerball, Trümmerflug und eine Druckwelle. Neben der Beschreibung der Auswirkungen eines kritischen Versagens eines LH2-Tanks sind weitere Ziele der Arbeit die Identifizierung kritischer Behälterzustände sowie die Erstellung eines umfassendes Datensatzes der Trümmer des geborstenen Tanks. Die größten Abstände für kritische Abstände ergaben sich durch Fragmentwurf. Hier sollen 3D-Scans für die Verwendung in CAD und FEM Anwendungen bereitgestellt werden. Umfassende Daten zu den Fragmentwurfweiten, -massen und -positionen wurden bereits publiziert. Damit soll die Voraussetzung geschaffen werden, um vorhandene Wurfweitenmodelle, die bisher nur für einschalige Behälter konzipiert wurden auf ihre Eignung für mehrschalige Behälter zu überprüfen oder mögliche Anpassungen anhand der realen Daten vornehmen zu können. Zudem wurde damit begonnen die nicht geborstenen Tanks zu vermessen und zu zerlegen, um u.a. die Perlit-Schüttung auf Beeinträchtigungen durch den Transport und die Unterfeuerung zu untersuchen. T2 - Magdeburg-Köthener Brandschutz- und Sicherheitstagung 2024 CY - Magdeburg, Germany DA - 14.03.2024 KW - LH2 KW - Flüssigwasserstoff KW - Bleve KW - Tank KW - Bersten KW - Unterfeuerung PY - 2024 SN - 978-3-948749-42-2 SP - 117 EP - 126 CY - Magdeburg AN - OPUS4-59711 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Kluge, Martin T1 - Consequences of exposing cryogenic storage vessels containing liquid hydrogen to a fire load N2 - Experiments have been performed to determine whether a storage vessel containing LH2 and caught in a fire engulfing the vessel can result in a BLEVE (Boiling Liquid Expanding Vapour Explosion) and if so its effects. The tests were performed at the Test Site Technical Safety of the Bundesanstalt für Materialforschung und –prüfung (BAM) in Horstwalde, Germany. Three tests were performed using double-walled vacuum insulated vessels of 1 m3 volume. The cylindrical Vessels differed in orientation (horizontal or vertical) and the insulation material used (perlite or multi-layer insulation (MLI)). The degree of filling of the vessels was approximately 35-40 % in each of the tests performed. The fire load was provided by a propane fed burner positioned under the storage vessel and designed to give a homogeneous fire load. The conditions in the vessel (temperatures and pressure) as well as external effects (heat radiation, blast waves, flame ball development and fragmentation) were measured. All vessels were equipped with K-type thermocouples at several locations: inside the inner vessel in the gas phase and the liquid phase, on the inner and outer side of the inner vessel and on the inner and outer side of the outer vessel. The pressure inside the inner vessel (both in liquid, as a level indicator, and gaseous phase), and in the space between the inner and outer vessels (vacuum pressure) was measured. Bolometers were used to measure the heat radiation generated by both the propane fire and that generated by a possible fireball/BLEVE. To measure blast generated by the vessel burst/BLEVEs blast pencils were positioned at three locations in two directions. Weather conditions were monitored at two weather stations. Further several cameras were used to monitor the events: normal cameras, infrared (IR)-cameras, high-speed cameras also on board of a drone. Two of these vessels, a horizontal and a vertical vessel both insulated with perlite withstood the fire loading for 1 hour 20 minutes and 4 hours respectively without catastrophic failure. A horizontal vessel insulated with MLI failed by bursting after 1 hour and 6 minutes resulting in a fireball, fragments, and blast waves. T2 - 14th International Symposium on Hazards, Prevention, and Mitigation of Industrial Explosions (ISHPMIE) CY - Braunschweig, Germany DA - 11.07.2022 KW - Liquid Hydrogen KW - LH2 KW - BLEVE KW - Cryogenic Tank PY - 2022 AN - OPUS4-55355 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER -